
2
StarLink
™
SLe-GSM and SLe-GSM-3/4G Series GSM Communicators Installation Instructions
Mounting: Two vertical slots for #8 hardware
Environmental
Operating Temperature: –10°C - 49°C (14°F - 120°F)
Humidity: 95% Non-Condensing
TERMINAL DESCRIPTIONS
Located at the bottom of the
SLe-GSM
PC board, the 17
terminals are described as follows:
TB1: PWR (+12V)
(Refer to section "
STEP 4: APPLY POWER
")
TB2: PWR GND (–)
(Refer to section "
STEP 4: APPLY POWER
")
TB3: PGM1 (–):
Open collector output. PGM1 is nor-
mally on (active low). When it is triggered (for ex-
ample, a trouble is detected) it becomes open col-
lector/high. To have a zone dedicated to an SLe-
GSM trouble, insert one side of the end of line re-
sistor into this PGM1 terminal, and wire the other
side of the resistor to the positive terminal of the
zone. The output can be re-configured to activate
on other conditions using the Management Center
screen (located at www.napconoc.com).
TB4: PGM2 (–):
Open collector output. This output is
defaulted as "Fail to Communicate", and is nor-
mally open collector/high. When a report fails to
communicate, the output is active low. The output
can be re-configured to activate on other condi-
tions using the Management Center screen
(located at www.napconoc.com).
TB5: PGM3 (–):
Open collector output. This output is
defaulted as "Telephone Line Cut". When the 24V
telephone line voltage is correct, the output is
open collector/high; when the telephone line volt-
age is too low, the output is active low. This out-
put can be re-configured using the Management
Center screen (located at www.napconoc.com).
TB6: IN 1 (B/F):
Active high input intended for wiring to
the control panel bell output. When this input de-
tects a steady high, it sends a burglary alarm;
when it detects a pulsing temporal high, it sends a
Fire alarm; when it detects the "CO Alarm" pat-
tern, a CO alarm is sent. For this input to report to
a central station, the SLe-GSM must be config-
ured with the central station telephone number
and correct reporting formats and codes.
When used as arm/disarm status input, a high in-
dicates "armed" and a low indicates "disarmed".
Note:
When using Napco Armed Lugs (E4 or
E15), do not use
IN 1
for armed status; instead,
use
IN 2
or
IN 3
.
TB7: IN 2:
See
TB9
, below.
TB8: GND:
Common ground terminal.
TB9: IN 3:
Both terminals
IN 2
and
IN 3
are, by default,
active low inputs. Use active low outputs to acti-
vate. For these inputs to report to a central sta-
tion, the SLe-GSM must be configured with the
Central station telephone number and correct re-
porting formats and codes. Jumpers 4 and 5 may
be used to make the
IN 2
and
IN 3
terminals su-
pervised end of line resistor inputs that can be
triggered with N/O or N/C relay contacts. Wire the
common ground terminal
GND
(terminal
TB8
) to
the relay common. When used as arm/disarm
status input, a low indicates "armed" and a high
indicates "disarmed".
TB10: TIP:
See
TB11
, below.
TB11: RING:
Terminals
TIP
and
RING
: When used for
backup reporting, the house tip and ring telephone
wires must be routed from the outside to these
terminals. Under normal back up conditions,
these terminals are wired to the panel tip and
panel ring terminals respectively, allowing all
transmissions to the central station to be moni-
tored. These wires are monitored for voltage such
that if voltage falls below 3V, a Telco Line Fault
trouble is detected, and the SLe-GSM applies
telephone line voltage to the control panel Tip and
Ring allowing it to receive and transmit any alarms
sent by the control panel.
TB12: PANEL RING:
See wiring diagrams.
TB13: PANEL TIP:
See wiring diagrams.
TB14: RTS (R):
See
TB17
below.
TB15: PANEL TX (B):
See
TB17
below.
TB16: PANEL RX (G):
See
TB17
below.
TB17: CTS (Y):
These terminals are wired to the
SLe-
DLEXT
download extender (see WI1950) to allow
control panel downloads of the GEM-X255, GEM-
P9600, GEM-P3200, GEM-P1664, GEM-P1632,
GEM-P816 and Freedom F-64 control panels
when the SLe-GSM is mounted remotely to the
control panel.
LED DESCRIPTIONS
The PC board contains several LED's, as follows:
GREEN RF SIGNAL STRENGTH LED
Labeled "D3", this LED is located at the lower right cor-
ner of the PC board.
Every 30 seconds, the SLe-GSM receiver section turns
on and listens to the cell tower. Depending on the sig-
nal strength detected, it will blink the Signal Strength
LED from 1 to 8 times, providing a signal strength indi-
cator that is updated constantly and is always dis-
played. Refer to Coverage Table below.
Operation
Signal strength (as received by the radio) is displayed
by this LED blinking 1 to 8 times at a constant rate (with
LED LOCATIONS
RED DIAGNOSTIC LED (Labeled "D7")
YELLOW OPERATIONAL STATUS LED (Labeled "D4")
GREEN RF SIGNAL STRENGTH LED (Labeled "D3")
RED TROUBLE LED (Labeled "D5")
D4 D3 D5