background image

 

32 of 35

 

Opus Control Wiring and Programming Installation Manual 

www.NabcoEntrances.com

P/N C-00139 

Rev 3-9-18

CHAPTER 13: TROUBLESHOOTING

Programming Issues

Problem

Possible Solution

Hard to manually open door

On outswing only: Check if shoe position and rod length are in accordance with the 

dimensions in the manual.

Except GT710: Reduce the preload on the operator. The Opus is not dependent on preload 

since there is no cam and doorposition switches. Maximum preload on GT8500’s should be 

one notch on the operator spline to maintain ANSI 156.19

Software Revision (up to, and including 18)

• Re-enter “0” for “hold closed force” under “optional settings”. The software on early Opus 

controls may suggest it’s alreadyset to “0”, but does not act like it. Entering “0” again will fix it.

After manually opening door, 

the door stays open

Software Revision (up to, and including 18)

“Manual Open Function” is set to “No Action” and “Manual Open Sensitivity” is set to “0”. If “No 

Action” is desired, change “Manual Open Sensitivity” to anything other than “0”.

Control does not react to 

Activation signal

At the main screen, confirm that “IN” or “EXT” highlights when an activation signal 

isapplied. If not, check the wiring or the activation device.

At the main screen, determine if “BA” is highlighted. If a 4-wire on/off/hold-openswitch is  

being used, with a blue wire connected to terminal 8, then “Input BACircuit” (found under 

“Input Settings”) must be set to “Normally Closed”. If a 3-wire switch is being used, or no 

switch is being used (nothing connected to terminal 8), then “Input BA Circuit” should be 

set to “Normally Open”.

At the main screen, if Status shows “Stopped” while the door is closed, and BA isnot 

highlighted, turn off power for at least 4 seconds then turn on again. With the doorstill 

closed, status should now show “Fully Closed”.

Must navigate back to the main screen (as shown at right) for an activation signal to work.

Sim Pair behaves oddly

 

(Controls may not be 

communicating correctly)

All Revisions

• Do a “copy data” from one control to the other. One control should then indicate “Type 1” on 

the main screen, the other should indicate “Type 2”. There is no rule as to which needs to be 

which, but they must be different than each other.

Closing functions do not 

work when opened manually

Software Revision (up to 17)

• Closing functions such as (speed, latch-check, power close), change “manual open function” 

to something other than “no action”. “stop and close” is usually ideal. 

Sim Pair using “Stop & Close” 

but results in a “Push & Go”

Software Revision (up to, and including 20)

• Remove sim-pair harness, set both controls to “single door”, parallel the common terminal 

and any input being used between both controls.

Door does not always close 

during Latch Check

Software Revision (up to, and including 19)

Symptom: When the door is used manually it closes every time. However, when the door is 

activated, once in a while it will stop at latch check and not continue to close.

• Increase latch check speed or try increasing operator arm preload (if GT710 - increase spring 

tension on hydraulic closer)

Double Egress pairs are not 

Synchronizing

Software Revision (up to, and including 20)

• Remove CANbus cable. Set both Controls as single doors. The activation signal should 

be paralleled between both Controls. Safety signals should only be attached to their 

corresponding door’s Control.

Software version is 21

• Be sure both controls are set to “Double Egress”. Safety signals should only be attached to 

their corresponding door’s control.

• See also “Sim Pair behaves oddly” located at top of this Table.

Summary of Contents for Opus Control

Page 1: ...s operational WARNING Table of Contents CHAPTER 1 SAFETY 3 CHAPTER 2 SCOPE 4 SECTION 2 1 To the Installer 4 SECTION 2 2 Objective 4 CHAPTER 3 FEATURES 4 CHAPTER 4 SPECIFICATIONS 4 SECTION 4 1 General...

Page 2: ...CTION 12 2 Activation using ON OFF Hold Open Switch 21 SECTION 12 3 Safety 22 SECTION 12 4 Safety with Monitoring 23 SECTION 12 5 Lock 24 SECTION 12 6 Standard Wiring for Single Full Automatic 25 SECT...

Page 3: ...sult in seriouc personal or fatal injury When uncertain whether power supply is disconnected always verify using a voltmeter Do not place finger or uninsulated tools inside the electrical controller T...

Page 4: ...ces at 1 877 622 2694 between 8 am 4 30 pm Central time for additional assistance SECTION 2 2 Objective The Opus Control is designed to be installed within the Header of X X New Swing and Folding Door...

Page 5: ...mber Current Consumption Acuvision V 00202 80mA ea unit at 12VDC Optex Reaction V 00173 125mA Acusensor M A 01306 150mA Optex i one V 00055 130mA Radio Control Receiver 24 11467 50mA CX33 Logic Relay...

Page 6: ...d is properly secured to the grounding screw or grounding wire whichever is provided Attention Insert all Incoming 120 VAC Power wires into the pre drilled Electric Service Access Hole located at the...

Page 7: ...Communication 7 CN1 Power Connector 4 Rotary Dial 8 Fuse CHAPTER 7 THE ROTARY DIAL X X Push down on the Rotary Dial Long push 2 seconds to gain access to LCD Catagory Screens Short push under 2 second...

Page 8: ...se Recycle Cnt Latest Recycle Posi on DN 1334 LEVEL 4 Push and Hold Rotary Dial 2 Sec Rotate Dial Rotate Dial Rotate Dial Short Push Figure 3 LCD Screen Transition SECTION 8 1 Level One Specification...

Page 9: ...ke Learning Go to Se ng menu Reset to Default Set Yes No Passcode Stroke Learning Yes No Ac vate Passcode Rotate Dial Rotate Dial Rotate Dial Figure 6 Level Two Screen Attention To prevent tampering a...

Page 10: ...Passcode 8 2 3 Stroke Learning Stroke Learning is used to measure from Fully Closed to Fully Open points in effort to determine where Check Points should happen Stroke Learning is also used to determ...

Page 11: ...which Handing to enter Left or Right DN 0833 EXTERIOR BREAKOUT SIDE LEFT HAND RIGHT HAND Door Hand for Slide Doors Left Right Left From the Exterior Side of Building determine which Handing to enter L...

Page 12: ...er Range Default Description Hold Close Force 0 3 0 0 OFF 3 Strongest Hold Close force Power Close Range No Power Close No Power Close Closing assisted by Motor to fight wind or stack pressure Whole C...

Page 13: ...the door slams open No Sim Pair Setting Single Door Single Door Select type of Door Normal Sim Pair If selected before returning to last screen option to copy settings to other Control is given Double...

Page 14: ...lock functionality Breakout Pass through Output changes when breakout occurs Door Sequencing Provision for door sequencing Sensor Monitoring N O Normally open contacts for Monitoring Sensor Monitoring...

Page 15: ...side of Door If activated Opus will ignore the Activation Sensor while Door is moving This input is for the ASIAN market ONLY AsiaSpec_ExtActSwgSd Input 62 Open Timer N A Same as Open timer Same as Op...

Page 16: ...ing N A Not Active Active Not Active Sensor monitoring function SWL Monitoring N A Not Active Active Not Active Sensor monitoring function If Monitoring is enabled for any input then the sensor MUST b...

Page 17: ...Push Rotary Dial LEVEL 4 1 Rotate Dial to select Movement Se ng 2 Push Rotary Dial Back Check Speed 0 1 2 3 4 5 6 7 0 1 Slow 7 Fast Speed Ajustment 11 20 10 12 Push and Hold Rotary Dial 2 Sec SECTION...

Page 18: ...en al Ac va on signals to open or signals to close 10 H Input H Programmable input 11 M0 Mode 0 When grounded puts door into One Way Mode Hold Open when grounded with M1 12 M1 Mode 1 When grounded put...

Page 19: ...uen al Sequen al Ac va on signals to open or signals to close 10 H Input H Programmable input 11 M0 Mode 0 When grounded puts door into One Way Mode Hold Open when grounded with M1 12 M1 Mode 1 When g...

Page 20: ...kout overhead swing side safety sensor Slide Door Sidelite Sensor 7 Out1 Programmable Output 5 6 7 2 8 12 14 11 13 9 10 1 2 3 4 5 6 7 3 4 1 2 3 4 5 6 7 1 2 3 4 2 3 4 1 N O COM N O COM Exterior Push Pl...

Page 21: ...utput 5 2 8 12 14 11 13 9 10 1 2 3 4 5 6 7 3 4 1 5 6 7 1 2 3 4 2 3 4 1 N O COM N O COM Exterior Push Plate Interior Push Plate ALL DEVICES MUST BE N O DRY CONTACT 8 12 14 11 13 9 10 1 2 3 4 5 6 7 N O...

Page 22: ...ty with Lockout overhead swing side safety sensor Slide Door Sidelite Sensor 7 Out1 Programmable Output NOTE For Safety Sensors equipped with a monitoring func on TERMINAL 7 should be connected to MON...

Page 23: ...o BODYGUARD OUTPUT Please see programming instruc ons for details PWR PWR TEST TEST Door Mounted Approach Side Sensor N O COM PWR PWR TEST TEST N O COM PWR PWR TEST TEST 5 2 4 5 1 2 3 4 6 7 1 6 7 8 12...

Page 24: ...13 12 11 10 9 8 7 6 5 4 3 2 1 Fail Secure Electric Strike Fail Secure Lock Shown Fail Safe and Mag Locks will use N C instead of N O Power Supply For Electric Strike N O COM N C Varistor MOV TVS DO N...

Page 25: ...13 14 8 WHITE Rocker Switch P N A 00805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used...

Page 26: ...ker Switch P N A 00805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used WARNING TOTAL POW...

Page 27: ...0805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used WARNING TOTAL POWER CONSUMPTION OF...

Page 28: ...OTAL POWER CONSUMPTION OF ALL SENSORS MUST NOT EXCEED 750 MA N O COM PWR PWR N O COM PWR PWR N O COM PWR PWR COM PWR PWR N O Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor 5 2 4 1 2...

Page 29: ...30 Clear A 70430 Dark Bronze RED BLACK 14 13 12 11 10 9 8 8 WHITE Off Hold Open On Off 14 13 12 11 10 9 8 8 14 BA break out input must be set to N C on the Opus Control is by default Panic Latch must...

Page 30: ...LAY TIMER must be set to an appropriate me for the door to unlock before opening LOCK CONDITION must be set to ONE WAY NIGHT ONLY NOTE If the Rocker Switch is not being used Interior Ac va on connects...

Page 31: ...mon for all above signals Example A Switch being used to turn ON OFF Power Close and Hold Close Programmable Terminal 10 Input H would be set to SPRING CLOSE ONLY 12 8 9 1011 1314 5 1 2 3 4 6 7 12 8 9...

Page 32: ...t highlighted turn off power for at least 4 seconds then turn on again With the doorstill closed status should now show Fully Closed Must navigate back to the main screen as shown at right for an acti...

Page 33: ...rive Circuit If the Drive Circuit detects an unusual state the Opus will stop door movement Possible causes are Abnormal voltage at Motor Circuit Abnormal current draw from motor Check all connections...

Page 34: ...ROLLER OPUS W CHASSIS BRAKE 9 M 01072 HARNESS POWER MAGNUM BOARD 10 V 00713 Used on A 01249 FUSE 2 AMP 5X20MM 250V FAST ACTING 11 A 01249 Used on GT710 8710 only HARNESS MOTOR OPUS 710 12 A 01002 Retr...

Page 35: ...10 7 M 01680 HARNESS OPUS CONTROL SIM PAIR 8 A 01098 CONTROLLER W BRAKE BOTTOM LOAD OPUS 9 M 01735 PLATE BOTTOM LOAD OPUS 10 A 01143 CONTROLLER W O BRAKE BOTTOM LOAD OPUS 11 A 01003 Not used on GT710...

Reviews: