Operating Instructions EBL512, V1.44.x
15
LED indicators on the Control Panel (CP)
LED indicator
Indicating
L8
Fault (yellow)
Acknowledged fault(s) and/or acknowledged but not
corrected fault(s).
L9
Test mode (yellow)
One or more zones are in "test mode".
L10
Disabled (yellow)
Something in the system is disabled.
L11
Power on (green)
Power on, i.e. the power supply (rectifier and/or
battery are connected and working properly.
L12
Fault
System (yellow)
System program (SW) is not running correct (e.g.
CPU/memory fault).
L13
Fault
Sounder (yellow)
One or more supervised outputs (type 3=alarm
device) have generated fault.
L14
Fault
Power supply (yellow) Power supply fault(s), described in chapter "Fault
L15
Fault tx (yellow)
1.
One or more faults (not acknowledged) are
generated in the system.
2.
Output(s) for fault tx (routing equipment) is(are)
activated.
L16 Key
switch
9
(yellow)
(see chapter "Door open
(Key switch)", see page 25.
The control unit door is open. When a TLON
network is used, one or more doors in the system are
open.
10
L17
Service (yellow)
One or more sensors have reached the service level.
L18
Disabled
Fire brigade tx
(yellow)
Output(s) for fire brigade tx (routing equipment)
is(are) disabled via menu (H8/S1) or open door.
11
L19
Disabled
Fault tx (yellow)
Output(s) for fault tx (routing equipment) is(are)
disabled via menu (H8/S1) or open door.
L20
Disabled
Extinguish
Output(s) for extinguishing equipment is(are)
disabled via time channel or menu (H2/B3 or B8).
9
In Brittish Standard (Marine application) convention: "Door open".
10
It is programmable if also the ext. FBP open door(s) should be indicated
and if it should indicate for each control unit individually or the whole
system.
11
It is programmable if open door should disable the output(s).