background image

 

DF Series installation manual  

26

 

www.nagasinnovation.com 

MAXITROL TROUBLESHOOTING CHECK LIST

 

SYMPTOMS 

POSSIBLE CAUSE 

ON-SITE CHECK 

ACTIONS 

NO GAS FLOW 

1. Modulating valve Improperly 
installed or defective 

1. The arrow on the side of the 
valve must point in the direction 
of the gas flow. 

1. Install the valve properly. 

CONTINUOUS LOW FIRE 
(ELECTRONIC PROBLEM) 

2. No voltage to the amplifier. 
3. Open circuit in TD114 
(circuit or wiring) 
4. Short circuit in TS114, 
(circuit or wiring) 
5. Defective amplifier 

2. Check for 24 VAC supply at 
amplifier terminals 7 and 8. 
3. Check for loose or broken wires 
between amplifier terminals 1 
and 2 and between TD114 
terminals 1 and 3. 
4. Connect the test resistor 
between terminals 3 and 4 of the 
amplifier and disconnect the 
wiring. Follow Maxitrol analysis 
procedure. 
5. Perform checks 2, 3 and 4. 

2. Verify the power source. 
3. Tighten connections or replace 
wiring. 
4. If a modulating signal is read, 
check TS114 for short circuits. 
Replace the TS114 if necessary. 
5. If steps 2, 3 and 4 do not solve 
the problem and a modulating 
signal is still not read, replace the 
amplifier. 

CONTINUOUS LOW FIRE 
(NO ELECTRONIC 
PROBLEM) 

6. Short circuit or open circuit in 
the amplifier coil 
7. Missing, jammed or improperly 
installed valve plunger.  

6. With control wires 
disconnected, check the 
resistance at the connecting 
terminals of the modulating 
valve. 
7. Check the plunger; it should 
move freely upward. 

6. Replace the modulating valve 
head if the resistance is not 
approximately 45-55 ohms for the 
M511 or ES371 valves and 
approximately 60-80 ohms for the 
MR212 valve. 
7. Clean the plunger or replace it 
if necessary. Install it according to 
the instructions provided. 

LOW FIRE - PULSATING 
OR ERRATIC FLAME OR 
IMPROPER CAPACITY 

8. Incorrect low fire adjustment. 
9. Excessive negative pressure at 
burner 

8. Make sure that low fire is 
properly adjusted. There should 
be a low flame throughout the 
burner. 
9. Shut off main gas supply and 
check the suction at the elbow 
located before the burner while 
the blower is in operation; the 
negative pressure should not 
exceed 1.5 inches of water for the 
M511. 

8. Adjust the low fire. 
9. If the negative pressure 
exceeds 1.5 inches of water, 
check for clogged filters or air 
inlet restrictions. Refer to the 
manufacturer for other 
suggestions. 

CONTINUOUS HIGH FIRE 
(ELECTRONIC PROBLEM) 

10. Short circuit in TD114 
(circuit or wiring) 
11. Open circuit in TS114/TS1007 
(circuit or wiring). 
12. Jumper not connected 
between terminals 2 and 3 of the 
amplifier. 

10. Check for short circuits at 
amplifier terminals 1 and 2 and 
TD114 terminals 1 and 3. 
11. Check TS114 for open circuits. 
Follow step 4. 
12. Make sure jumper is 
connected. 

10. Correct wiring if necessary. 
11. If a modulating signal is read, 
check TS114 for open circuits. 
Replace the TS114 if necessary. 
12. Correct the wiring. 

CONTINUOUS HIGH FIRE 
(NO ELECTRONIC 
PROBLEM) 

13. Foreign object holding the 
valve open. 
14. Jammed plunger. 

13. Remove valve bottom plate 
and inspect valve plunger and 
seat. 
14. Check the plunger; it should 
be clean, smooth and move freely 
in the valve. 

13. Clean the seat. Clean the 
valve or replace it if necessary. 
14. Clean the plunger or replace if 
necessary. 

ABNORMAL HIGH FIRE 

15. Gas inlet pressure too low. 
16. Incorrect adjustment of 
regulator outlet pressure. 

15. Make sure that the minimum 
inlet pressure recommended by 
the manufacturer is respected. 
16. Adjust the gas inlet pressure 
according to the manufacturer’s 
specifications. 

15. Increase the inlet pressure if 
possible. 
16. Adjust the regulator to obtain 
the required pressure. 

Summary of Contents for DF SERIES

Page 1: ...DIRECT GAS FIRED AIR HEATER DF SERIES INSTALLATION AND OPERATION MANUAL CUSTOM GAS SOLUTIONS LEGENDARY PERFORMANCE...

Page 2: ...y read the installation start up and maintenance instructions before installing or servicing this unit GAS ODOR If a gas odor is detected 1 Open all windows 2 Do not touch any switches 3 Extinguish al...

Page 3: ...N 6 2 GAS CONTROL PANEL INSTALLATION 7 3 GAS PIPING CONNECTIONS 8 4 ELECTRICAL CONTROL SENSORS CONNECTIONS 9 5 AIR PRESSURE SWITCH CONNECTION 10 6 IGNITION AND FLAME DETECTIONS CONNECTIONS 10 7 START...

Page 4: ...FPA 70 in the USA and all local applicable codes for this category of equipment All electrical installations must comply with the electric diagrams of the heater For more information refer to the star...

Page 5: ...plate installation 2 Control panel installation 3 Gas piping connections main burner pilot and vents 4 Electrical control sensors connections 5 Differential pressure switches connections 6 Ignition w...

Page 6: ...g to allow the insertion of the profile plate at the chosen location CLEARANCES TO BE RESPECTED Table of clearances Model F G H in mm in mm in mm DF 25 50 75 100 1 25 6 152 30 762 DF 150 12 305 DF 200...

Page 7: ...th of the control panel length TYPICAL PIPING SCHEMATIC OF AN INSTALLATION WITH THE PANEL MOUNTED DIRECTLY ON UNIT TYPICAL PIPING SCHEMATIC OF AN INSTALLATION WITH THE PANEL REMOTELY MOUNTED FROM UNIT...

Page 8: ...BH and less Use external gas regulator to reduce to psig From 751 to 1000 MBH 1 From 1001 to 2500 MBH 1 1 1 From 2501 to 5000 MBH 2 1 2 5001 MBH and more 3 2 3 Pilot vent and bleed valve pipe size NPT...

Page 9: ...of operation of the electrical diagram must never be modified without consulting the manufacturer Electrical controls location Installed by others Items Description All wires must comply with codes a...

Page 10: ...ropriate hardware to pass the tubes through unit wall 6 IGNITION AND FLAME DETECTIONS CONNECTIONS SNAPPING BUSHING IF DOUBLE WALL RUBBER GROMMET BLACK PLASTIC TUBE PROFILE PLATE PROFILE PLATE SUPPORT...

Page 11: ...H GTO 15 Red with blue stripe 13mm 4 Pilot gas tubing With ultra violet flame detector Components Description Wire gauge Color Hole diameter to drill in wall5 1 Pilot ignition wire GTO 15 Black 13mm 2...

Page 12: ...mation should only be used by a qualified technician for gas equipment installation with qualification cards with knowledge in electricity and ventilation WARNING Smoking is not recommended during the...

Page 13: ...Pa DF 150 200 300 375 450 550 700 Min 13 w c 3235 Pa Min 11 w c 2734 Pa Max 14 w c 3484 Pa Max 14 w c 3484 Pa For lower gas pressure consult manufacturer b Ensure that the air is completely purged fr...

Page 14: ...r profile plate is too high or too low the unit will not function properly This could produce an excess of carbon monoxide CO or trigger a FLAME FAILURE alarm b To measure the differential pressure at...

Page 15: ...to the value indicated in the graph below 40 35 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 0 4 0 5 0 6 0 7 0 8 40 36 32 28 24 20 16 12 8 4 0 4 8 12 16 20 24 28 32 36 4...

Page 16: ...ing of the profile plate by moving the adjustment plates closer to the burner g If the differential pressure reading is higher than the desired value enlarge the opening of the profile plate by moving...

Page 17: ...mperature 20 F 29 C Desired final temperature 70 F 21 C Temperature rise T 90 F 50 C b When the outside temperature does not allow for the simulation of the specified temperature rise across the burne...

Page 18: ...utside air temperature permits full fire M511 M611 or ES371 MR212 FINAL AIR TEMPERATURE ADJUSTMENT a Set the MAXITROL temperature selector TD 114 to the desired final temperature This selector is loca...

Page 19: ...e following checks must be performed a Verify the alarm code on the flame supervision relay and consult the troubleshooting section of this manual b Set the main power switch to OFF c Ensure that all...

Page 20: ...e selected set point of the temperature selector 10 OPERATING SEQUENCE FOR DOUBLE VOLUME DIRECT FIRED HEATER For guidance only Starting up the burner a Create a heating demand b If outside temperature...

Page 21: ...it switches are closed and terminal 6 is energized c The PTFI light is ON only during the pilot ignition cycle d The FLAME light is ON only when the flame safeguard relay detects a flame signal and is...

Page 22: ...n and operation manual of the flame relay manufacturer for any code not listed in this table CONSULT THE FIREYE TROUBLESHOOTING TABLE TO ESTABLISH THE DIAGNOSTIC Trouble code Trouble description alarm...

Page 23: ...ng demand b The PILOT light is ON when there is a heating demand and the pilot control valve coil as well as the ignition transformer is energized c The FLAME light is ON when the flame safeguard rela...

Page 24: ...el it should be set to BURNER 3 Check the outside temperature thermostat it prevents the burner from running if the outside temperature is over 70 F 4 Check the burner purge time delay relay 5 Refer t...

Page 25: ...N C and open if the differential pressure at the burner exceeds 1 2 inches of water see the Start up Instructions section for more information on the adjustment of the burner profile plate AT START UP...

Page 26: ...provided LOW FIRE PULSATING OR ERRATIC FLAME OR IMPROPER CAPACITY 8 Incorrect low fire adjustment 9 Excessive negative pressure at burner 8 Make sure that low fire is properly adjusted There should b...

Page 27: ...orrespond to the desired average discharge air temperature 24 Disconnect the room thermostat from terminal 2 of the TD114 21 Correct wiring 22 Adjust the TD114 23 Move the TS114 to a location where th...

Page 28: ...ct thermostat ______ F Pre purge delay ______sec Start up delay on low fire ______sec Inlet temperature thermostat ______sec Profile plate openings _______ X _______ _______ X _______ Main fixed Auxil...

Reviews: