Version 1, May 2020
under window displays "0", change "0" to "1" by pressing the “INC” button, then
press the “SET” button, the controller will run the auto
-
tuning program, the “A
U
T”
indicator flickers. After auto-tuning end, the indicator stops flickering, PID parameter
value is saved automatically. In the auto-
tuning process, press the “SHIFT” button for
another 6 seconds, the controller will stop the auto-tuning program.
During the Auto-tuning process, if over temperature alarm, the buzzer does not beep,
"ALM" indicator is not lit, the heat output will be cut off; the “SET” button is invalid,
the under window always displays temperature set point value.
5
.
Internal parameters settings
In the
normal state, press the “SET” button for 3 seconds, windows will display
the prompt “Lc” and the password value. Adjust the password to the required
value, then press the “SET” button again, it will enter the internal parameters
setting state. Press the “SET” button for another 3 seconds, it will return to the
normal state, the set value will be saved automatically.
Parameter table 1
Prompt
Name
Function description
(Setting range)
Factory value
Lc
Password
key
When “Lc=3”, enter the next
parameters.
0
ALH
Over-temp
alarm
If
“PV>(SV+ALH)”,
the
ALM
indicator turns on. The buzzer sounds
and the heat output turn off.
(0
~
100.0
℃
)
5.0
P
Proportional
band
Adjustment of proportional function.
(0
~
100.0
℃
)
10.0
I
Integration
time
Adjustment of integration function.
(1
~
2000S) 300
D
Differential
time
Adjustment of differential function.
(0
~
1000S) 200
T
Control cycle The temperature control cycle.
(1
~
60S)
5
Pb
Temperature
deviation
correction
It is usually used to correct errors
in low temperature measurement.
Pb = Actual value
–
PV
(-50.0
~
50.0
℃
)
0