SPECIFICATIONS
Operating voltage
Detection angle
Mounting height
Detection range
Time settings
Lighting load
Lux adjustment
Protection class
Operating tempreture
Power consumption
HF Frequency
230V~ 50/60 Hz
360°
1.5 m - 3.5 m (adjustable)
2 m - 10 m (adjustable radius)
10sec
±
3sec / 30min
±
5min
2000W Incendescent
800W Flourescent
6 x Max. 58W LED Load
C 132 F
10 - 500 lux
IP20 Class II
-20 °C ~ +40 °C
0.9W
5.8GHz, ISM Band
Distance Setting:
Detection range explain the radius distance on the floor after you install to the ceiling.
Switch “ 1 “ open, Switch “ 0 “ close position.
Note:
The above detection distance is measured using a person who is between 1.6m~1.7m tall
with an average build, moving at a speed of 1 ~ 1.5m/sec. if any of these variables are changed,
the detection distance will also resultantly change.
Time setting:
Time can be set 10sec. to 30min. Any movement detected before this time elapse will re-start
the timer. It is recommended to select the shortest time for adjusting the detection zone and
for performing the walk test. Switch to the on is “ 1 ”, switch to the off is “ 0 “; the corresponding
file of switch location and detection distance as follow.
Note:
After the light switches OFF, it takes approx. 1 sec. before it is able to start detecting
movement again. The light will only switch on is response to movement once this period as
elapsed.
USAGE AREAS
• At the building entrances, stair vestibutes.
• At the long halls within the flats.
• At the places required within the flats.
• At the parking garage.
• At the requisite locations within the hotels.
• At the schools, hospitals and oil filing station.
“OFFERS ENERGY SAVING FEATURE”
GENERAL SECURITY CAUTIONS
• Take of the original package and control if there is any damage of transportation
and general view of the product.
• Do not use the product at cross purposes.
• Keep it away from water and moist areas.
• Do not use the prodct at dusty, dirty and rusty places.
• Do not supply high voltage.
• Do not apply and liquid.
• Protect from any stroke.
• Using 230V~ voltage is so dangerous that only the specialist electricians
must install and apply.
CAUTIONS FOR INSTALL AND USAGE
• Installing must be carried out professional in accordance with applicable national wiring and
electrical operating conditions.
• Turn off the mains before mounting.
• Do not mount the product near the radiator and moist areas.
• Place the product horizontal to the ceiling.
• Use 10A fuse the supply input.
• Setting can be made 10-15 second after the releasing of the power.
• Time and daylight setting can be made during the day or night.
• Do not change the time and daylight setting abruptly.
• Do not make a second adjustment before you get a result from the first setting of the the time
and daylight.
• After you determine the right setting of the daylight, you can arrange the time as you need.
• The best result for the daylight setting can be obtained by adjusting the minimum. And that
you can find the correct setting for sensitivity incrementally.
• When a cleaning needed for the product, take of carefully and clean with a dry rag.
• Avoid mounting the detector close to objects that can cause rapid temperature changes such
as heaters, fans, refrigerators and ovents etc, and prevent the detector from point-blank
sunshine.
• If you cause the device operate inaccurately if there is tree, brushes etc. in the coverage area.
Complies with ROHS Regulation Directive
2002/95/EC
TROUBLESHOOTING
S3
0
0
0
0
S4
0
0
1
1
Time
10 sec
1 min
5 min
10 min
S5
0
1
0
1
S3
1
1
1
1
S4
0
0
1
1
Time
15 min
20 min
25 min
30 min
S5
0
1
0
1
S1
0
0
S2
0
1
Distance
2m
5m
S1
1
1
S2
0
1
Distance
8m
10m
ON
1 2
S1 S2
SENS: S1, S2
S6
0
0
0
0
S7
0
0
1
1
LUX
24H
10 Lux
20 Lux
50 Lux
S8
0
1
0
1
S6
1
1
1
1
S7
0
0
1
1
LUX
100 Lux
200 Lux
300 Lux
500 Lux
S8
0
1
0
1
6 7 8
S6 S7 S8
LUX: S6, S7, S8
Daylight setting:
Swich (1,1,1 ) max position can work day time and night time . (0,0,0 )min position can work if
the light is less then 10lux. Other positions are for intermediate values.
Installation
• Switch off the power
• Use screwdriver to take off top cover from the clips.
• Time, daylight and distance settings are available on the below, when you make the setting
close the top cover.
• Please check the below connection wiring diagram for power and load connections.
L’
L’
L
L
N
230VAC
Mounting
• Pull the spring back and place the product to the mounting hole on the ceiling.
• After installation give the power and test the product.
Wiring connection diagram
Connect N, L with power
Connect N, L’ with load
10366
360° Flush-Mount Ceiling Type Microwave Motion Sensor
1,5 - 3,5 m
20 m
10 m
10 m
360°
Mounting height
Detection range
Ceiling
The load don’t work
• Check the power and the load.
• Whether the indicator light is turned on after sensing? If yes,
please check load.
• If the indicator light does not turn on after sensing, please check
if the working light corresponds to the ambient light.
• Please check if the working voltage corresponds to the power
source.
The sensitivity is poor
• Please check if in front of the detection window there are hinder
that effect to receive the signal.
• Please check the ambient temperature
• Please check if the signals source is in the detection fields.
• Please check the installation height.
The sensor can’t shut
automatically the load
• If there are continual signals in the detection fields
• If the time delay is set to the longest
• If the power correspond to the instruction
• If the air temperature change near the sensor, air condition or
central heating etc.
KK-10366_150415_EN_00
GUARANTY
We will remedy defects caused by material flaws or manufacturing faults. The warranty will be
met by repair or replacement at our own discretion. The warranty shall not cover damage to
wear parts, damage or defects caused by improper treatment or maintenance. Further
consequential damage to other object is excluded.
Claims under the warranty will only be accepted if the unit is sent fully assembled and well
packed complete with a brief description of the fault, a receipt or invoice ( date of purchase and
dealer’s stamp) to the appropriate Service Center.
SETTING
DETECTION AREA
MALFUNCTION
SOLUTION