StarLink
™
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions
3
triggered with N/O or N/C relay contacts. Wire the
common ground terminal
GND
(terminal
TB8
) to the
relay common. In Burglary applications, when used
as arm/disarm status input, a low indicates "armed"
and a high indicates "disarmed". For these inputs to
report to a central station, the radio must be config-
ured with the central station telephone number and
correct reporting formats and codes. See table on
page 17 for more information.
TB10: TIP:
See
TB11
, below.
TB11: RING:
Terminals
TIP
and
RING
: When used for
backup reporting, the house Tip and Ring telephone
wires must be routed from the outside to these ter-
minals. Under normal back up conditions, these
terminals are internally wired to the
PANEL TIP
and
PANEL RING
terminals, allowing all transmissions
to the central station to be monitored. These wires
are monitored for voltage such that if voltage falls
below 1.5V, a Telco Line Fault trouble is detected,
and the StarLink radio applies telephone line volt-
age to the control panel Tip and Ring DACT inter-
connect to the radio allowing it to receive and trans-
mit any alarms sent by the panel.
TB12: PANEL RING:
See wiring diagrams.
TB13: PANEL TIP:
See wiring diagrams.
Note:
TB14-TB17 no connections permitted by UL.
TB14: RTS (R):
See
TB17
below.
TB15: PANEL TX (B):
See
TB17
below.
TB16: PANEL RX (G):
See
TB17
below.
TB17: CTS (Y):
No connections permitted.
LED DESCRIPTIONS
The PC board contains several LED's, as follows:
GREEN RF SIGNAL STRENGTH LED
Labeled
"
D3
", this LED is located at the lower right corner
of the PC board.
Every 30 seconds, the StarLink radio receiver section
turns on and listens to the cell tower. Depending on the
TERMINAL DESCRIPTIONS
Configure all inputs and outputs using the Manage-
ment Center screen (located at www.napconoc.com).
Located at the bottom of the StarLink radio PC board, the
17 terminals are described as follows:
TB1: PWR (+12V)
Note:
Model
SLE-LTEV-CFB
is rat-
ed 12/24VDC input.
(Refer to section "
STEP 4: APPLY POWER
")
TB2: PWR GND (–)
(Refer to section "
STEP 4: APPLY POWER
")
TB3: PGM1 (–):
Open collector output. PGM1 is nor-
mally on (active low). When it is triggered (for ex-
ample, a trouble is detected) it becomes open col-
lector/high. To have a zone dedicated to an Star-
Link radio trouble, insert one side of the end of line
resistor into this PGM1 terminal, and wire the other
side of the resistor to the positive terminal of the
zone.
TB4: PGM2
(–):
Open collector output. This output is
defaulted as "Fail to Communicate", and is normally
open collector/high. When a report fails to com-
municate anywhere in the communications path, the
output is active low.
TB5: PGM3
(–):
Open collector output. This output is
defaulted as "Telephone Line Cut". When the tele-
phone line voltage is correct, the output is open col-
lector/high; when the telephone line voltage is too
low, the output is active low.
TB6: IN 1:
Active high input for wiring to the panel
bell output. When this input detects a pulsing tem-
poral 3 high, it sends a Fire alarm; a pulsing tem-
poral 4 (CO Alarm), a CO alarm is sent. When
used, these conductors must be run in conduit (max
20 feet for Commercial Fire, and 3 feet for Residen-
tial Fire).
Do not use for Burglary applications
.
TB7: IN
2:
See
TB9
, below.
TB8: GND:
Common ground terminal.
TB9: IN
3:
Both terminals
IN 2
and
IN 3
by default are
supervised end-of-line resistor inputs that can be
Supervised Fire / Burg Input
10K
10K
C
C
N/O
Alarm
N/O
TBL*
To StarLink
Terminals
IN2 (TB7)
-or-
IN3 (TB9)
Radio GND
(TB8)
The EOLR must be installed and located within the control panel housing.
(Radio)
(Alarm Panel)
8
7
9
-or-
Supervised Arm / Disarm Input
10K
10K
C
Open = Disarmed
Closed = Armed
The EOLR must be installed and located within the control panel housing.
Radio GND
(TB8)
(Radio)
(Alarm Panel)
8
7
9
-or-
To StarLink
Terminals
IN2 (TB7)
-or-
IN3 (TB9)
N/C
*Reverse polarity / energized state.