39
The data inside this manual are not binding and they can be modified by the manufacturer without notice.
All rights reserved.
NPC 280 - 400
C
HAPTER
11
S
ETTING
TABLES
The following tables show the list of all masks which contain adjustable parameters.
On
Factory setting
column are indicated the setting values set during the unit testing; they are referred only to the unit which has the same serial
number you can find on the label of the first page of this manual.
DANGER
The wrong programming of the electronic control could cause big damages to the unit.
The parameters can be modified by specialized personnel only.
ATTENTION
The values of the probes can be displayed using a measurement system other than the manufacturer's factory setting. This operation does not
automatically convert the parameter values, which retain the measurement unit set by the manufacturer. To change the measurement unit
from one system to the next proceed with the utmost caution and ensure the operation is carried out by skilled personnel.
1 1 . 1 P a r a m e t e r s e t t i n g
To modify the following parameters, follow the procedure illustrated in chapters 7.9.1 “Access to the parameters” and 7.9.2 “How to change the
value of a parameter” .
11.1.1 Therm oreg ulatio n p arameters
11.1.2 Displaying parameters
11.1.3 Configuration parameters
Parameter
Description
Min.
Max.
Udm
Resolution
Factory setting
ST01
Chiller set point
It allows to fix the operating set point during chiller operation
ST02
ST03
°C
°F
dec
int
45
°F
ST02
Chiller minimum Setpoint
It fixes the min. setpoint limit during chiller operation
-30.0
-22
ST01
°C
°F
Dec
int
41
°F
ST07
Tripping band of regulation steps during chiller operation
0.1
0
25.0
45
°C
°F
Dec
int
7.0
°F
Pr1
Password
0
999
023
Pr2
Password
0
999
Pr3
Password
0
999
Parameter
Description
Min.
Max.
Udm
Resolution
Factory setting
Displaying
Forced displaying of remote terminals
Pr1
Password
0
999
023
Pr2
Password
0
999
Pr3
Password
0
999
Parameter
Description
Min.
Max.
Udm
Resolution
Factory setting
Unit
Compressors
Analogue inputs
Probe Offset
Digital inputs
Relay outputs
Condensing proportional outputs
Module outputs
Remote terminal
CF74
Remote terminal n° 1 configuration:
0= absent
1= NTC probe installed
2= NTC probe not installed
0
2
0
2
with remote
terminal kit
Operating logic