Napoleon BGD38NT Installation And Operation Instructions Manual Download Page 15

15

W415-0244 / A / 05.15.03

FIGURE 25

The vent system must be supported approximately every 3
feet for both vertical and horizontal runs. Use Wolf Steel
vent spacers every 3 feet and either side of each elbow to
maintain the minimum 1¼" clearance between the outer
and inner vent pipes. Use Wolf Steel support ring assem-
bly or equivalent noncombustible strapping to maintain the
minimum clearance to combustibles for both vertical and
horizontal runs.

1. Move the fireplace into position. Meas-

ure the vent length required between ter-
minal and fireplace taking into account
the additional length needed for the finished wall surface and
any 1¼" overlaps between venting components.

2. Apply high temperature sealant to the outer edge of the 5"

inner collar of the fireplace.  Attach the first vent component and
secure using 3 self tapping screws. Repeat using 8" piping.

3.  Holding the air terminal (with the air deflectors to the

top), insert into both vent pipes with a twisting motion to ensure
that both the terminal sleeves engage into the vent pipes and
sealant. Secure the terminal to the exterior wall and make
weather tight by sealing with caulking (not supplied).

The air terminal mounting plate may be recessed into the
exterior wall or siding by 1½", the depth of the return flange.

1. Follow the instructions for "Horizontal Air Terminal In-

stallations", items 1 to 3.

2.  Continue adding components alternating inner and

outer venting. Ensure that all 5" venting and elbows have
sufficient vent spacers attached and each  component is
securely fastened to the one prior. Attach the 5" telescopic
sleeve to the vent run.

Repeat using a 8" tel-
escopic sleeve. Secure
and seal as before. To
facilitate completion, at-
tach 5" and 8" couplers
to the air terminal.

3. Install the air terminal. See item 3 of

the Horizontal Air Terminal Installation.
Extend the 5" telescopic sleeve; connect
to the air terminal assembly. Fasten with
self tapping screws and seal. Repeat
using the 8" telescopic sleeve.

TELESCOPIC SLEEV

VENTING

20" 
COUPLER

AIR TERMINAL

FIGURE 26

Do  not nail through

the lower portion of the
flashing. Make
weather-tight by seal-
ing with caulking.
Where possible, cover
the sides and top
edges of the flashing
with roofing material.

6.  Apply a heavy

bead of weatherproof caulking 2 inches above the flash-
ing. Slide the storm collar around the air terminal and down
to the caulking. Tighten to ensure that a weather-tight seal
between the air terminal and the collar is achieved. Attach
the other storm collar centered between the air intake and
the air exhaust slots onto the air terminal. Tighten securely.
FIGURE 23. Attach the vertical rain cap.

Spacers are attached to the 5" inner flex liner at prede-
termined intervals to maintain a 1-1/4" air gap to the 8"
outer liner. These spacers must not be removed.

7. If more liner needs to be used to reach the fireplace,

follow the same procedure as found in EXTENDED HORI-
ZONTAL AIR TERMINAL INSTALLATION
. The vent system
must be supported approximately every 3 feet for both ver-
tical and horizontal runs. Use Wolf Steel support ring as-
sembly  or equivalent noncombustible strapping to main-
tain a clearance to combustibles.

1.  Install the 5 inch diameter aluminium flexible liner to

the fireplace. Secure with 3 screws and flat washers. Seal
the joint and screw holes using the high temperature seal-
ant provided. FIGURE 24.

2.  Install the 8 inch diameter aluminium flexible liner to

the fireplace. Attach and seal the joints.

FIGURE 24

FIGURE 23

FIREPLACE VENT CONNECTION

USING RIGID VENT COMPONENTS

HORIZONTAL AIR TERMINAL INSTALLATION

EXTENDED HORIZONTAL AND CORNER

AIR TERMINAL INSTALLATION

Summary of Contents for BGD38NT

Page 1: ...ANADA AND UNITED STATES USING ANSI CSA METHODS Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions i...

Page 2: ...inspect the fireplace and to replace any part of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replaceme...

Page 3: ...prior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to work however requires the prior approval of...

Page 4: ...35 BTU hr at an efficiency of 64 4 with the fan on and 17 212 BTU hr for propane at an efficiency of 66 2 with the fan on The maxi mum A F U E annual fuel utilization efficiency rating is 56 3 for nat...

Page 5: ...ength and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstructed and undamaged Purge all g...

Page 6: ...at open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance...

Page 7: ...ing v ting ver er er er ertically tically tically tically tically the v the v the v the v the ver er er er ertical rise is a tical rise is a tical rise is a tical rise is a tical rise is a minimum 36...

Page 8: ...is less than is less than is less than is less than horizontal horizontal horizontal horizontal horizontal run run run run run horizontal horizontal horizontal horizontal horizontal run verti run ver...

Page 9: ...ne 90 elbow FIGURE5 See graph to determine the required vertical rise VT for the required horizontal run HT For vent configurations requiring more than one 90 el bow the following formulas apply Formu...

Page 10: ...ore than one 90 elbow the following formulas apply Formula 1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4ft V2 1 5ft VT V1 V2 4 1 5 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4...

Page 11: ...s vent configuration is ac ceptable when Ht Vt Simple venting configurations FIGURE10 FIGURE11 For vent configurations requiring elbows the following for mulas apply Formula 1 HT VT Formula 2 HT VT 40...

Page 12: ...figuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 6 V1 1 5ft V2 5ft VT V1 V2 1 5 5 6 5 ft H1 1ft H2 1ft H3 1ft...

Page 13: ...installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE18 FORSAFEANDPROPEROPERATIONOFTHEFIREPLACE FOLLOW THE VENTING INSTRUCTIONS EXACTLY AHEATSHIELDMUSTBE...

Page 14: ...ts using the same procedure as described in points 2 and 3 The vent system must be sup ported approximately every 3 feet for both vertical and hori zontal runs Use Wolf Steel support ring assemblies o...

Page 15: ...uplers to the air terminal 3 Install the air terminal See item 3 of the Horizontal Air Terminal Installation Extend the 5 telescopic sleeve connect to the air terminal assembly Fasten with self tappin...

Page 16: ...ter edge of the of the outside sleeve of the air terminal Slip a 8 diameter coupler over the sleeve and secure as before FIG URE 27 Trim the 8 coupler even with the 5 coupler end 5 Thread the air term...

Page 17: ...and secure to the 2x4 framing The tabs will facilitate the installation of either a 3 4 or a 1 finished wall thickness The nailing tabs must not be removed Combustible mantle clearance can vary accor...

Page 18: ...he hinge screen into place and with the control door open secure to the firebox using three screws FIGURE35 LOUVRE BRACKET FIGURE36a UPPERLOUVREINSTALLATION A C B L38 LOUVRE INSTALLATION FIGURE 37 a c...

Page 19: ...op of the log should rest in the pocket on the back log LOG PLACEMENT 4 1 4 Position the notch located on the end of the center log 5 against the middle grate post with the other end of the log restin...

Page 20: ...h the connectors from the black and white wires to the thermodisc and se cure the thermodisc bracket to the securing stud at the bottom left of the unit using a lock washer and wing nut En sure that t...

Page 21: ...ed on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and for approximately 30 45 minutes after the fireplace has been turned off If...

Page 22: ...out any gas If you smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 D...

Page 23: ...ir shutter remove the two screws that se cure the cover to the air housing taking care not to dam age the gasket Adjust the pilot screw to provide properly sized flame Turn in a clockwise direction to...

Page 24: ...W135 0187 MIDDLE CROSSOVER LOG 5 19 W135 0188 RIGHT CROSSOVER LOG 6 20 W010 0811 BLACK DOOR C W GLASS 21 W455 0040 41 NATURAL GAS ORIFICE 21 W455 0003 54 PROPANE GAS ORIFICE 22 W500 0028 FIRESTOP SPAC...

Page 25: ...25 W415 0244 A 05 15 03 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 26: ...gas valve has an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correct...

Page 27: ...checked the same as above using screw B Gauge should read 3 5 water column for natural gas or 10 water column for propane Check that main burner is operating on HI AFTER TAKING PRESSURE READINGS BE SU...

Page 28: ...28 W415 0244 A 05 15 03 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Reviews: