Napa BK 700-2606 User Instructions Download Page 2

Ω

 

 

 

 

 
SPECIFICATIONS 

FUNCTION  

RANGE & RESOLUTION 

ACCURACY (% of reading) 

DC Current 

40.00 AAC 

± (2.8% + 10 digits) 

400.0 AAC 

± (2.8 % + 5 digits) 

1000 AAC 

± (3.0 % + 5 digits) 

AC Current 

40.00 AAC 

± (3.0% + 10 digits) 

400.0 AAC 

± (3.0 % + 5 digits) 

1000 AAC 

± (3.0 % + 5 digits) 

DC Voltage 

400.0 mVDC 

± (0.8% + 3 digits) 

4.000 VDC 

± (1.5% + 3 digits) 

40.00 VDC 
400.0 VDC 
600 VDC 

± (2.0% + 3 digits) 

AC Voltage 

400.0 mVAC 

± (0.8% + 20 digits) 

4.000 VAC 

± (1.8% + 5 digits) 

40.00 VAC 
400.0 VAC 
600 VAC 

± (2.5% + 5 digits) 

Resistance 

400.0 

Ω

 

± (1.0% + 4 digits) 

4.000K

Ω

 

± (1.5% + 2 digits) 

40.00K

Ω

 

400.0K

Ω

 

4.000M

Ω

 

± (2.5% + 3 digits) 

40.00M

Ω

 

± (3.5% + 5 digits) 

Capacitance 

40.00nF 

 (5.0% r 100 digits) 

400.0nF 

 (3.0% r 5 digits) 

4.000

μ

 (3.5% r 5 digits) 

40.00

μ

100.0

μ

 (5.0% r 5 digits) 

Frequency 

 

5.000Hz 

 (1.5% r 5 digits) 

50.00Hz 

 

 (1.2% r 2 digits) 

Sensitivity: 10Vrms min. 

500.0Hz 
5.000kHz 
50.00kHz 
100.0kHz 

Duty Cycle 

0.5 to 99.0% 

 (1.2% r 2 digits) 

Pulse width: 100µs - 100ms, Frequency: 5.000Hz ~ 100.0kHz 

Temp (type-K) 
(probe accuracy 
not included) 

-20 to 1000 

 (3.0% r 5

C) 

-4 to 1832 

 (3.0% r 7

F) 

   Note:  No Auto-ranging & 400mV AC Voltage Range  

            

Clamp size                        

Opening 1.2" (approximately 30 mm) 

Diode Test

 

                    

Test current of 0.3mA typical; Open circ. volt. 1.5V DC typical         

typical. 

Continuity Check

 

     Threshold <100

; Test current < 1mA 

Low Battery Indication

 

“ BAT ” is displayed 

Over-range Indication 

“OL” is displayed 

 
 

 
 

SPECIFICATIONS (CONTINUED) 

Measurements Rate         

2 per second, nominal 

Input Impedance

 

     7.8M

 (VDC and VAC) 

Display 

4000 counts LCD 

AC Current 

50/60Hz (AAC) 

AC Voltage bandwidth  

50/60Hz (VAC) 

Operating Temperature 

14 to 122

o

F (-10 to 50

o

C)

 

Storage Temperature

 

-14 to 140

o

F (-30 to 60

o

C) 

Relative Humidity

 

 

90%(0

o

C to 30

o

C); 75%(30

o

C to 40

o

C); 45%(40

o

C to 50

o

C) 

Altitude 

Operating: 3000m; Storage 10,000m 

Over voltage

 

 

Category III 600V 

Battery

 

One  “9V” Battery 

Auto Off

 

Approximately 35 minutes  

Dimensions/Weight

 

     229 x 80 x 49mm/303g 

Safety                                  

For indoor use and in accordance with Overvoltage Category II, 
Pollution Degree 2. Category II includes local level, appliance, 
portable equipment, etc., with transient overvoltages less than 
Overvoltage Cat. III 

OPERATION 

NOTICES

: Read and understand all 

warning

 and 

precaution

 statements listed in the 

safety section of this operation manual prior to using this meter. Set the function 
select switch to the OFF position when the meter is not in use. 

DC/AC CURRENT MEASUREMENTS 

WARNING: 

Ensure that the test leads are 

disconnected from the meter before making current  
clamp measurements. 

1. Set the Function switch to the 

1000A, 400A, or 

 

  40A

 range. If the range of the measured is not known,  

  select the higher range first then move to the lower  
  range if necessary. 
2. Select DC or AC by pressing 

MODE

 button. 

3. Press the trigger to open jaw.  Fully enclose over one 

conductor wire to be measured. 

4.  The clamp meter LCD will display the reading. 

DC/AC VOLTAGE MEASUREMENTS 

WARNING: 

Ensure that the test leads are 

disconnected from the meter before making current  
clamp measurements. 

1. Insert 

Black test lead

 into negative (

COM) jack

 and 

Red test lead

 into positive (

V) jack

2. Set the function switch to the V position. 

3. Select AC or DC with the 

MODE

 button.  

4. Connect the test leads in parallel to the circuit under test. 

5. Read the voltage measurement on the LCD display. 

   

 

 

 

DC

DC

A C

A C

Ω

Ω

CAP

CAP

n n

n n

A

A

+

+

.

.

.

.

No

Yes