4. PREVENTATIVE MAINTENANCE PROCEDURES 
 

WIRE CONNECTIONS 

All power wire connections should be inspected for tightness one (1) month after 
commissioning and every six (6) months thereafter. 

 

CAPACITOR CELLS 

Capacitor cells should be visually checked for distorted tops one (1) month after 
commissioning and every six (6) months thereafter. 

 

INDICATION LIGHTS 

 

Blown fuse indication lights may be checked daily. 

 
 

CLEANLINESS  

Every six (6) months the fan filters should be inspected and cleaned or replaced 
and the unit should be clean of all contaminants. Note: DO NOT USE HIGH 
PRESSURE LIQUID TO CLEAN UNITS. 
 

 

CONTACTORS  

Remove covers and visually check contacts for signs of wear and excessive arcing 
every six (6) months. Energize each contactor with the controller in "manual" mode 
to ensure proper operation.  
 

How to Check Fuses: 

 

Trouble: Fuse light is illuminated. 

 

This indicates that a fuse is blown. Typically, power surges or a bad capacitor 
causes a fuse to blow. 

 

Disconnect power

 from the capacitor unit and wait one minute after the 

power has been disconnected to allow the capacitors to discharge. 

 

Check affected capacitor following steps below: 

How to Test a Capacitor Cell

 

Replace affected fuse. 

 

How to Test a Capacitor Cell: 

 

With a Capacitance Meter

 

Capacitor cells are rated in microfarad and voltage. The easiest way to test a cell 
is to measure the microfarads with a capacitance meter. 

 

Disconnect power 

from the capacitor unit and wait one minute after the 

power has been disconnected to allow the capacitors to discharge. 

 

Measure microfarads using a capacitance meter. The microfarads should be 
equal to the microfarad rating or up to 5% over the rating. 

 

If microfarads are below the minimum, the cell is going bad. 

 

Replace bad capacitor cells. 

 

Visual Inspection of Cell

 

If a capacitor meter is not readily available, the status of a cell can sometimes be 
determined visually. 

 

If the cell can is "bulged out" or "pouched up" on the top, it is definitely bad. 

 

Disconnect power 

from the capacitor unit and wait one minute after the 

power has been disconnected to allow the capacitors to discharge. 

 

Replace bad capacitor cells. 

 
 
 