General

T6 IVC

 SERIES

 RADIATOR

 

Installation

 Guide

 - 

Jan 2019

Myson Inc./Rettig USA  45 Krupp Drive, P.O. Box 1460,  Williston,  VT 05495 www.mysoncomfort.com

A variety of matching valves 

and other accessories are

 available and recommended from MYSON. For 

specific  applications  see  our 

d

etailed  installation  and  technicals  manuals 

and  price  book 

which 

are 

available on our web site.

It  is  assumed  that  the  installer  has  the  appropriate  technical  knowledge  related  to 

building  codes, standard  trade practices, and proper use of the tools of the trade. 

Failure to flush system of debris and flux may cause premature radiator failure, which can result in leaks and 

property damage NOT covered under the Myson Warranty.

Step 1  Fill and vent the system.

Step 2  Run the system for two (2) hours at full temperature with all radiator valves in the open position.

 

Step 3  Shut off and drain the system while the water is still hot. 

Step 4  Refill the system.

Step 5  Reheat, vent, and balance the system.

Step 6  Once the 

T6

 Radiator is filled with water the system should be left filled.

Step 7  System should be checked for leaks on seasonal start-ups. Leaks must be repaired 

as automatic system fill valves allow fresh water/oxygen into the system attacking 

radiators internally.

SYSTEM START-UP

MAINTENANCE  &  CLEANING

1

 

Once  operating,  avoid  the  introduction  of  fresh  water  and  oxygen  to  the  system  to  prevent  corrosion.

 

2  An occasional wiping with a damp cloth using a non-abrasive detergent can protect the finish of your

    

Myson radiator.

3

 

The use of abrasive cleaners will damage the surface of your radiator and void the manufacturer’s warranty.

DESIGN AND LAYOUT CONSIDERATIONS:

Myson  radiators  should  only  be  used  with  recirculation  pump

 closed loop hydronic heating systems

 such as 2 pipe 

reverse  return,  2  pipe  direct  return,  1  pipe  monoflo  or  homerun  piping  systems.  Series  loop  piping  is  not 

recommended. Myson radiators are not for use in gravity or steam systems.  Position  your  radiator  away  from  your

 

circulator pump to avoid either excess pressure that could force water out the air vent or excess suction that could 

draw  air  into  the  system.    The  suggested  location  for  your  Myson radiator,  where  possible,  is  below  a  window 

where  it  can  minimize  downdrafts  from  glazed  areas.    Mounting  the  radiator  a minimum of 4 inches off the floor

 

will

a

provide

a

for

a

adequate

a

convection.

 

Myson 

T6 

radiators are supplied with 

drain plug, vent plug, mounting brackets

 

and 

TRV insert.

NOTE! 

For 

instuctions on how to connect the T6 radiator using the 4 side connections please consult the 

"Optional Side Connection Installation Addendum"

available at MysonComfort.com. 

VALVE ROUGH-IN: 

The

  Myson 

T6 

radiator 

is  intended  to  be 

install

ed  using  the  bottom  center  3/4" 

connections.

 

The supply MUST be connected to the left hand connection as you face the radiator in order for the 

internal thermostatic valve to work.

MOUNTING:  Myson 

T6

  radiators  are  supplied  with  welded  mounting  lugs 

located 

3

-15/16"  in  from  each  end.

 

These  lugs  accept  the  included  KOM 

(BH) 

wall  brackets.  Optional  SIGARTH  brackets  may  be  positioned 

anywhere along the length of the radiator to accommodate retofit appplications

 

For  more  detailed  bracket  installation  dimensions  and  mounting  positions  please  consult  the 

detailed  installation  manual  available  at  MysonComfort.com  and/or  the  assembly    instructions 

included with the mounting brackets. 

SAFETY PRECAUTIONS

Radiators  are  hot  when  in  use,  and  as  such,  present  a  risk  of  burns  to  users  on  prolonged  contact.  The 

temperature of a

 

radiator is dependent on the temperature of the system water, as set by the system installer 

or  user.    Installers

 

and  users  should  take  all  necessary  steps  to  minimi

z

e  the  risks  of  burns.  If  the  risk  is 

significant, consideration should be

 

given to installing low surface temperature radiators, or to placing guards in 

front of the radiators.

For the correct installation of radiators it is essential that the 

mounting

 of the radiator 

to the wall 

is carried out 

in such a way

 

that it is suitable for intended use AND predictable misuse. 

VENT LOCATION:

 

The 

vent and the internal valve location can be reversed in the field

.

 

Standard 

Connections:

4 x internal thread G 1/2“ BSP side 4 corners

2 x external thread G 3/4" bottom center 

Maximum positive operating pressure

 145 psi 

Maximum operating temperature: 230° F

10

10

10

Pictured is the optional HV-S valve

commonly installed when using the

bottom center connections. (Also 

available is the HV-A angle version)

Jan 2019