![NanoSense E4000 Installation Manual Download Page 8](http://html.mh-extra.com/html/nanosense/e4000/e4000_installation-manual_705120008.webp)
Guide d’Installation sonde E4000
E4000 probe Installation Guide
www.nano-sense.com
All Rights Reserved
Tel : 33 (0)1 41 41 00 02
page 8/22
In KNX version, the bus powers only the interface board, the main board is powered
by the secondary 31V–DC power supply (yellow and white).
Use a certified KNX power supply.
Most of KNX power supplies have a secondary 31V-DC power supply (yellow and
white cables and connector of the same colors).
In LON version use a 24V power supply independent from the bus.
In POE version, consumption is about 30mA.
Installation sample
RS485
KNX
LON
POE
Per Unit consumption
45 mA
40 mA
40 mA
30 mA
20 probes connected
20* (45 + 13) mA
To be adjusted for
voltage losses in long
cables worn.
20*40 = 800 mA
Δ Security : 20 % =
160 mA
Power supply :1 A
20*40 = 800 mA
Δ Security: 20 % = 160
mA
Power supply : 1 A
20*30 = 600 mA
Δ Security: 20 % = 120
mA
Total 720 mA
7.1.2.
Power supply connection
In all cases but POE, the probe requires a power supply separated from the bus
7.1.2.1.
RS485, Analogical, EnOcean, KNX and LON
The KNX or LON power supply cable allows receiving and sending data and powering the interface
board only. The main board shall be powered separately
Power supply connector
24VAC or 33V DC
RS485
Analog
EnOcean
The power supply connector is designed for monofilament cables from 0,6 to 0,8 mm of Ø. Reveal the wire on 5 mm.
It is not necessary to respect the polarity.
24V AC or 15+ 33V DC
Complementary Power supply REQUIRED
KNX
LON
EnOcean/KNX Gateway
For cable selection, refer to § Choice of cables attached
in the annex
.