3. Internal resistance and short circuit current
The internal resistance of the battery is a dynamic nonlinear parameter that is continuously
changed along with the temperature and discharge state. The internal resistance is the lowest
when battery is fully charged. The table 2-1 shows the internal resistance and short circuit
current in fully charged state
Table 2-1 Internal resistance and short circuit (25
℃
)
Type
Internal Resistance(mΩ)
Short Circuit Current (A)
MPG12V50F
8.39
1487
MPG12V65F
7.50
1720
MPG12V85F
6.79
1880
MPG12V100F
5.55
2290
MPG12V105F
5.45
2337
MPG12V125F
3.91
3151
MPG12V150F
4.55
3223
MPG12V150FA
3.91
3200
MPG12V150FB
4.00
2500
MPG12V155F
3.10
3230
MPG12V170F
3.03
3873
MPG12V200
2.83
4187
Note: Short circuit current will decrease the voltage of the battery to 0V, and damage the internal