06 Commissioning
6.1 Before connecting system power supply
1.
Ensure that all modules are correctly mounted,
and the power supply is connected properly.
2.
Ensure that all touchpads and motors are
connected as per the connection diagram supplied.
NOTE: DO NOT CONNECT MYZONE 2 MZWFTP8-V2
TO MOTOR OUTPUTS.
3.
Ensure the air conditioning system is OFF
6.2 Spill Zone Configuration
1.
A spill zones(s) may be designated by turning
on one or more the of the spill DIP switches
on the MZWFCBT8-V2 Main Processor Module.
6.3 Initial Power Check
When power is applied to the system, the start-up
routine will drive all zone damper motors to the
fully open position, then all dampers will drive to
the appropriate position as dictated by the zone
status, and, if the zone is on, the system conditions.
1.
Connect the 24VAC power supply to the
MyZone 2 system.
2.
Check the main modules for fault LEDs (any
red LED indicates an excess current fault
on the output – generally a cable short).
6.4 System Configuration
The following system configuration steps must be
completed to ensure the system will operate correctly
with the motors supplied, and that the system safety
mechanisms are operating as intended. Using the
MZWFTP8-V2 System Configuration settings are
accessed by pressing the “Zones” icon from the
Home screen, from the “Zone Overview Screen” press
the “Settings” icon in the top right corner. System
configuration settings are password protected to
prevent accidental tampering. The password is “4321”.
Please see MyZone 2 User Manual for instructions.
1.
Set Present Zones
2.
Set Motor Time
3.
Display / Hide Spill Zones
4.
Enable / Disable Buzzer
5.
Favourites Set
6.
Name Favourites
7.
Name Zones
8.
Balance System with min and
max zone airflow settings
9.
Set System Time Clock
10.
Set Individual Zone time clock schedules
(if required)
11.
Set Individual favourite time clock schedules
(if required)
6.5 Damper Motor Check
1.
Select the appropriate zone and turn the zone Off
(make sure the zone drives to the off position).
2.
Select the appropriate zone and set the
damper to 100% open position (check the
damper drives to the on position).
3.
Select the appropriate zone and set the
damper to the 50% open position (check the
damper drives to the half way position).
4.
Repeat this for each zone.
6.6 Spill Check
1.
Turn all zones Off one at a time.
2.
Verify the spill zone(s) activates (the
zone name will change to green to
indicate that zone is spilling).
7