Napoleon StarFire GD70NT-S Installation And Operation Instructions Manual Download Page 11

11

W415-0434 / C / 03.24.05

FIGURE 14

OR

This application occurs
when venting through a
roof. Installation kits for
various roof pitches are
available from your Na-
poleon dealer. See Ac-
cessories to order the
specific kit required.

1.

Determine the air ter-

minal location, cut and
frame 9½ inch open-

ings in the ceiling and the roof to provide the minimum
clearance between the fireplace pipe / liner and any com-
bustible material. Try to center the exhaust pipe location
midway between two joist to prevent having to cut them.
Use a plumb bob to line up the center of the openings.
DO NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL.
A vent pipe shield will
prevent any materials
such as insulation,
from filling up the 1"
air space around the
pipe. Nail headers be-
tween the joist for ex-
tra support.

2.

Apply a bead of caulking (not supplied) to the framework

or to the Wolf Steel vent pipe shield plate or equivalent (in
the case of a finished ceiling), and secure over the open-
ing in the ceiling. A firestop must be placed on the bottom
of each framed opening in a roof or ceiling that the venting
system passes through. Apply a bead of caulking all around
and place a firestop spacer over the vent shield to restrict
cold air from being drawn into the room or around the fire-
place. Ensure that both spacer and shield maintain the
required clearance to combustibles. Once the vent
pipe / liner is installed in its final position, apply sealant
between the pipe / liner and the firestop spacer.

 3.

In the attic, after the pipe / liner

has been installed, slide the
vent pipe collar down to cover up
the open end of the shield and
tighten. This will prevent any ma-
terials, such as insulation, from
filling up the 1" air space around
the pipe.

*

 The 11½ inch framing dimension may be reduced to a

9½ inch opening if the vent length, from the fireplace to
the framed hole, is 24 inches or greater. If not, it is rec-
ommended to use a terminal extension plate, W500-0103,
when mounting the air terminal.

FIGURE 13

*

INSTALLATION

WALL AND CEILING PROTECTION

HORIZONTAL INSTALLATION

VERTICAL INSTALLATION

FIGURE 17

FIGURE 16

FIGURE 15

For optimum performance it is recommended that all
horizontal runs have a minimum ¼ inch rise per foot
using flexible venting.

For safe and proper operation of the fireplace, follow the
venting instructions exactly.

HORIZONTAL TERMINATION:  A clearance to combus-
tibles of 2" must be maintained during the first 24" of
venting when penetrating combustible walls. The
firestop spacer (GD-500.106 ) supplied with the unit
should be used to maintain this clearance. The first two
feet of outer 7" diameter vent pipe, from the appliance
must be wrapped in the 1 inch thick insulation sleeve
(supplied) as well as having a 1 inch air gap. Thereafter
a 1" clearance to combustibles may be maintained us-
ing firestop spacer (GD-500.96 for use with flexible vent-
ing or GD-500.136 for use with rigid venting).

VERTICAL TERMINATION:  Only a clearance to com-
bustibles of 1" all around the vent pipe is required.

HORIZONTAL INSTALLATION:

This application occurs when
venting through an exterior wall.

FIGURES 2a-d.

 Having deter-

mined the air terminal location,
cut and frame a hole in an exterior
wall with a minimum square or
round opening of 11½"

*

. (As an

alternative to framing, a vent pipe
shield may be installed, ensuring
a 1" clearance to combustibles.

Mark and cut the vent pipe shield to the determined depth
of the combustible wall. Apply a bead of caulking (not sup-
plied) to the framework or to the shield plate (in the case of
a finished wall) and secure the shield through the opening
to the interior wall. 

The final location of the vent pipe shield

should maintain the required clearance to the 7" vent
pipe / liner. Do not fill this cavity with any type of material.

Apply a bead of caulking all around and place a firestop
spacer over the vent shield to restrict cold air from being
drawn into the room or around the fireplace. Ensure that
both spacer and shield maintain the required clearance to
combustibles. Once the vent pipe / liner is installed in its
final position, apply sealant between the pipe / liner and
the firestop spacer.

Summary of Contents for StarFire GD70NT-S

Page 1: ...88 FOR VENTED GAS FIREPLACE HEATERS WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YOUR S...

Page 2: ...and draperies Clothing or other flammable material should not be placed on or near the fireplace Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace It i...

Page 3: ...ranty This limited warranty further does not cover any scratches dents corrosion or discolouring caused by excessive heat abrasive and chemical cleaners nor chipping on porcelain enamel parts mechanic...

Page 4: ...an only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas WARNING The door for this fireplace is sold separately The door must be installed and close...

Page 5: ...hat all horizontal runs have a minimum inch rise per foot horizontal runs have a minimum inch rise per foot horizontal runs have a minimum inch rise per foot horizontal runs have a minimum inch rise p...

Page 6: ...h formulas are met this vent configuration is ac ceptable FIGURE5 90 H1 V2 H2 V1 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT...

Page 7: ...1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4ft V2 1 5ft VT V1 V2 4 1 5 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft...

Page 8: ...or HT and VT when HT VT Simple venting configurations FIGURE 9 For vent configurations requiring more than zero 90 elbow top exit or one 90 elbow rear exit the following formu las apply Formula 1 HT V...

Page 9: ...8 1 ft HT HR HO 8 8 1 16 1 ft HT VT 16 1 4 5 20 6 ft Formula 1 HT 3VT 3VT 3 x 4 5 13 5 ft 16 1 13 5 Since this formula is not met this vent configuration is unacceptable Formula 2 HT VT 40 feet 20 6...

Page 10: ...pen Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to u...

Page 11: ...he air terminal FIGURE13 INSTALLATION WALL AND CEILING PROTECTION HORIZONTAL INSTALLATION VERTICAL INSTALLATION FIGURE17 FIGURE16 FIGURE15 For optimum performance it is recommended that all horizontal...

Page 12: ...oof support to the roof using the screws pro vided The roof support is optional In this case the venting is to be ad equately supported us ing either an alternate method suitable to the authority havi...

Page 13: ...e 7 inch diameter alu minum flexible liner to the fireplace Attach and seal the joints For optimum performance it is recommended that all horizontal runs have a inch rise per foot For safe and proper...

Page 14: ...me pattern and creat ing a more traditional appearance 1 Remove all obstructing obsta cles i e brick panels logs etc 2 Remove the baffle plate from the rear wall of the firebox exposing the two screws...

Page 15: ...d wall position the framework to accomodate the thickness of the finished wall MAINTAIN THESE MINIMUM CLEARANCES TO COM BUSTIBLES Fireplace framing 0 to stand offs top rear sides Fireplace finishing 3...

Page 16: ...the hinge screen into place and with the control door open secure to the firebox using three screws Remove the pro tective plastic wrap from the louvres and install as illus trated Clip each upper lo...

Page 17: ...he louvre tabs into the slots located at the top left and right corners of the unit A CLIPS CENTRE SLOT FLANGE SLOT TAB B C HINGE CLIP SLOT Before installing the logs you must first remove the log shi...

Page 18: ...be necessary however to install the fibre baffle on top of the side and rear panels Charcoal provided should be randomly placed in the trian gular trays on either side of the of the burner Log colour...

Page 19: ...he four screws that secure the lens frame This frame retains the glass lens The lamp can now be accessed Note Note Note Note Note Do not handle the lamp bulb with bare fingers Do not handle the lamp b...

Page 20: ...ng contact with any mo mo mo mo moving or hot objects ving or hot objects ving or hot objects ving or hot objects ving or hot objects Drywall dust will penetrate into the blower bearings Drywall dust...

Page 21: ...ng Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire de partment WARNING The gas valve has an inter...

Page 22: ...obstructed 1 In order to properly clean the burner and pilot assem bly remove the logs to expose both assemblies 2 Keep the control compartment logs burner air shut ter opening and the area surroundi...

Page 23: ...LOUVRE KIT BLACK 59 GDLVG UPPER LOWER LOUVRE KIT GOLD 60 L38K LOUVRE KIT UPPER LOWER BLACK 60 L38AB LOUVRE KIT UPPER LOWER ANTIQUE BRASS 60 L38PB LOUVRE KIT UPPER LOWER POLISHED BRASS 60 L38SS LOUVRE...

Page 24: ...24 W415 0434 C 03 24 05 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 25: ...me pattern around the thermocouple Pilot flame is not engulfing the thermocouple Thermocouple shorting faulty loosen and tighten thermocouple clean thermocouple and valve connection replace thermocoup...

Page 26: ...sulation is broken or frayed replace the electrode if the ceramic insulator is cracked or broken replace the push button ignitor No spark at pilot burner fill the tank Out of propane gas Spark gap is...

Page 27: ...27 W415 0434 C 03 24 05 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...