Napoleon Park Avenue GD82NT-PA Installation And Operation Instructions Manual Download Page 14

14

W415-0665 / B / 02.11.08

  7.

 Aligning the seams of the terminal and air terminal connector, 

place the terminal over the 
air terminal connector 
making sure the liner goes 
into the hole in the terminal. 
Secure with the three screws 
provided.

 8.

 Apply a heavy bead of 

weatherproof caulking 2” 
above the flashing. 

NOTE:

Maintain a minimum 2” 
space between the air inlet 
base and the storm collar. 
Install the storm collar 
around the air terminal 
connector and slide down to 
the caulking. Tighten to ensure that a weather-tight seal between 
the air terminal connector and collar is achieved.

FLASHING

CAULKING

2”

AIR INLET 
BASE

WEATHER 
SEALANT

STORM COLLAR

1.

 Install the 4” diameter flexible vent pipe to the fireplace. 

Secure with 3 screws 
and flat washers. Seal 
the joint and screw 
holes using the high 
temperature sealant 
W573-0007 (not 
supplied).

 2.

 Install the 7” 

diameter flexible vent 
pipe to the fireplace. 
Attach and seal the 
joints using high 
temperature sealant 
W573-0002 (not 
supplied).

#8 x 1/2”

SELF DRILLING

SCREWS

2” OVERLAP

HI-TEMP

SEALANT

FIREPLACE VENT CONNECTION

USING RIGID VENT COMPONENTS

HORIZONTAL AIR TERMINAL INSTALLATION

The vent system must be supported approximately every 3 feet 
for both vertical and horizontal runs. Use Wolf Steel vent spacers 
or equivalent every 3 feet and either side of each elbow to 
maintain the minimum 1¼” clearance between the outer and inner 
vent pipes. Use Wolf Steel support ring assembly or equivalent 
noncombustible strapping to maintain the minimum clearance to 
combustibles for both vertical and horizontal runs. 

All inner exhaust and outer intake vent pipe joists may be 
sealed using either red RTV high temp silicone sealant or 
black high temp Mill Pac with the exception of the fireplace 
exhaust flue collar which must be sealed using Mill Pac (not 
supplied).

EXTENDED HORIZONTAL AIR TERMINAL 

INSTALLATION

1.

 Move the 

fireplace into 
position. Measure 
the vent length 
required between 
terminal and 
fireplace taking 
into account the 
additional length 
needed for the 
finished wall 
surface and any 1¼” overlaps between venting components.

2.

 Apply high temperature sealant W573-0007 (not supplied) to 

the outer edge of the 4” inner collar of the fireplace.  Attach the 
first vent component and secure using 3 self tapping screws. 
Repeat using 7” piping.

3.

 Holding the air terminal insert the terminal into both vent pipes 

with a twisting motion to ensure that both the terminal sleeves 
engage into the vent pipes and sealant. Secure the terminal to the 
exterior wall and make weather tight by sealing with caulking 
W573-0002 (not supplied).

CAULKING

#10x2"

SCREWS

HI-TEMP

SEALANT

#8x½"

SCREWS

7" PIPE

2" OVERLAP

4" PIPE

  3.

 Install the air terminal. See 

item 3 of the Horizontal Air 
Terminal Installation. Extend the 
4” telescopic sleeve; connect to 
the air terminal assembly. Fasten 
with self tapping screws and seal. 
Repeat using the 7” telescopic 
sleeve.

VENTING

TELESCOPIC

SLEEVE

20"
COUPLER

AIR TERMINAL

  1.

 Follow the instructions for “Horizontal Air Terminal Installa-

tions”, items 1 to 3. 

  2.

 Continue adding components alternating inner and outer 

venting. Ensure that all 4” venting and elbows have sufficient vent 
spacers attached and each  component is securely fastened to 
the one prior. Attach the 4” telescopic sleeve to the vent run.   
Repeat using a 7” telescopic sleeve. Secure and seal as before. 
To facilitate completion, attach 4” and 7” couplers to the air 
terminal.

1.

Move the fireplace into position.

2.

 Fasten the roof support to the roof 

using the screws provided. The roof 
support is optional. In this case the 
venting is to be adequately supported 
using either an alternate method 
suitable to the authority having 
jurisdiction or the optional roof 
support.

3.

Apply high temperature sealant 

W573-0007 (not supplied) to the outer 
edge of the inner pipe of the air 
terminal connector. Slip a 4" diameter 
coupler a minimum of 2" over the pipe 
and secure using 3 screws. 

4.

Apply high temperature sealant 

W573-0007 (not supplied) to the outer 
edge of the of the outside pipe of the air 
terminal connector. Slip a 7" diameter 
coupler over the pipe and secure as before. 
Trim the 7" coupler even with the 4" coupler 
end.

5.

 Thread the air terminal pipe assembly 

down through the roof  support and attach, 
ensuring that a minimum 16" of air terminal 
will penetrate the roof when fastened. If the 
attic space is tight, we recommend threading the Wolf Steel vent 
pipe collar or equivalent loosely onto the air terminal assembly as 
it is passed through the attic. The air terminal must be located 
vertically and plumb. 

6.

 Remove nails from the shingles, above and to the sides of the 

chimney. Place the flashing over the air terminal and slide it 
underneath the sides and upper edge of the shingles. Ensure that 
the air terminal is properly centered within the flashing, giving a 
3/4" margin all around. Fasten to the roof. Do NOT nail through 
the lower portion of the flashing. Make weather-tight by sealing 
with caulking. Where possible, cover the sides and top edges of 
the flashing with roofing material.

4” RIGID VENT 

PIPE

7” RIGID 

VENT PIPE

INNER

PIPE

HIGH

TEMPERA-

TURE

SEALANT

AIR

TERMINAL

CONNECTOR

VENT PIPE

SHIELD

VENT

PIPE

COLLAR

VERTICAL VENTING INSTALLATION

FIGURE 23

FIGURE 24

FIGURE 25

FIGURE 26

FIGURE 22c

FIGURE 27

Summary of Contents for Park Avenue GD82NT-PA

Page 1: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions I...

Page 2: ...e fireplace Due to high temperatures the fireplace should be located out of traffic and away from furniture and draperies Ensure you have incorporated adequate safety measure to protect infants toddle...

Page 3: ...ivolt components and wearable parts such as blowers gas valves thermal switch switches wiring remote controls ignitor gasketing and pilot assembly are covered and NAPOLEON will provide replacement par...

Page 4: ...4 W415 0665 B 02 11 08 FIGURE 1 22 1 8 21 4 DIA 7 DIA 17 3 4 13 7 8 28 14 7 8 46 58 2 8 7 8 28 37 5 8 24 5 GAS INLET INSTALLATION OVERVIEW FIGURE 2 FIREPLACE DIMENSIONS...

Page 5: ...or both natural gas and propane When the fireplace is installed at elevations above 4 500ft and in the absence of specific recommendations from the local authority having jurisdiction the certified hi...

Page 6: ...t GD330 These vent kits allow for either horizontal or vertical venting of the fireplace The maximum number of allowable 4 vent connections is three horizontally or vertically excluding the fireplace...

Page 7: ...oth formulas are met this vent con guration is acceptable FIGURE 6 90 90 90 H1 V2 H2 V1 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT...

Page 8: ...HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 ceptable Example 3 V1 4 ft V2 1 5 ft VT V1 V2 4 1 5 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 3...

Page 9: ...quired vertical rise VT for the required horizontal run HT VERTICAL TERMINATION The shaded area within the lines represents acceptable values for HT and VT V1 5 ft V2 6 ft V3 10 ft VT V1 V2 V3 5 6 10...

Page 10: ...90 03 90 90 90 90 90 8 1 ft HT HR HO 8 8 1 16 1 ft HT VT 16 1 4 5 20 6 ft Formula 1 HT 3VT 3VT 3 x 4 5 13 5 ft 16 1 13 5 Since this formula is not met this vent con guration is unacceptable Formula 2...

Page 11: ...11 W415 0665 B 02 11 08 MINIMUM AIR TERMINAL LOCATION CLEARANCES GD 301 FIGURE 14...

Page 12: ...HE CAVITY BETWEEN THE PIPE AND THE FIRESTOP SLEEVE WITH ANY TYPE OF MATERIAL VERTICAL INSTALLATION 1 Determine the air terminal location cut and frame 9 3 4 openings in the ceiling and the roof to pro...

Page 13: ...pe Use only approved flexible vent pipe kits marked 1 Move the fireplace into position 2 Fasten the roof support to the roof using the screws provided The roof support is optional In this case the ven...

Page 14: ...ather tight by sealing with caulking W573 0002 not supplied CAULKING 10x2 SCREWS HI TEMP SEALANT 8x SCREWS 7 PIPE 2 OVERLAP 4 PIPE 3 Install the air terminal See item 3 of the Horizontal Air Terminal...

Page 15: ...around the pipe Figure 27 Proceed once the vent installation is complete NOTE All gas connections must be contained within the fireplace when complete 1 Move the fireplace into position and secure to...

Page 16: ...e left clear to provide adequate clearance for the vent in this 14 wide area centered along the front of the fireplace No combustibles are allowed 22 1 2 3 1 2 MAXIMUM 58 1 4 14 MINIMUM 1 1 2 MAXIMUM...

Page 17: ...om the sides of replace opening 22 3 8 to the top of replace opening Combustible replace nishing 0 to rear and sides 2 all around the vent pipe 22 1 2 recessed depth 72 from bottom of unit to enclosur...

Page 18: ...under water Call a quali ed service technician IMMEDIATELY to have the replace inspected for damage to the electrical circuit IfaccesstothecontrolareaisnecessaryBEFOREINSTALLATION remove the access pa...

Page 19: ...riod on a low ame 3 2 1 HERRINGBONE PATTERN ILLUSTRATED 5 Rest the bottom edge of the rear panel on top of the rear portion of the air de ector at the back of the rebox and push into place The rear pa...

Page 20: ...the log sits on the screw and spacer 6 Finally align the rectangular peg on log 6 with the notch on the front right portion of the burner NOTE Decorative brick panels must be installed before the logs...

Page 21: ...ng irreparable damage Care must be taken to prevent drywall dust from coming into contact with the blower or its compartment Any damage resulting from this condition is not covered by the warranty pol...

Page 22: ...LOURED SIDE UP OPERATION FIGURE 55 SPARK MODULE BATTERY REPLACEMENT 1 Remove optional front Instructions on Pg 19 2 Tilt the control panel forward and remove allowing access to the electode box which...

Page 23: ...esired temperature to control the comfort level in the room 1 Press the ON OFF key on the transmitter it controls all functions of the remote The transmitter display will show all active icons on the...

Page 24: ...tteries are low no beep will be emitted from the receiver when it receives an ON OFF command This is an alert for the receiver that there s low battery When the batteries are replaced the beep will be...

Page 25: ...ing the gas knob cannot be turned from pilot to off unless the knob it depressed slightly 1 STOP Read the safety information on the operating la bel 2 Turn off all electric power to the replace 3 Turn...

Page 26: ...0 second total light up period is satisfactory If ignition takes longer consult your Napoleon dealer distributor 7 Check that the gasketing on the sides top and bottom of the door is not broken or mis...

Page 27: ...W175 0013 7 COUPLER 58 W175 0239 CONVERSION KIT NG TO LP 59 W175 0240 CONVERSION KIT LP TO NG 60 GD811 KT HERRINGBONE SANDSTONE BRICK KIT 61 W135 0148 ANDIRON 62 GD812 KT REFRACTORY PANEL KIT 63 RFK8...

Page 28: ...28 W415 0665 B 02 11 08 40 40 54 53 52 19 9 22 20 10 18 21 32 60 61 66 26 24 25 27 35 2 13 11 15 14 12 63 46 47 48 7 1 3 4 49 64 5 6...

Page 29: ...ern around the thermocouple Pilot ame is not engul ng the thermocouple Thermocouple shorting faulty loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple replace...

Page 30: ...r frayed replace the electrode if the ceramic insulator is cracked or broken replace the push button ignitor No spark at pilot burner ll the tank Out of propane gas Spark gap is incorrect spark gap sh...

Page 31: ...31 W415 0665 B 02 11 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Page 32: ...32 W415 0665 B 02 11 08 NOTES...