Minimum Circuit Ampacity

MCA = 1.25 x (Load 1 + Load 2 + Load 3 + Load 4)

Maximum Overcurrent Protection

MOP = (2.25 x load 1) + load 2 + load 3 + load 4

If the calculated MOP does not equal the standard current rating of an overcurrent protective device (typically even multiples of 5), 
then the marked MOP is the next lower standard rating.

Exceptions:

1. The marked MOP will be the next higher standard rating than the computed value, if the next lower standard rating is less than 

125 percent of the current rating of an electric heater load when such heater is involved.

2. If the computed value for MOP is less than the MCA, then the marked MOP is increased to the largest MOP appropriate for the 

MCA.

3. If the MCA does not correspond to a standard protective device rating, the next higher standard rating of the protective device 

will be marked if this rating does not exceed 800 A.

For Nailor Fan Powered Terminal Units and Fan Powered Chilled Water Terminal Units, 

Load 1

 is the largest motor current, 

Load 2

 

is the sum of all other motor currents, and 

Load 3

 is the heater current. 

Load 4

 is used for other loads greater than 1.0 ampere and 

can be considered zero for most standard products.
For Nailor Variable Air Volume Units, 

Load 1

 and 

Load 2

 are considered zero.

Load 3

 is the heater current 

Load 4

 is used for other loads greater than 1.0 ampere and can be considered zero for most standard 

products.
(Motor currents are determined by product application test in accordance with UL 1995 and may not be the same as the motor 
manufacture’s FLA marking.)

All formulae, definitions, and exceptions are cited from Underwriters Laboratories Inc. Standard for Safety for Heating and Cooling Equipment, UL 
1995 Fourth Edition (Sec. 37.14, 37.15) CAN/CSA-C22.2 No. 236 Fourth Edition

Appendix A – MCA and MOP Calculations

OL

CLH

HLH

OL

CLH

HRH

OL

CRH

HLH

OL

CRH

HRH

CRH

OR

HRH

CLH

OR

HRH

CRH

OR

HLH

CLH

OR

HLH

AIRFLOW

LEFT HAND CONTROLS

AIRFLOW

RIGHT HAND CONTROLS

9/18 IOM-DOAS

Page 7 of 8

Model 33SZ • Orientations

Summary of Contents for 33SZ

Page 1: ...N MANUAL FAN POWERED CHILLED WATER DOAS TERMINAL UNIT MODEL 33SZ Nailor Industries Inc reserves the right to change any information concerning product or specification without notice or obligation 9 18 IOM DOAS Page 1 of 8 ...

Page 2: ...ss 3 Field Wiring 3 Electrical Suggestions and Requirements 3 Water Pipe Connections 4 Control Start up and Operation 4 Primary Air Damper and Fan Adjustment 4 Starting the fan motor 4 Maintenance Procedures 4 Fan and Motor 4 If fan motor does not run do the following 4 Fan motor runs but emits excessive noise 4 Fan motor runs but airflow too low 4 If repair or replacement is required 4 Primary Ai...

Page 3: ...t contain corner posts Caution Nailor 33SZ units are too heavy to suspend with the ductwork and must be independently supported Nailor recommends attaching straps or screws into the 16 gauge frame corner posts of the size 40 and 50 units when possible and into the inlet outlet or side panels of the size 30 unit Duct Connections All ducts should be installed in accordance with SMACNA guidelines Sli...

Page 4: ...s clear of all debris and foreign objects c Ensure unit enclosure blower housing and blower wheel are free of any debris and foreign objects Starting the fan motor 1 Start motor and let it run in at least 15 minutes During run in check ductwork connections for leaks and repair if necessary 2 All 33SZ units are equipped with ECM motors Set the primary air dampers as described in 3 Set the fan as de...

Page 5: ...NLET SIZE CONTROL VOLTAGE CONTROL SEQUENCE VOLT AMP VOLT AMPÈRE KW WATTS NB WATTS MOTOR VOLTAGE MAX FAN CLG MIN Bande Morte L S NOMBRE DE RANGÉES SERPENTIN EAU RÉFRIGERÉÉ MAX FAN CLG MIN Bande Morte CFM 481059 2 01 TOTAL MAX OVERCURRENT PROTECTION RESISTANCE DES FUSIBLE MAX VOLTAGE DU MOTEUR MOTOR AMP AMPERAGE DU MOTEUR EACH CIR CHAQUE CIRCUIT 2 TOTALE 5 Jun 2015 D33SZE 40 06 24 9 18 IOM DOAS Page...

Page 6: ... O D tube V1108 40 50 10 3 16 O D tube V1110 40 50 12 3 16 O D tube V1112 Unit Size Filter Type Filter Part No 1 Throwaway H1 2506 30 2 Merv 8 H1 2507 2 Merv 13 H1 2508 1 Throwaway H1 2509 40 2 Merv 8 H1 2510 2 Merv 13 H1 2511 1 Throwaway H1 2512 50 2 Merv 8 H1 2513 2 Merv 13 H1 2514 Airflow Switch Part No AFS H1 235 AFS Probe 4 H1 242 AFS Probe 8 H1 245 EON Control Cards Part No EPIC Single Motor...

Page 7: ...ked if this rating does not exceed 800 A For Nailor Fan Powered Terminal Units and Fan Powered Chilled Water Terminal Units Load 1 is the largest motor current Load 2 is the sum of all other motor currents and Load 3 is the heater current Load 4 is used for other loads greater than 1 0 ampere and can be considered zero for most standard products For Nailor Variable Air Volume Units Load 1 and Load...

Page 8: ... Heating Rack Integral Drip Pan Optional Supplement Heat Electric Resistive Coil Filter Rack Accommodates up to 2 51 Merv 13 Filter Model 33SZE Size 40 50 Opposed Blade Primary Air Valve Hinged Fan Control Enclosure Optional Door Interlocking Disconnect Primary Air Valve Control Enclosure Optional Supplementary Heat Hot Water Coil Motor Blower Sensible Cooling Coil Optional Filter Multi Point Flow...

Reviews: