background image

General

DECOR

 SERIES

 RADIATOR

 

Installation

 Guide

Connections:

 

4 - 1/2" B.S.P. (British Standard Pipe) 2 per side

 

Maximum positive operating pressure:

 

Standard design: 72 psi

 

Maximum positive operating pressure:  High-pressure design: 116 psi 

Maximum operating temperature: 230° F           

rectangular steel tubes,

 

2-3/4"x7/16"x16 ga.

 

rectangular steel tubes, 2-3/4"x7/16"x14 ga.

Myson Inc./Rettig USA  45 Krupp Drive, P.O. Box 1460,  Williston,  VT 05495 www.mysoncomfort.com

A variety of matching valves 

and other accessories are

 available and recommended from MYSON. For 

specific  applications  see  our 

d

etailed  installation  and  technicals  manuals 

and  price  book 

which 

are 

available on our web site.

It  is  assumed  that  the  installer  has  the  appropriate  technical  knowledge  related  to  building  codes, 

standard  trade practices, and proper use of the tools of the trade. 

Myson  radiators  should  only  be  used  with  recirculation  pump

 closed loop hydronic heating systems

 such as 2 pipe 

reverse  return,  2  pipe  direct  return,  1  pipe  monoflo  or  homerun  piping  systems.  Series  loop  piping  is  not 

recommended. Myson radiators are not for use in gravity or steam systems.  Position  your  radiator  away  from  your

 

circulator pump to avoid either excess pressure that could force water out the air vent or excess suction that could 

draw  air  into  the  system.    The  suggested  location  for  your  Myson radiator,  where  possible,  is  below  a  window 

where  it  can  minimize  downdrafts  from  glazed  areas.    Mounting  the  radiator  a minimum of 4 inches off the floor

 

will

a

provide

a

for

a

adequate

a

convection.

aa

(3

3

/

16

"

a

minimum

a

for

a

2H

a

baseboard)

Myson radiators are supplied with drain plugs, vent plugs, and mounting brackets.

Failure to flush system of debris and flux may cause premature radiator failure, which can result in leaks and 

property damage NOT covered under the Myson Warranty.

Step 1  Fill and vent the system.

Step 2  Run the system for two (2) hours at full temperature with all radiator valves in the open position.

 

Step 3  Shut off and drain the system while the water is still hot. 

Step 4  Refill the system.

Step 5  Reheat, vent, and balance the system.

Step 6  Once the Décor Radiator is filled with water the system should be left filled.

Step 7  System should be checked for leaks on seasonal start-ups. Leaks must be repaired 

as automatic system fill valves allow fresh water/oxygen into the system attacking 

radiators internally.

SYSTEM START-UP

MAINTENANCE  &  CLEANING

1

 

Once  operating,  avoid  the  introduction  of  fresh  water  and  oxygen  to  the  system  to  prevent  corrosion.

 

2  An occasional wiping with a damp cloth using a non-abrasive detergent can protect the finish of your

    

Myson radiator.

3

 

The use of abrasive cleaners will damage the surface of your radiator and void the manufacturer’s warranty.

DESIGN AND LAYOUT CONSIDERATIONS:

NOTE! 

For optimum performance connect the supply to the top and the return to the bottom of the opposite side. Bottom 

supply and return will result in a 5% reduced heat output. (See online manual for detailed piping diagrams.)

VALVE ROUGH-IN:  When  using  Myson  radiator  valves  to  install  your  radiator  add  the  following  distance  from 

the end of the radiator to the center of your Supply/Return pipe

 for each valve.

 

For 2TRV1/2AN and LKD16AN valves add 1-3/4"   ---   For 2TRV1/2IN and FF16LAC/FF16WAC valves add 1-5/8"

MOUNTING: Myson horizontal radiators 3H to 11H are supplied with welded mounting lugs 

located 

6-15/16" in 

from each end. Myson vertical radiators  V11  are supplied with welded mounting  lugs 

located 

4-1/4" in from 

each  end  (top  and  bottom).

 

Pedestal  style  radiators  H34  are  supplied  with 

adjustable  height 

stands.  Myson 

baseboard  style  radiators  2H  are  supplied  with  the  appropriate  number  of  brackets  for  each  length. 

(See 

Mounting Detail Supplement for more information)

For  more  detailed  bracket  installation  dimensions  and  mounting  positions  please  consult  the 

detailed  installation  manual  available  at  MysonComfort.com  and/or  the  assembly    instructions 

included with the mounting brackets. 

SAFETY PRECAUTIONS

Radiators  are  hot  when  in  use,  and  as  such,  present  a  risk  of  burns  to  users  on  prolonged  contact.  The 

temperature of a

 

radiator is dependent on the temperature of the system water, as set by the system installer 

or  user.    Installers

 

and  users  should  take  all  necessary  steps  to  minimi

z

e  the  risks  of  burns.  If  the  risk  is 

significant, consideration should be

 

given to installing low surface temperature radiators, or to placing guards in 

front of the radiators.

For the correct installation of radiators it is essential that the 

mounting

 of the radiator 

to the wall 

is carried out 

in such a way

 

that it is suitable for intended use AND predictable misuse. 

VENT LOCATION:

 

The radiator vent should be located on the return side of the radiator at the top tapping.

 

DECOR

10

10

10

MAR 2016