DESCRIPTION
This variable-purpose power supply is suitable for many differ-
ent applications for security, access control and CCTV system
accessories that need supplementary power. NP-LPS6-24VDC
power supply/charger converts low voltage AC input into 6VDC
or 12VDC (@ 1.5 amps or 24VDC @ 1A of continuous supply
current). See specifications that follow.
FEATURES
•
Dip switch selectable 6VDC-12VDC-24VDC.
•
1.5 amp continuous supply current at 6VDC-12VDC.
•
1A continuous supply current at 24VDC.
•
Filtered and electronically regulated output.
•
Built-in charger for sealed lead acid or gel type batteries.
•
Maximum charge current 300mA.
•
Automatic switchover to stand-by battery when AC Fails.
•
Circuit breaker battery protection (fused available).
•
AC input and DC output LED indicators.
•
Extremely compact design.
•
Includes battery leads.
Board dimensions: 70mm L x 60mm W x 40mm H
Voltage Output/Transformer Selection Table:
INSTALLATION INSTRUCTIONS
1. Mount NP-LPS6-24VDC in desired location / enclosure.
2.
Unit is factory set for 12VDC.
For 6VDC output dip switch
2 off, for 24VDC output dip switch 1 on.
3. Connect proper transformer to terminals marked [AC] (refer
to Voltage Output/Transformer Selection Table).
Use 18 AWG or larger for all power connections (Battery,
DC output).
Keep power limited wiring separate from non-power
limited wiring (115VAC / 60Hz Input, Battery
Wires). Minimum .25” spacing must be provided.
4. Devices to be powered should be connected to terminals
marked [+ DC] and [– DC] carefully observing polarity.
Note:
It is important to measure output voltage before con-
necting devices. This helps avoid potential damage.
5. Connect battery to terminals marked [BAT +] and [BAT –]
(battery leads included). Use two (2) 12VDC batteries con-
nected in series for 24VDC operation.
Note:
When batteries are not used, a loss of AC will result
in a loss of output voltage.
LED Diagnostics:
Terminal Identification:
R
333 Bayview Avenue
Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440
NP-LPS6-24VDC
LINEAR POWER SUPPLY
WI1325D 12/05
© NAPCO 2005
Red
(DC)
Green
(AC)
Power Supply Status
ON
ON
Normal operating condition.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged or no battery present.
Terminal
Legend
Function/Description
AC
Low voltage AC input (refer to voltage output/transformer
selection table).
+ DC -
6VDC-12VDC @ 1.5 amp continuous supply current.
24VDC @ 1A continuous supply current.
+ BAT -
Stand-by battery connections. Maximum charge rate
300mA.
Item
Description
Dimension Volume
Memo
1
Instruction Sheet
A4
1
2
Wire
18AWG 22cm
1
Red
3
Wire
18AWG 22cm
1
Black
4
Double Stick Foam Tape 60*20*7mm
1
APPENDIX LIST
Output
Voltage Selector
(DIP SWITCH)
Transformer
24VDC @ 1A continuous
supply current
1. ON
2. ON
P-TRF2450
12VDC @ 1.5 amp con-
tinuous supply current
1. ON
2. OFF
P-TRF1650
6VDC @ 1.5 amp con-
tinuous supply current
1. OFF
2. OFF
P-TRF1650
AC