Operation manual for Acme series V4.2
- 16 -
12NDT180
3.88
3200
12NDT190
3.98
3200
12NDT100A
6.31
1979
12NDT100S
5.50
2318
12NDT150S
5.17
2450
12NDT170S
4.63
2758
12NDT190S
4.276
2978
12NDT200S
4.27
2978
Note: Short circuit current will decrease the voltage of the battery to 0V, and damage the internal components of
the battery.
Chapter Three Operation and Maintenance
1.
Operation Conditions
Ambient temperature: Acme series optimum temperature is 15°C
~
25°C, the higher
and lower temperatures will impact battery performance
Operation temperature range
Operate status
Temperature range
Optimum
temperature
Discharge
-40°C
~
50°C
15°C
~
25°C
Charge
-20°C
~
50°C
15°C
~
25°C
Storage
-20°C
~
40°C
15°C
~
25°C
Ambient humidity
:
≤95
%
Cabinet ventilation conditions: meet the standard EN 50272-2:2001
2. Capacity and influence factors
2.1
The capacity of battery is the capacity that battery can be discharged under certain
conditions, expressed as signal C. The usual unit of capacity is ampere-hour,
shortened as Ah.
The capacity can be expressed in Rated Capacity or Actual Capacity. The Rated
Capacity please see Table 1-1. The Actual Capacity is the product of the discharge
current and the discharge time, the unit is Ah.
2.2
The Influence Factor of Actual Capacity
The actual capacity is mainly related with the battery’s construction, manufacturing