The 

GEMC

-

WL

-

SMK 

and 

GEMC

-

WL

-

SMK

-

are high

-

quality photoelectric 

smoke detectors with integral supervised digitally

-

coded radio transmitters.  

During normal operation, when a detector is in standby mode and is within 
proper sensitivity limits, its green LED flashes once every 10 seconds.  As 
soon  as  smoke  is  detected,  the  detector  sounds  a  local  alarm  and  the 
transmitter  sends  an  alarm  signal  to  the  supervised  receiver  (operating 
frequency:  319.5Mhz).  The alarm signal is repeated as long as smoke is 
present.    A  restore  report  is  sent  when  the  smoke  detection  chamber 
clears.  Supervision status reports are sent from the detector every hour.

 

 

UL 864 COMPLIANCE

 

 

The 

GEMC

-

WL

-

SMK

-

2

  is  intended  for  use  with  GEMC  series  panel  in-

stallations Certified to UL 864 10th edition using firmware version 90.69 

or greater.  These versions of GEMC series panels will detect an inoper-

ative transmitter within 200 seconds and will annunciate/report the asso-

ciated supervisory trouble (E

-

04).  The 

GEMC

-

WL

-

SMK

-

2

 is also Certi-

fied for use in UL 864 9th edition versions of the previous GEMC series 

panels.  Do not use the 

GEMC

-

WL

-

SMK

 (without the "

-

2

") with installa-

tions  using  the  GEMC  panels  certified  with  UL  standard  UL  864  10th 

edition as this will cause supervisory troubles from the transmitter, gener-

ating  an  error  report  within  200  seconds  and  then  every  hour.    The 

GEMC

-

WL

-

SMK

 can be used in 9th edition installations that detect inop-

erative  transmitters  within  4  hours  and  can  also  be  used  with  UL  864 

10th edition installations when the AHJ approves 4

-

hour supervision with 

the  GEMC  control  panel  (versions  90.69  or  greater)  that  are  not  pro-

grammed for "

WL  Fire  200  Sec.  Supervision

".  

Note:

  Both model de-

tectors require at least one 

GEMC

-

RECV

 in the system.   

Note: 

 Coding 

switches are not required or used; each transmitter is assigned a unique 

identification  code  number  at  the  factory.    A  maximum  of  50  wireless 

devices are allowed per system.  These devices include the GEMC

-

WL

-

SMK

-

2, GEMC

-

WL

-

HEAT

-

2, GEMC

-

WL

-

WD2

-

2 and GEMC

-

WL

-

CO.  

 

Low Battery Warning

 

The smoke detector and transmitter are powered by one 3

-

volt lithium battery (supplied) that can power the unit for at 

least one year.  If battery voltage drops below normal, a low 

battery report is sent to the panel for a period of 48 hours; if 

the voltage is still below normal after this time, the detector 

sounder  will  chirp  and  its  red  LED  will flash  every  45  sec-

onds.  

Note: 

 Unit shuts down after 7 days.  A low

-

battery 

report is sent to the receiver with any status or alarm trans-

mission.    If  a  low

-

battery  condition  is  indicated,  always  re-

place battery.  

 

NOTE: 

Temperature  and  humidity  extremes  may  reduce 

the life of the battery.  The detector is designed to prevent 

re

-

mounting  to  the  mounting  plate  without  the  battery  in-

stalled.  

Use Only Battery Specified In Marking.  Use of A 

Different Battery May Have A Detrimental Effect On Detec-

tor Operation and may present a risk of fire, burns or explo-

sion

.   

CAUTION: 

  Do  not  recharge,  disassemble,  heat 

above  100°C  (212°F),  or  incinerate.    Dispose  of  used  bat-

teries  promptly  and  according  to  local  codes.    Keep  away 

from children.

 

Remove  the  mounting  plate.   

Remove  the 

mounting  plate  by  turning  the  plate  counter

-

clockwise and pulling it up.

 

Identify components.  

Examine the detector to 

identify the component locations.

 

Install  battery. 

Place one 3

-

volt lithium Duracell 

DL123A,  Varta/Power

-

One  model  CR123A  or 

Panasonic  CR123A  in  its  battery  compartment, 

observing correct polarity.  Install battery and enroll the 

detector into the control panel before mounting.  During 

power  up  and  status  initialization,  both  the  green  and 

red  LED's  blink  four  times  in  unison.    Then  press  the 

TEST 

button once to complete installation.

 

continued

 

 

1

 

 

2

 

 

3

 

LIFT TO  
REMOVE 
MOUNTING 
PLATE 

TWIST 

MOUNTING 

PLATE TO 

UNLOCK 

ENSURES UNIT 

IS CORRECTLY 

MOUNTED 

BATTERY  

COMPARTMENT 

3-VOLT BATTERY  

LOCATION 

(

)

 

(+) 

GEMC

-

WL

-

SMK & GEMC

-

WL

-

SMK

-

2

 

Supervised Wireless Digital Smoke Detectors

 

 

INSTALLATION / SERVICE INSTRUCTIONS

 

WI1726D.aLF  5/23

 

333 Bayview Avenue, Amityville, New York 11701

 

For Sales and Repairs, (800) 645

-

9445

 

For Technical Service, (800) 645

-

9440 or visit us at

 

Tech.NapcoSecurity.com

 

(Note:  Technical Service is for security professionals only)

 

Publicly traded on NASDAQ      Symbol: NSSC

 

© NAPCO 2023

 

Reviews: