Page 15
17-110-0142
Under no circumstances should external voltage/current be applied to pins 1 and 4,
damage to the controller will occur, negating the warranty.
Electrical Connector
• To set up for remote control eco mode.
Remove the link between pins 1 and 4 (3)
in the electrical connector plug. A zero volt
switching signal from the remote control needs
to be connected between pins 1 and 4 (4).
• When the connection is made, the generator
will operate normally. If the connection is
broken, i.e. the generator has been remotely
switched off, the generator will commence
shut down procedure, stop cycling and go into
standby mode, displaying “STANDBY” on the
display once completed.
• Using remote stop / start ensures the correct
shut-down sequence is implemented.
Generator Remote Stop/Start Control (if required)
8. Generator Operation
Locate the electrical connector on the underside of the controller in the shroud.
8.1 6 Pin Electrical Connector Configuration
Links 1/4
Remote stop/start link
1.
2.
3.
4.
1
2
3
6
4
5
Links 2/3
General (no-volt) alarm output
Link 5/6 (-Ve/+Ve)
4-20mA Retransmission
(Optional - where fitted)