background image

StarLink

 SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 

triggered with N/O or N/C relay contacts.  Wire the 
common ground terminal 

GND

 (terminal 

TB8

) to the 

relay common.  In Burglary applications, when used 
as arm/disarm status input, a low indicates "armed" 
and a high indicates "disarmed".  For these inputs to 
report to a central station, the radio must be config-
ured with the central station telephone number and 
correct reporting formats and codes.  See table on 
page 17 for more information.   

TB10: TIP:

  See 

TB11

, below.

 

TB11: RING:

  Terminals 

TIP 

and 

RING

:  When used for 

backup reporting, the house Tip and Ring telephone 
wires must be routed from the outside to these ter-
minals.  Under normal back up conditions, these 
terminals are internally wired to the 

PANEL TIP 

and 

PANEL RING 

terminals, allowing all transmissions 

to the central station to be monitored.  These wires 
are monitored for voltage such that if voltage falls 
below 1.5V, a Telco Line Fault trouble is detected, 
and the StarLink radio applies telephone line volt-
age to the control panel Tip and Ring DACT inter-
connect to the radio allowing it to receive and trans-
mit any alarms sent by the panel. 

TB12: PANEL RING:

  See wiring diagrams. 

TB13: PANEL TIP:

  See wiring diagrams. 

 

Note:  

TB14-TB17 no connections permitted by UL. 

TB14: RTS (R):

  See 

TB17

 below. 

TB15:  PANEL TX (B):

  See 

TB17

 below. 

TB16: PANEL RX (G):

  See 

TB17

 below. 

TB17: CTS (Y):

  No connections permitted.   

 
 

LED DESCRIPTIONS 

 

The PC board contains several LED's, as follows: 

 

  GREEN RF SIGNAL STRENGTH LED

 

 Labeled 

"

D3

", this LED is located at the lower right corner 

of the PC board.   

 

Every 30 seconds, the StarLink radio receiver section 
turns on and listens to the cell tower.  Depending on the 

TERMINAL DESCRIPTIONS 

Configure all inputs and outputs using the Manage-
ment Center screen (located at www.napconoc.com).  

Located at the bottom of the StarLink radio PC board, the 
17 terminals are described as follows: 

 

TB1: PWR (+12V)

  

Note:

  Model 

SLE-LTEV-CFB

 is rat-

ed 12/24VDC input. 

 

(Refer to section "

STEP 4:  APPLY POWER

") 

TB2:  PWR GND (–)

 

 

(Refer to section "

STEP 4:  APPLY POWER

") 

TB3: PGM1 (–):

  Open collector output.  PGM1 is nor-

mally on (active low).  When it is triggered (for ex-
ample, a trouble is detected) it becomes open col-
lector/high.  To have a zone dedicated to an Star-
Link radio trouble, insert one side of the end of line 
resistor into this PGM1 terminal, and wire the other 
side of the resistor to the positive terminal of the 
zone.   

TB4: PGM2 

(–):

  Open collector output.  This output is 

defaulted as "Fail to Communicate", and is normally 
open collector/high.  When a report fails to com-
municate anywhere in the communications path, the 
output is active low.   

TB5: PGM3 

(–):

  Open collector output.  This output is 

defaulted as "Telephone Line Cut".  When the tele-
phone line voltage is correct, the output is open col-
lector/high; when the telephone line voltage is too 
low, the output is active low.   

TB6: IN 1:

  Active high input for wiring to the panel 

bell output.  When this input detects a pulsing tem-
poral 3 high, it sends a Fire alarm; a pulsing tem-
poral 4 (CO Alarm), a CO alarm is sent.  When 
used, these conductors must be run in conduit (max 
20 feet for Commercial Fire, and 3 feet for Residen-
tial Fire).  

Do not use for Burglary applications

.   

TB7: IN 

2:

  See 

TB9

, below. 

TB8: GND:

  Common ground terminal. 

TB9: IN 

3:

  Both terminals 

IN 2 

and 

IN 3

 by default are 

supervised end-of-line resistor inputs that can be 

Supervised Fire / Burg Input

 

10K

 

10K

 

C

 

C

 

N/O

 

Alarm

 

N/O

 

TBL*

 

To StarLink 
Terminals 
IN2 (TB7)  

-or- 

IN3 (TB9)

 

Radio GND 

(TB8)

 

 

The EOLR must be installed and located within the control panel housing. 

(Radio) 

 

(Alarm Panel)

 

-or- 

Supervised Arm / Disarm Input

 

10K

 

10K

 

C

 

Open = Disarmed 

Closed = Armed

 

The EOLR must be installed and located within the control panel housing. 

Radio GND 

(TB8)

 

(Radio) 

 

(Alarm Panel)

 

-or- 

To StarLink 
Terminals 
IN2 (TB7)  

-or- 

IN3 (TB9)

 

N/C

 

*Reverse polarity / energized state. 

Summary of Contents for SLE-LTEV-CB

Page 1: ...com Note Technical Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2018 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio c...

Page 2: ...structions Note Antennas are not Listed by UL For LTE radios where an External Antenna needs to be in stalled outside of the room in which the radio is installed maximum 30 meters 98 feet in Resident...

Page 3: ...c com Located at the bottom of the StarLink radio PC board the 17 terminals are described as follows TB1 PWR 12V Note Model SLE LTEV CFB is rat ed 12 24VDC input Refer to section STEP 4 APPLY POWER TB...

Page 4: ...rent due to the application such as when 24 hour standby time is required for Fire or CO the SLE ULPS R Charger Module accessory must be used to charge an additional battery and to supply the power fo...

Page 5: ...StarLink radio can also func tion as a backup to the existing telephone lines install jumper 3 in terminal block X5 When used as a backup communicator and when it senses telephone line trouble the Sta...

Page 6: ...receivers via TCP IP STARLINK RADIO RELATED EVENT REPORT CODES Contact ID by default EVENT AREA CONTACT ID CODE ZONE IN 1 Fire 0 E110 990 1A IN 2 Panic 0 E120 992 22 IN 3 Trouble 0 E300 993 F3 Low Ba...

Page 7: ...PGM activates the control panel zone and the panel generates a trouble that is sent to the central station All installations also require wiring an output from the control panel as follows With Gemin...

Page 8: ...he transformer compartment knockouts Keep all non power limited wiring separate from all power limited wiring inside the housing by 1 4 In addition maintain a minimum 1 4 separation of all primary wir...

Page 9: ...ng inside the housing by 1 4 Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the al...

Page 10: ...ther the TRF12 T123 16 5V 20VA transformer or the chas sis mounted 16 5VAC 20VA transformer Transformer optional Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink t...

Page 11: ...IP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional Transformer TELCO QUAD WIRE Optional When Power...

Page 12: ...nstructions for the GEMC F8ZCPIM as a Monitor Zone Only When PGM1 is wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with a 560ohm 1 2 watt min EOL resistor Connect PGM1 to the negative...

Page 13: ...Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer StarLink BATTERY RED BLACK Power Supply SLE ULP...

Page 14: ...TERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RIN...

Page 15: ...ring Diagram for PRIMARY Reporting Configuration GEM X255 GEM P9600 GEM P3200 Control Panels Use when telephone line is NOT available AUX POWER CONTROL PANEL HOUSING 13 14 15 16 17 18 19 20 21 22 26 2...

Page 16: ...GRAY GRAY Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity GRN RED YELLOW BLACK StarLink BATTERY RED BLACK Refer to section S...

Page 17: ...report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble Panel has alarm and Trouble Rel...

Page 18: ...wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper...

Page 19: ...3 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Ma...

Page 20: ...ompromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provid...

Reviews: