StarLink™ Connect SLE-LTEV-C / SLE-LTEV-Z Alarm Communicators -- Installation Instructions
3
RED TROUBLE LED
Labeled
"
D5
", this LED is located at the bottom right of the
PC board. Operation is as follows:
1 Blink:
Low Aux Power input voltage
2 Blinks:
Battery trouble
3 Blinks:
Alarm report Failed to Communicate (will
restore only when both paths are operational)
4 Blinks:
RF trouble (antenna connection or cellular
registration)
5 Blinks:
Radio poll or check-in failure (radio only).
The unit must only fail on one path to trigger the trouble,
but for the trouble to clear, unit requires both IP and ra-
dio polling / checkins to be operational.
6 Blinks:
Unit disabled (reporting or control panel
downloading not allowed)
7 Blinks:
Unit was shutdown and has no functionali-
ty; requires a restart (full power down and full power up
sequence) to restore operation.
RED DIAGNOSTIC LED
Labeled
"
D7
", this LED is located in the middle of the PC
board. One blink indicates a weak or non-existent signal
from the network (green LED is off). If this red LED is
blinking in any other manner, please contact technical sup-
port.
NETWORK CONNECTION LEDs
Labeled "
DS14
" (green), "
DS15
" (yellow) and
"
DS16
" (red), these LEDs are located at the bottom
right of the PC board.
The green LED labeled "
DS14
" describes the IP network
connection type or the connection quality, as follows:
When
DS14
is off = No network cable detected
When
DS14
is flashing rapidly = No IP connection
(occurs just after power on while trying to obtain an IP
address; therefore has priority over any other green
flashing LEDs)
When
DS14
is flashing slowly = Normal operation:
1 Slow Blink:
Static IP Address (as programed by
the NOC)
2 Slow Blinks:
DHCP (default)
3 Slow Blinks:
Auto IP (if unable to acquire DHCP
address, after 5 minutes radio will convert to Auto IP.
The Yellow LED labeled "
DS15
" describes the status of
the IP network.
When
DS15
is off = No power
When
DS15
is on solid = IP reporting disabled
When
DS15
is flashing rapidly = Push button on Wi-Fi
module is being pressed
When
DS15
is flashing steady with 1 quick blink off eve-
ry 2 seconds = Reporting signal to NOC
When
DS15
is flashing steady with 2 quick blinks off
every 2 seconds = Downloading to control panel or the
module
LED LOCATIONS
D4: YELLOW OPERATIONAL STATUS
D3: GREEN RF SIGNAL STRENGTH
D5: RED TROUBLE
DS14: GREEN IP NETWORK TYPE OR QUALITY
DS15 YELLOW IP NETWORK STATE
DS16 RED IP NETWORK TROUBLES
DL: RED DIAGNOSTIC LED
Supervised Arm / Disarm Input
10K
10K
C
Open = Disarmed
Closed = Armed
The EOLR must be installed and located within the control panel housing.
Radio GND
(TB8)
(Radio)
(Alarm Panel)
8
7
9
-or-
To StarLink
Terminals
IN2 (TB7)
-or-
IN3 (TB9)
Supervised Fire / Burg Input
10K
10K
C
C
N/O
Alarm
N/O
TBL*
To StarLink
Terminals
IN2 (TB7)
-or-
IN3 (TB9)
Radio GND
(TB8)
The EOLR must be installed and located within the control panel housing.
(Radio)
(Alarm Panel)
8
7
9
-or-
N/C
*Reverse polarity / energized state.