background image

 

INSTALLATION, USE AND SERVICE    

 

 

INSTRUCTIONS

SAUNA WOODBURNING STOVES 
– MIRVA, STEAMMASTER, NARVI 30 AND NARVI 50.

SAFETY DISTANCES

Prior to installation of the sauna woodburning stove, ensure the required safety 
distances to combustible structures are observed. For woodburning stoves the safety 
distances are 500 mm to the sides and rear and 1,200 mm overhead. A min. 70 mm 
thick concrete slab or a NARVI installation base should be installed beneath the 
woodburning stove. For any further queries regarding fire safety, please contact your 
local fire authority for assistance.

Note! If the sauna woodburning stove is installed above under-floor heating,  
a NARVI installation base must always be used.

GB

Combustible components 
(wooden walls, benches etc.)

1. Distance to wooden components from vertical 
sides of sauna woodburning stove without heat 
shield min. 500 mm. (Figure 1)

2. The safety distance stated in section 1 
(500 mm) can be reduced by half to 250 mm if 
so-called light, single-layer thermal protection 
is installed. A single-layer, light thermal shield 
can be made from min. 7 mm thick fire-resistant 
fibre-reinforced cement board or from min. 1 mm 
 thick metal sheet which has been fixed 
sufficiently tightly to the wall. A ventilation gap of 
30 mm must be left between the thermal shield 
and the wooden surface, e.g. using pipe sleeves. 
(Figure 2)

The heat shield must also be in non-contact 
with the floor or ceiling.

3. The safety distance mentioned in section 2 
can be further reduced by half (125 mm) if a 
double shield is installed. A double thermal 
shield can consist e.g. of two boards of the type 
recommended in section 2 if a ventilation gap of 
30 mm is left between the wall and the boards. 
(Figure 3)

30 mm ventilation gap

1 mm metal plate or 7 mm
incombustible fibre-reinforced
cement board

Figure 1

Figure 2

Figure 3

30 mm ventilation gap

1 mm metal plate or 7 mm
incombustible fibre-reinforced
cement board

Reviews: