background image

16

Please check the machine according to the following form before asking for maintenance: 

Faults Diagnosis

Problem

Possible Cause

P1 Error Code

In COOL mode: room

temperature is lower than

the set temperature

The air filter is blocked with

dust or animal hair

The unit is low on

refrigerant

Temperature setting is too

high
The windows and doors in

the room are open
The room area is too large

Troubleshooting

Reset the temperature

Unit does not turn

on when pressing

ON/OFF

 button

Unit does not cool

well

The unit is noisy

and vibrates too

much

The unit makes a

gurgling sound

Exhaust hose is not

connected or is blocked

The Water Collection Tray is full.

Turn off the unit, drain the water 

from the Water Collection Tray 

and restart the unit.

There are heat sources

inside the room

Turn off the unit and clean the

filter according to instructions

Call a service technician to inspect

the unit and top off refrigerant 
Decrease the set temperature
Make sure all windows and doors 

are closed
Double-check the cooling area

Turn off the unit, disconnect the

hose, check for blockage and 

reconnect the hose

Remove the heat sources if 

possible

The ground is not level

Place the unit on a flat, level 

surface

The air filter is blocked with

dust or animal hair

Turn off the unit and clean the

filter according to instructions

This sound is caused by the

flow of refrigerant inside

the unit

This is normal

EN

Summary of Contents for KA 9006

Page 1: ...KA 9006...

Page 2: ......

Page 3: ...Produktdatenblatt 32...

Page 4: ......

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ...en Bereich gelagert werden muss in dem die Raumgr e der f r denBetrieb festgelegtenRaumfl che entspricht Jede Person die an Arbeiten an oder dem Einbruch in einen K ltemittelkreislauf beteiligt ist so...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ...ble Air Conditioner Portable Air Conditioner Local Air Conditioner Instruction Manual Before using your air conditioner please read this instruction manual carefully and keep it for future reference R...

Page 35: ...ety Precautions Cautions Warnings for using R290 R32 refrigerant only Preparati ons Installation Operati on Maintenance Faults Diagnosis Design and Compl iance Notes Sociable Remark 2 3 4 8 9 12 15 16...

Page 36: ...ause electrical components to short circuit DO NOT install the unit in a location that may be exposed to combustible gas as this could cause re The unit has wheels to facilitate moving Make sure not t...

Page 37: ...ffic area and where it will not be tripped over Do not operate unit with a damaged cord plug power fuse or circuit breaker Discard unit or return to an authorized service facility for examination and...

Page 38: ...shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the perso...

Page 39: ...possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibl...

Page 40: ...may not be adequate or Warnings for using R290 R32 refrigerant only may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potent...

Page 41: ...hen removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ens...

Page 42: ...l lever adjust manually vertical louver control lever adjust manually panel Caster bottom tray drain outlet air filter behind the grille upper air intake air outlet lower air intake drain outlet NOTE...

Page 43: ...the Intakes Outlets or Remote Signal Receptor of the unit as this could cause damage to the unit NOTE All the illustrations in the manual are for explanation purpose only Your machine may be slightly...

Page 44: ...iders once they are adjusted to proper length Window slider A Window slider B Bolt Part Description 1 pc 1 pc 1 pc 1 pc 1 pc 1 pc 1 pc 1 pc 2 pc 1 pc 1 pc 2 pc 1 set 1 set Unit Adaptor Window Slider A...

Page 45: ...e Make sure that there is no obstacle around the air outlet of the exhaust hose in the range of 500mm in order to the exhaust system works properly All the illustrations in this manual are for explana...

Page 46: ...Operation 12 Control panel EN...

Page 47: ...he drain hose and drain the collected water away If protection repeats call for service Note When one of the above malfunctions occurs turn off the unit and check for any obstructions Restart the unit...

Page 48: ...nit will continue to operate as originally programmed NOTE This feature is unavailabe under FAN or DRY mode AIR FLOW DIRECTION ADJUSTMENT Adjust the air flow direction manually The louver can be set t...

Page 49: ...the appliance on FAN mode for 12 hours in a warm room to dry it and prevent mold Turn off the appliance and unplug it Clean the air lter according to the instructions in the previous section Reinstal...

Page 50: ...not connected or is blocked The Water Collection Tray is full Turn off the unit drain the water from the Water Collection Tray and restart the unit There are heat sources inside the room Turn off the...

Page 51: ...ebsite please check for the latest version Unit Temperature Range Cool 17 35 C 62 95 F Dry 13 35 C 55 95 F Mode Temperature Range Energy Rating Information The Energy Rating for this unit is based on...

Page 52: ...cipality has established collection systems where electronic waste can be disposed of at least free of charge to the user B When buying a new product the retailer will take back the old product at lea...

Page 53: ...ECONOMIC TECHNOLOGICAL DEVELOPMENT AREA WUHU ANHUI CHINA THE PRODUCT IS IN CONFORMITY WITH THE FOLLOWING STANDARDS LVD 2014 35 EU EN 60335 2 40 2003 A11 2004 A122005 A1 2006 A2 2009 A13 2012 EN 60335...

Page 54: ......

Page 55: ......

Page 56: ......

Reviews: