Guide d’Installation sonde E4000
E4000 probe Installation Guide
www.nano-sense.com
All Rights Reserved
Tel: 33 (0)1 41 41 00 02
page 3/27
1. Security
WARNING
Danger of death, risk of electric shock and fire!
The installation should only be undertaken by a qualified electrician!
To apply for correct bus and power cables and to activate the device, comply with the state of the art
and standards.
Any intervention or modification to the device will invalidate any warranty claim.
• Do not use the sensors for measuring gas content relating to safety!
• Use the probe only with secured low voltages!
• Use an external 24VAC or DC power supply capable of delivering 60mA per probe and ensuring a
peak voltage under 40V.
2. Positioning
The position of the probe is crucial vis-à-vis efficiency and energy savings for
ventilation, heating and cooling.
• The probe is designed to ensure air quality; it must be placed in the area of
occupancy of the premise served by outlet vents, on a wall at eyes level
(breathing human level, between 1.5 and 1.8m).
• Avoid drafts (near openings, blowing air, doors, outlet vents) and dead zones
(niche, shelves and curtains).
• Avoid orthogonal walls (corners of room in particular)
• Avoid heat sources and the proximity of occupants (radius of 1 m from
workstation).
• Avoid direct exposure to sunlight.
• Position the sensor vertically on a wall or partition.
This device is not intended for installation in duct or ceilings.
• When used with an EnOcean radio module, see the complementary positioning constraints § 7.2.4.4
Any work not in accordance with this documentation or
changes to the device will invalidate all warranty claims.