MyMeters MM-SDM630-2C User Manual Download Page 2

Secondary PT setting
 
The setting method is same 

as Primary voltage setting 
PT1. Max PT2 value is 500V

Set PT Ratio Value

Press             to enter the 
PT Ratio. The range is from 

0001~9999.

From the Set-up menu, use
        and        buttons 
to select the PT option. 
The screen will show the 
voltage PT secondary 

voltage value.

Press              to exit the system selection routine and return 
to the menu. SET will disappear and you will be returned to 
the main Set-up Menu.

4.7 Pulse Output

This option allows you to configure the pulse output. The 

output can be set to provide 2 pulses, Pulse 1 is lock to C1, 

and Pulse 2 is lock to C2. The setting will be effective for both 

pulse outputs. Use this section to set up the pulse output 

(Units: kWh, kVarh)

From  the  Set-up  menu,  use              
         and         buttons 
to select the Pulse output 

option.

Press               to enter the 

selection routine. The unit 

symbol will flash.

Use              and             
buttons to choose kWh 

or kVArh.

On completion of entry procedure, press              to confirm 

the setting and press              to return to the main set 
up menu.

4.7.1 Pulse Rate

Use this to set the energy represented by each pulse. Rate can 

be set to 1 pulse per 0.01/0.1/1/10/100/1000kWh/KVArh.

(It shows 1 impulse = 

10kWh/kVArh)

Press          to enter the 
selection routine. The cur-

rent setting will flash. Use        

and          and         buttons 
to choose pulse rate.

From  the  Set-up  menu,  use             
         and         buttons 
to select the Pulse Rate 

option.

On completion of the entry procedure, press              to 

confirm the setting and press              to return to the main 

set up menu.

4.7.2 Pulse Duration

The energy monitored can be active or reactive and the pulse 

width can be selected as 200, 100 or 60ms.

(It shows pulse width 
of 200ms)

From  the  Set-up  menu,  use             

         and         buttons 

to select the Pulse width 
option.

Press          to enter the se-
lection routine. The current 

setting will flash. 

200/100/60ms

Use            and    
buttons to choose pulse 
width.

On completion of the entry procedure, press              to 

confirm the setting and press              to return to the main 

set up menu.

4.8 Communication

There is a RS485 port can be used for communication using 

Modbus RTU protocol. For Modbus RTU, parameters are 

selected from Front panel.

From  the  Set-up  menu,  use                  
        and         buttons to 

select the Address ID.

Press               to enter 
the selection routine. The 

current setting will be 

flashing.

Use              and             
buttons to choose Modbus 
Address (001 to 247).

On completion of the entry procedure, press              button 

to confirm the setting and press              button to return to 

the main set-up menu.

4.8.2 Baud Rate

From  the  Set-up  menu,  use              

        and         buttons to 
select the Baud rate option.

Press               to enter 
the selection routine. The 

current setting will flash.

Use              and             
buttons to choose Baud 

rate 2.4k, 4.8k, 9.6k, 19.2k, 
38.4k.

On completion of the entry procedure, press              to 

confirm the setting and press             to return to the main 

set-up menu.

4.8.3 Parity

From  the  Set-up  menu,  use              
        and         buttons to 

select the Parity option.

Press               to enter 

the selection routine. The 

current setting will flash.

Use              and             
buttons to choose Parity 

(EVEN / ODD / NONE). 
Default is NONE.

On completion of the entry procedure, press              to 

confirm the setting and press             to return to the main 

set-up menu.

4.8.4 Stop Bits

From  the  Set-up  menu,  use              

        and         buttons to 
select the Stop Bit option.

Press               to enter 
the selection routine. The 

current setting will flash.

Use              and             
buttons to choose Stop Bit 
(2 or 1).

On completion of the entry procedure, press              to 

confirm the setting and press             to return to the main 

set-up menu.

5. Specifications

5.1 Measured Parameters

The unit can monitor and display the following parameters of 

a single phase, 3-phase 4-wire supply.

5.1.1 Voltage and Current

• 

Phase to neutral voltages 100 to 289V a.c.

• 

Voltages between phases 173 to 500V a.c.

• 

Percentage total voltage harmonic distortion (THD%) for 
each phase to N

• 

Percentage voltage THD% between phases

• 

Current on each phase – 1 to 9999A range, set by external 
current transformer(s) (CTs) 

• 

Current THD% for each phase

5.1.2 Power Factor and Frequency and 

Max. Demand

• 

Frequency in 

• 

Hz Instantaneous power

• 

Power 0 to 3600 MW

• 

Reactive Power 0 to 3600 MVAr

• 

Volt-amps 0 to 3600 MVA

• 

Maximum demanded power since last 

• 

Demand reset Power factor 

• 

Maximum neutral demand current, since the last Demand 

reset

5.1.3 Energy Measurements

• 

Imported active energy  

0 to 9999999.9 kWh

• 

Exported active energy 

0 to 9999999.9 kWh

• 

Imported reactive energy 

0 to 9999999.9 kVArh

• 

Exported reactive energy 

0 to 9999999.9 kVArh

• 

Total active energy 

0 to 9999999.9 kWh

• 

Total reactive energy 

0 to 9999999.9 kVArh

5.2 Measured Inputs

Voltage inputs through 4-way fixed connector with 2·5mm2 

stranded wire capacity. Line frequency measured from L1 
voltage or L3 voltage.

 
Three current inputs (six physical terminals) with 2.5mm2 

stranded wire capacity for connection of external CTs. 
Nominal rated input current 5A or 1A a.c. Rms.

5.3 Accuracy

Voltage 

 

0.5% of range maximum

Current 

 

0.5% of nominal

Frequency 

 

0.2% of mid-frequency

Power factor 

 

1% of unity (0.01)

Active power (W) 

±1% of range maximum

Reactive power (VAr) 

±1% of range maximum

Apparent power (VA) 

±1% of range maximum

Active energy (Wh) 

Class 1 IEC 62053-21

Reactive energy (VARh) 

±1% of range maximum

Total harmonic distortion 

1% up to 31st harmonic

5.4 Power Supply

Two-way fixed connector with 2.5mm2 stranded wire capacity.

 

The meter is powered from Phase L1. The user must make 

sure the meter Phase 1 has power on.

5.5 Interfaces for External Monitoring

Three interfaces are provided:

• 

an RS485 communication channel that can be programmed 
for Modbus RTU protocol.

• 

an output indicating real-time measured energy.

(configurable)

• 

an pulse output 3200imp/kWh (not configurable).

The Modbus configuration (Baud rate etc.) and the pulse 

output assignments (kW/kVArh, import/export etc.) are 

configured through the Set-up screens.

5.5.1 Pulse Output

The pulse output can be set to generate pulses to represent 

kWh or kVArh. 
Rate can be set to generate 1 pulse per: 
0.01 = 10 Wh/VArh 
0.1 = 100 Wh/VArh 

1 = 1 kWh/kVArh 

10 = 10 kWh/kVArh 
100 = 100 kWh/kVArh 
1000 = 1000 kWh/kVArh 

Pulse width 200/100/60 ms.

5.5.2 RS485 Output for Modbus RTU

For Modbus RTU, the following RS485 communication 

parameters can be configured from the Set-up menu:

Baud rate 2400, 4800, 9600, 19200, 38400 
Parity none/odd/even 
Stop bits 1 or 2 

RS485 network address nnn – 3-digit number, 001 to 247

MyMeters.com 
Unit 4, 59 Beattie St, Kallangur QLD 4503 Australia 
Tel: 1300 METERS (1300 638 377) 
Email: [email protected] 
web: www.mymeters.com

MID

7.3 Six Circuits Single Phase Two Wire

7.2 One Circuit Three Phase Four Wire +

Three Circuits Single Phase Two Wire

7.1 Two Circuits Three Phase Four Wire

7. Installation

6. Dimensions

105mm

35mm

92mm

65mm

4.8.1 RS485 Address

(The range is from 001 to 247)

4.9 CLR

The meter provides a function to reset the maximum demand 

value of current and power.

From  the  Set-up  menu,  use                  
        and         buttons to 

select the reset option.

Press               to enter the 
selection routine. The dlt 

will flash.

Press             button to confirm the setting and press              

to return to the main set up menu.

Modbus™ Word order Hi/Lo byte order is set automatically 

to normal or reverse. It cannot be configured from the 

set-up menu.

5.6 Reference Conditions of Influence 

Quantities

Influence Quantities are variables that affect measurement 

errors to a minor degree. Accuracy is verified under nominal 
value (within the specified tolerance) of these conditions.

• 

Ambient temperature  

23°C ±1°C

• 

Input waveform  

50 or 60Hz ±2%

• 

Input waveform  

Sinusoidal (distortion  

 

 

factor < 0.005)

• 

Magnetic field of external origin Terrestrial flux

5.7 Environment

• 

Operating temperature 

-25°C to +55°C*

• 

Storage temperature 

-40°C to +70°C*

• 

Relative humidity 

0 to 90%, non-condensing

• 

Altitude 

 

Up to 3000m

• 

Warm up time  

1 minute

• 

Vibration 

 

10Hz to 50Hz, IEC 60068- 

 

 

2-6, 2g

• 

Shock 

 

30g in 3 planes

CT3

CT2

CT1

CT3

CT2

CT1

Cir

cuit 1

Cir

cuit 2

N L3 L2 L1

1a fast blow fuses

CT input for Circuit 1

CT input for Circuit 2

L32  L31  L22  L21  L12  L11

L32  L31  L22  L21  L12  L11

Voltage Input

Pulse 1 Pulse 2 RS485

N    L3           L2           L1

-       +     -      +     B      A

CT3

CT2

CT1

CT3

CT2

CT1

Cir

cuit 1

Cir

cuit 2

N L3 L2 L1

1a fast blow fuses

CT input for Circuit 1

CT input for Circuit 2

L32  L31  L22  L21  L12  L11

L32  L31  L22  L21  L12  L11

Voltage Input

Pulse 1 Pulse 2 RS485

N    L3           L2           L1

-       +     -      +     B      A

CT3

CT2

CT1

CT3

CT2

CT1

Cir

cuit 1

Cir

cuit 2

N          L1

1a fast blow fuses

CT input for Circuit 1

CT input for Circuit 2

L32  L31  L22  L21  L12  L11

L32  L31  L22  L21  L12  L11

Voltage Input

Pulse 1 Pulse 2 RS485

N    L3           L2           L1

-       +     -      +     B      A

Reviews: