W415-1345 / D / 05.01.17
EN
30
framing
STEEL HEADER
REQUIRED (SUPPLIED)
49"
124.5cm
(TOP EXIT)
(REAR EXIT)
1 1/2"
38mm
14"
35.6cm
17 1/4"
43.8cm
MAX
MIN
1 1/2"
38mm
MAX
40 3/4"
103.5cm
40 1/2"
102.9cm
40 1/2"
102.9cm
Combustion protrusions such as mantels and shelves may occur at or after a minimum distance of 2" (51mm)
away from the side of the appliance. Thereafter, the depth of any protrusions must be equal to or less than the
distance from the side of the appliance up to a depth of 6" (152.4mm), after which no greater clearance than 6"
(152.4mm) is required. This can be considered a side wall with no length boundary.
!
WARNING
•
For top exit applications, do not build in this area. It must be left clear to provide adequate clearance
for the vent. In this 14” (35.6cm) wide area centered along the front of the appliance, no combustibles
are allowed.
These appliances are supplied with two standoffs. For
convenience, the standoffs have been shipped fl at and located on
the top at the front. Before framing ensure the standoffs are bent
up and screwed into place ensuring a height of 4 1/2" (114.3mm).
NOTE: The information and dimensions in this section
represent the minimum clearances to combustible material.
It is best to frame your appliance after it is positioned and the vent
system is installed. Use 2x4's and frame to local building codes.
6.1 installing
stand-offs
6.2
minimum framing dimensions