StarLink
™
SLE Commercial Series Alarm Communicators -- Installation Instructions
Input Configuration Options
Option
Armed
Disarmed
Resend
TBL every
24 Hrs.
NOC Inputs
"Function"
Selection
Comments
Cut
Wire*
Open Short
Cut
Wire*
Open Short
1
FACP
with
DACT
Use IN2 or IN3 only for trouble.
Panel reports via dialer capture,
but Linecut reports via an input
on radio.
TBL
TBL
TBL
-
-
-
Yes
Supervised Fire
Trouble (Linecut)
Requires two EOLRs. Radio
reports in CID.
2
FACP
with
DACT
Use IN1 (not supervised) either
for trouble
or
alarm. Panel has
trouble (or alarm) relay that
closes on the condition.
-
TBL
(or
ALARM)
-
-
-
-
Yes
Un-Supervised
Fire Trouble (use
'User Defined'
selection for
Alarms)
Non-supervised (use conduit
activation re12V)
3
FACP
without
DACT
Use IN2 or IN3 for both Alarm
and Trouble on one input.
Panel has alarm and trouble
relay outputs.
TBL
TBL
ALARM
-
-
-
Yes
Supervised Fire
Alarm/Trouble
Requires two EOLRs. The
Trouble relay N.C. contact
(energized opens) is put in
series with one ELOR. Alarm
relay put across both EOLR
and trouble relay.
4
BURG
with
DACT
Use IN2 or IN3 for only trouble
reporting. Panel reports via
dialer capture but Linecut re-
ports via an input on radio.
ALARM
ALARM ALARM
TBL
TBL
TBL
No
Supervised Burg-
Linecut
Requires two EOLRs. Pro-
gram panel to report Open/
Close (radio remembers last
state of panel for Napco panels
when used with local download
cable).
5
BURG
without
DACT
Use IN2 or IN3 for both Alarm
and Trouble. Panel has alarm
and Trouble Relay/PGM out-
puts. Two EOLRs are needed
since for UL Burg it is required
to detect both wire breaks and
shorts.
ALARM
TBL
ALARM
TBL
TBL
TBL
No
Supervised Burg
Alarm/Trouble
Requires two 10K EOLRs.
Three off normal conditions
can be detected, namely, cut
wire, shorted loop and one of
the EOLR's having a closed
contact in series. The Trouble
relay N.C. contact (energized
opens) is put in series with one
ELOR. The Alarm relay N.O.
contact is put across both
EOLRs and trouble relay. The
panel Armed or Disarmed state
is determined by a separate
input (see Option 6 in this table
below for armed status opera-
tion). (
Note:
The Alarm relay
should NOT activate on 24hr
zones.)
6
BURG
without
DACT:
Armed
Status
Use IN2 or IN3 for Armed Sta-
tus input. Two EOLRs are
needed since for UL Burg it's
required to supervise for both
wire breaks and shorts.
TAMPER
ALARM
N/A
ALARM
TBL
N/A
TBL
No
Supervised Arm/
Disarm Status
Requires two 10K EOLRs. A
relay or PGM for Arm/Disarm
status goes in series with one
EOLR where open is disarmed
and closed is armed. The other
EOLR is across the series
combination (relay for Arm/
Disarm and first ELOR) to
provide the loop supervision.
Application
*Note: On line cut, PGM1 will activate.