Napoleon GDIZC - P Installation And Operation Instructions Manual Download Page 6

6

W415-0223 / D / 01.12.04

Move the insert close to its final position inside the wood-
burning fireplace. This unit is equipped with 6 levelling
screws located as follows: two are on either side of the
circulation blower on the rear panel; four are located front
and back on either side beneath the log support. Level
using four of the levelling screws. See Figure 1a. Levelling
the unit will eliminate rocking or excessive noise when the
fan is in operation. Once the unit is level, move it partially
into place within the fireplace to allow for all connections to
be made. It is not practical to level the insert once the it has
been installed. Determine the required depth prior to in-
stalling the unit and adjust the four levelling screws accord-
ingly.

Chimney installation must conform to both national and
local code requirements. The chimney must be lined with
one 2" or 3" diameter liner for intake and one 3" diameter
liner for exhaust. The minimum and maximum vent lengths
are 10 and 35 feet respectively. Recommended Napoleon
kits come in 3 lengths:  While the liners must be continuous
from the fireplace to the terminal, to achieve the needed
length, they may be coupled, using an aluminium coupler,
provided installation is sealed & secured.

We recommend that exhaust vents that pass through
unheated  spaces,  such  as  a  garage  or  attic,  be
wrapped in a protective sleeve to minimize condensa-
tion and reverse flow symptoms. See Trouble Shooting
for details.
This unit is approved for use with a 2" liner for air intake
and  a  3"  liner  for  exhaust.  For  best  performance,
however, it is recommended to use two 3" liners.
If  a  2"  liner  is  used  for  the  intake,  it  is  necessary  to
adjust the primary air shutter. See "Air Shutter Settings"
on page 11.

1.  OUTSIDE:  Slip one

end of a liner a minimum
of 2" over one of the
collars of the terminal. Se-
cure using 3 screws. Then
seal the joint and screw
heads with high tempera-
ture sealant. Repeat with
the other liner.

NOTE: We recommend that the other end of the exhaust
liner be marked to eliminate the exhaust liner being con-
nected to the intake collar at the unit.

FIGURE 3

4. Detach the two screws from the back of the firebox and
remove the panel, as illustrated.

5. Reaching in through the insert, manoeuvre the vent con-
nection assembly through the openings in the firebox top,
taking care not to damage the gasket. In case of  a low
ceiling fireplace, the extension should be removed and
reinstalled after the vent connection is secured to the fire-
box. Attach the restrictor plate to the centre stud and se-
cure the assembly using the three studs and ¼-20 hex
nuts.

INSERT  VENT  CONNECTION

CHIMNEY  CONNECTION

FIGURE 4

VENT CONNECTOR

EXTENSION

RESTRICTOR
PLATE

STUDS

FIGURE5a-b

1-2" & 1-3" DOUBLE PLY ALUMINUM LINER-INLET  AND EXHAUST &
2-3" TO 2" REDUCER:
GDI-2320KT

VENT KIT 20FT

GDI-2325KT

VENT KIT 25FT

GDI-2335KT

VENT KIT 35FT

2-3" DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST:
GDI-320KT

VENT KIT 20FT

GDI-325KT

VENT KIT 25 FT

GDI-335KT

VENT KIT 35 FT

2. Gently stretch the liners to the required lengths and in-
sert into the chimney. Place the terminal onto the top of the
chimney cap and fit the flashing plate to suit.  Make weather
tight by sealing with caulking (not supplied) and fasten to
the chimney with screws and plugs (not supplied)
3.  INSIDE:  Attach and secure the flex liners to the vent
connection assembly using the same procedure as be-
fore, ensuring that the marked exhaust liner is attached
to the exhaust collar.

FIGURE 2

Summary of Contents for GDIZC - P

Page 1: ...r gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING If the information in these instructions is not fo...

Page 2: ...insert Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace insert It is imperative that the control compartments burners and circulating blower and its p...

Page 3: ...uires the prior approval of an authorized company official Labour costs to the account of to the account of to the account of to the account of to the account of NAPOLEON NAPOLEON NAPOLEON NAPOLEON NA...

Page 4: ...STALLER to con form with local codes Installation practices vary from re gion to region and it is important to know the specifics that apply to your area for example in Massachusetts State The firepla...

Page 5: ...the fireplace in a proper workman like manner This access hole must be plugged with non combustible in sulation after the gas supply line has been installed Ensure that existing chimney cleanouts fit...

Page 6: ...used for the intake it is necessary to adjust the primary air shutter See Air Shutter Settings on page 11 1 OUTSIDE Slip one end of a liner a minimum of 2 over one of the collars of the terminal Se cu...

Page 7: ...Any circulation air opening may be covered with non combustible material but not sealed The insert can be equipped with either a 3 or 4 sided trim kit to finish off the fire place opening Slide the tr...

Page 8: ...ate the clearance needed 4 Tear the glowing embers into pieces and place along the front row of ports covering all of the burner area in front of the logs Care should be taken to shred the embers into...

Page 9: ...you cannot reach your gas supplier call the fire depart ment When lighting and re lighting the gas knob cannot be turned from pilot to off unless the knob is depressed slightly 1 Stop Read the above s...

Page 10: ...e blower into the clip C Secure to the threaded stud using the existing lock washer and wing nut Ensure that the blower does not touch the fireplace base or the firebox 6 Reconnect the two wires Holdi...

Page 11: ...ctor plate shown in FIGURE 6b Bend the flap up as shown to reduce the velocity of the exhaust gases slowing down the flame pattern and creating a more traditional appearance FIGURE29 Closing the air s...

Page 12: ...ts always give the follow ing information 1 MODEL SERIAL NUMBER OF FIREPLACE 2 INSTALLATION DATE OF FIREPLACE 3 PART NUMBER 4 DESCRIPTION OF PART 5 FINISH Contact your dealer for questions concerning...

Page 13: ...13 W415 0223 D 01 12 04 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 14: ...ner lights check the wires for defects and or replace wires Faulty valve replace check that the manual valve is turned on check the pilot orifice for blockage replace the valve call the gas distributo...

Page 15: ...lace glass cleaner DO NOT CLEAN GLASS WHEN HOT If deposits are not cleaned off regularly the glass may be come permanently marked Main burner goes out pilot goes out REFER TO MAIN BURNER GOES OUT PILO...

Page 16: ...16 W415 0223 D 01 12 04 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Reviews: