F3 FASEALERT-3 MANUAL
Typical example of connection
M
= Contactor
OL
= Overload relay
F
= Fuse 2 Amp. Max.
A
= Alarm indicator lamp
C
M
M
A
M
M
MOTOR
FASEALERT-3
L1
L2
L3
START
STOP
OL
NC
NO
OL
OL
L2
L3
L3
L1
L2
L3
F
F
F
F
OL
M
Connect the terminals L1, L2 and L3 ,through the fuses, to the motor contactor and the terminals C and NO with
#14 gauge, 600 V wire. The FASEALERT-3 may be installed in THREE PHASE MOTORS OF ANY CAPACITY AND IN
ALL TYPES OF STARTERS. The diagram shown below is a common example of installation.
When the NO and C contact closes, it allows the motor to start running. When it opens, it disconnects the coil and
stops the motor. An indicator lamp may be used as an alarm as indicated in the diagram below.
Dimensions
1.77(45)
3
(77)
4.44(113)
4.68(119)
in (mm)
DANGER!
Potentially hazardous voltages are present. Electrical
shock can cause death or serious injury.
Installation should be done by qualified personnel
following all National, State & Local Codes.
BE SURE TO REMOVE ALL POWER SUPPLYING THIS
EQUIPMENT BEFORE CONNECTING OR DISCONNECTING
THE WIRING.
READ THE INSTRUCTIONS BEFORE INSTALLING OR
OPERATING THIS DEVICE.
KEEP THIS MANUAL FOR FUTURE REFERENCE.
OL