06 Commissioning

6.1 Before connecting system power supply

1.

Ensure that all modules are correctly mounted,

and the power supply is connected properly.

2.

Ensure that all touchpads and motors are

connected as per the connection diagram supplied.

NOTE: DO NOT CONNECT MYZONE 2 MZWFTP8-V2 

TO MOTOR OUTPUTS.

3.

Ensure the air conditioning system is OFF

6.2 Spill Zone Configuration

1.

A spill zones(s) may be designated by turning

on one or more the of the spill DIP switches

on the MZWFCBT8-V2 Main Processor Module.

6.3 Initial Power Check

When power is applied to the system, the start-up 

routine will drive all zone damper motors to the 

fully open position, then all dampers will drive to 

the appropriate position as dictated by the zone 

status, and, if the zone is on, the system conditions.

1.

Connect the 24VAC power supply to the

MyZone 2 system.

2.

Check the main modules for fault LEDs (any

red LED indicates an excess current fault

on the output – generally a cable short).

6.4 System Configuration

The following system configuration steps must be 

completed to ensure the system will operate correctly 

with the motors supplied, and that the system safety 

mechanisms are operating as intended. Using the 

MZWFTP8-V2 System Configuration settings are 

accessed by pressing the “Zones” icon from the 

Home screen, from the “Zone Overview Screen” press 

the “Settings” icon in the top right corner. System 

configuration settings are password protected to 

prevent accidental tampering. The password is “4321”.

Please see MyZone 2 User Manual for instructions.

1.

Set Present Zones

2.

Set Motor Time

3.

Display / Hide Spill Zones

4.

Enable / Disable Buzzer

5.

Favourites Set

6.

Name Favourites

7.

Name Zones

8.

Balance System with min and

max zone airflow settings

9.

Set System Time Clock

10.

Set Individual Zone time clock schedules

(if required)

11.

Set Individual favourite time clock schedules

(if required)

6.5 Damper Motor Check

1.

Select the appropriate zone and turn the zone Off

(make sure the zone drives to the off position).

2.

Select the appropriate zone and set the

damper to 100% open position (check the

damper drives to the on position).

3.

Select the appropriate zone and set the

damper to the 50% open position (check the

damper drives to the half way position).

4.

Repeat this for each zone.

6.6 Spill Check

1.

Turn all zones Off one at a time.

2.

Verify the spill zone(s) activates (the

zone name will change to green to

indicate that zone is spilling).

7

Summary of Contents for Myzone2

Page 1: ...Climate Control System 2 Installation Manual ...

Page 2: ...01 02 03 04 05 06 Introduction System Overview Technical Specifications Installation Crimping Instructions Commissioning 3 3 4 4 6 7 Contents 2 MyZone 2 Installation Manual ...

Page 3: ... Although the installation commissioning and operation of the system are simple the actual control process is ingenious The operation can be separated into 3 areas 1 Individual Zone Airflow Management 2 Total Airflow Management 3 Safety Modes 2 1 1 Individual Zone Airflow Management One of the strengths of the MyZone 2 system is the way it handles each zone as an independent entity The zone damper...

Page 4: ... 3 19 4 VA 15 8 VA 4 24 5 VA 18 8 VA 5 29 7 VA 21 8 VA 6 34 8 VA 24 8 VA 7 40 0 VA 27 8 VA 8 45 2 VA 30 8 VA 3 1 Electrical Requirements Power input to system 24 Volts AC 10 Line Frequency 50 Hz 3 2 System Power Consumption The power consumption data in this table represents maximum values with all motors driving and 2 x LCD touchpads with backlighting on Typical loads will be less than this 3 3 E...

Page 5: ...ntrol One touchpad on each floor or in each zone is often the case The touchpad has been designed to be mounted using the provided c clip and wall mount box 4 2 3 Motorised Damper The motorised dampers should be fitted in line with the flexible duct Care should be taken to make certain that all dampers motors are of the same type MyZone 2 utilises time proportional modulation and conducts a honing...

Page 6: ...tion each time Squeeze the handles firmly to set the contacts and secure the cable 05 Crimping Instructions Never insert uncrimped plugs into the sockets Doing so may cause damage to the socket contacts Crimped plugs should insert easily into sockets until the locking tab clicks into place Plugs that have been incorrectly crimped may be difficult to insert and may cause damage to the socket contac...

Page 7: ...otors supplied and that the system safety mechanisms are operating as intended Using the MZWFTP8 V2 System Configuration settings are accessed by pressing the Zones icon from the Home screen from the Zone Overview Screen press the Settings icon in the top right corner System configuration settings are password protected to prevent accidental tampering The password is 4321 Please see MyZone 2 User ...

Page 8: ...Climate Control System 2 ...

Reviews: