GENERAL DESCRIPTION AND USES

The WHR and WHRH Series are solids handling 

pumps that can be used to pump RAW SEWAGE 

for COMMERCIAL and DOMESTIC use, but are 

not intended to handle large rags, mop heads, or 

strings. All pumps can be used for normal sump 

duty where extra capacity is required.

The WHRE Series is for pumping sump water 

and EFFLUENT from septic tanks only. DO NOT 

USE FOR RAW SEWAGE.

RECESSED IMPELLERS

All of the pumps are of the recessed impeller 

type that provides a clear volute passage for 

solids as no solids pass through the impeller.

All of the pumps listed can be used to pump 

septic tank EFFLUENT or GROUND sewage as 

used in some pressure sewer systems.

DOUBLE SEAL PUMPS

All double seal models have two seals with an oil 

chamber between the seals so that seal faces of 

both lower and upper seals are oil lubricated for 

longer life and greater protection against water 

leaking into the motor windings. These double 

seal units are made with and without a seal leak 

probe. The leak probe in the oil seal chamber 

detects any water leakage into the chamber and 

turns on a red signal light in the control panel. 

Pumps should be removed from sump and seals 

replaced after seal light shows in the panel. 

Control panels must be used for pumps having 

the seal leak probe. 
Double seal pumps without the seal leak probe, 

should be pulled and seal leak checked in 12 to 

18 months. 

LEVEL CONTROLS

All pumps must use sealed level control switches 

for automatic operation. MLC and MFLC controls 

have sealed mercury* switches that are 1 H.P. 

rated at 230 volts. ALC and AWS-1 controls have 

sealed mechanical switches that are rated 2 H.P. 

at 230 volts. 

Simplex single phase pumps can be made 

automatic by attaching MFLC or MLC controls 

to pump. These switches have a fixed draw off 

level of 8 to 10” and can be used up to 1 H.P. For 

higher H.P. ratings two mercury* switch (or SMNO) 

controls with a magnetic starter can be used. 
The ALC and AWS-1 controls can be used for 

simplex single phase pumps with ratings up to 2 H.P.

 

 

 

 

 

 

 

3  

 

 

 

 

         

23833A201

Plug in cords can be used on all the single phase 

pumps without seal leak detector. The cord 

has a GROUND pin that plugs into a grounded 

receptacle. The grounded receptacle cannot be 

used in the wet sump or basin due to DANGER 

of current leakage. 
Sealed junction boxes must be used in wet sumps 

or basins to make connections to motor cord. The 

AWS-1 control also acts as a sealed junction box 

for connecting power cord to pump cord. 

SAFETY WARNING

All pumps single or three phase must have a 

GROUND WIRE that is connected to a screw 

in the metal pump housing. This wire goes to 

the control box and is connected to a good 

outside GROUND such as a metal water pipe or 

GROUND STAKE driven at least 6 feet into the 

ground. 

MOTOR TYPES

All single phase pump motors are of the 

permanent split capacitor type that do not 

require a start switch or start relay. 
Automatic reset overload switches are attached 

directly to the motor windings. 
Three phase pump motors require a magnetic 

starter with 3 leg overload protection.

INSTALLATION

Pumps can be installed inside sealed basin 

with proper venting for either simplex or duplex 

systems. SIMPLEX or DUPLEX basin systems 

are available. See Figs. 3 and 4.
It is not recommended that basins be used for 

RAW SEWAGE inside the home, but are for use 

in office buildings and small industrial buildings 

and factories.

*This product contains mercury and must be disposed of according to local 
and federal codes.

Summary of Contents for WHR

Page 1: ...E WASTE HANDLING SUMP PUMPS Installation and Servicing Instructions for Myers WHR WHRH and WHRE Submersible Sump Pumps Single Three Phase Power Single Double Seal 23833A201 Rev 6 09 SINGLE SEAL PUMPS DOUBLE SEAL PUMPS ...

Page 2: ...A201 2 TYPICAL SECTIONAL DRAWINGS FOR WHR WHRH AND WHRE SINGLE AND DOUBLE SEAL WASTE HANDLING PUMPS SINGLE SEAL FIG 1 WHR WHRH WHRE DOUBLE SEAL FIG 2 WHR DS WHR SD L D WHRH DS WHRH DS L D WHRE DS WHRE DS L D ...

Page 3: ... 2 H P at 230 volts Simplex single phase pumps can be made automatic by attaching MFLC or MLC controls to pump These switches have a fixed draw off level of 8 to 10 and can be used up to 1 H P For higher H P ratings two mercury switch or SMNO controls with a magnetic starter can be used The ALC and AWS 1 controls can be used for simplex single phase pumps with ratings up to 2 H P 3 23833A201 Plug ...

Page 4: ...NTROL CORD OPTIONAL ALARM CORD STEEL BASIN COVER EPOXY COATED SEALED TO BASIN WITH CAULKING COMPOUND CAST IRON PUMP COVER SEALS WITH RUBBER GASKET NEMA 1 DUPLEX CONTROL BOX 3 VENT PIPE 2 GATE VALVE 3 DISCHARGE PIPE 10 36 CV 200 CHECK VALVE OVERRIDE CONTROL START CONTROL WASTE HANDLING PUMPS STOP CONTROL 2 PUMP PIPING CAN BE 3 IF REQUIRED 11 2 CONDUIT BUSHING 11 2 CONDUIT O RING SEAL INLET FLANGE F...

Page 5: ...apped air Re tighten union 2 With 2 float controls turn on power at the control box and run water into sump When level gets above top control pump should start and continue to pump until level drops to lower control stopping pump Run pump through several cycles If pump runs but does not pump check air lock as in 1 Leave power on for automatic operation 3 Where ALCL or AWS 1 controls are used plug ...

Page 6: ...ol boxes mounted remote from the sump tank are generally of plastic construction for best corrosion resistance See Fig 4 MOTOR OVERLOAD PROTECTION All single phase motors have built in automatic reset overload switches fastened directly to the motor windings All 3 phase motors must be installed with magnetic starters having 3 leg overload protection HOW TO SET CONTROLS AND START SIMPLEX SYSTEMS 1 ...

Page 7: ... to be pinched or shorted when the door is closed See wiring diagrams page 8 4 All three phase motors can run either direction ROTATION can be changed by interchanging any two line leads at magnetic starter BE SURE CIRCUIT BREAKER IS OFF BEFORE MAKING THIS CHANGE To find if rotation is correct operate pumps and check delivery operation If flow and head is low refer to pump curves shown in this man...

Page 8: ...PLICES CONNECTORS GROUND SCREW MOTOR STATOR 230 VOLT 3 PHASE GREEN T3 B B B T4 T5 T6 T7 T8 T2 T9 T1 POWER CORD POTTING RESIN SPLICES CONNECTORS GROUND SCREW MOTOR STATOR 460 VOLT 3 PHASE GREEN T3 B B B T4 T5 T6 T7 T8 T2 T9 T1 WIRING DIAGRAMS FOR 3 PHASE MOTORS FOR SINGLE SEAL PUMPS AND DOUBLE SEAL PUMPS WITHOUT SEAL LEAK PROBE 23833A201 8 ...

Page 9: ...TAL HEAD IN FEET TOTAL HEAD IN METERS 0 20 40 60 80 100 120 140 80 70 60 50 40 30 20 10 24 22 20 18 16 14 12 10 8 6 4 2 0 PERFORMANCE CURVE WHRH SERIES WASTE HANDLING PUMPS WHRH5 1 2 HORSEPOWER WHRH10 1 HORSEPOWER WHRH20 2 HORSEPOWER CAPACITY LITERS PER MINUTE 0 100 200 300 400 500 600 700 CAPACITY GALLONS PER MINUTE TOTAL HEAD IN FEET TOTAL HEAD IN METERS 0 20 40 60 80 100 120 140 160 180 200 34 ...

Page 10: ...ED BY LOCAL CODES SLUDGE MOUND TYPE SEEPAGE BED AWS 1 CONTROL STORAGE CAPACITY IN CASE OF PUMP OR POWER FAILURE TURN ON LEVEL TURN OFF LEVEL EFFLUENT AND PUMP TANK SLUDGE FLCW ALARM CONTROL LIFT OUT GUIDE RAIL SEAL FITTING EFFLUENT PUMP 23833A201 10 FIG 5 FIG 5 PUMP IN SEPARATE TANK PUMPING TO SEEPAGE MOUND ...

Page 11: ...VALVE DISCHARGE TO LEACH FIELD OR PRESSURE SEWER 4 CONNECTING PIPE EFFLUENT PUMP AVAILABLE FOR HEADS OVER 100 FT BURIED CABLE TO POWER SUPPLY VENT PIPE STORAGE CAPACITY IN CASE OF POWER OR PUMP FAILURE SCUM PUMP OFF CAPACITY TURN OFF LEVEL TURN ON LEVEL 4 CLARIFIED EFFLUENT SEPTIC TANK SIZE ACCORDING TO CODE REGULATIONS SLUDGE SLUDGE CLEAN OUT TILE WASTE LINE FROM HOUSE 11 23833A201 FIG 6 PUMP INS...

Page 12: ...SHUT OFF VALVE DISCHARGE TO LEACH FIELD OR PRESSURE SEWER EFFLUENT PUMP SUPPORTED BY RAIL SYSTEM AVAILABLE FOR HEADS OVER 100 FT BURIED CABLE TO POWER SUPPLY STORAGE CAPACITY IN CASE OF POWER OR PUMP FAILURE SCUM PUMP OFF CAPACITY TURN OFF LEVEL TURN ON LEVEL 4 CLARIFIED EFFLUENT SEPTIC TANK SIZE ACCORDING TO CODE REGULATIONS SLUDGE SLUDGE CLEAN OUT TILE WASTE LINE FROM HOUSE 23833A201 12 Fig 7 FI...

Page 13: ...WAYS UN PLUG CORD OR TURN OFF CIRCUIT BREAKER BEFORE DOING ANY WORK ON THE PUMP If control panel is remote from pump disconnect lead wires to motor so that someone cannot turn the circuit breaker back on If motor is three phase mark the leads so they can be replaced in same order DISMANTLING PUMP FOR REPLACEMENT OF PARTS Clean pump thoroughly Knock off all scale and deposits Use sandblast if possi...

Page 14: ...described above Disconnect cord leads from motor and remove ground screw 2 Unscrew cord bushing and remove from hous ing Fig 14 3 Replace with new fitting and cord be sure O ring seal is in place Fig 14 4 Replace ground screw and re connect motor wires Wiring diagram is given in these instruc tions ...

Page 15: ...as thread is right hand Fig 18 6 Unscrew impeller turn counter clockwise to loosen Fig 19 7 Pry off seal with screwdrivers It is not important if seal is damaged as it must be replaced Replace both parts of seal never one or the other Fig 20 8 Bump shaft on end with plastic hammer to push ball bearing from lower motor plate Fig 21 9 Clean seal cavity thoroughly before replacing ceramic seal Use gr...

Page 16: ...with stator pressed in Both housing and stator must be replaced as a unit as stator is pressed in at factory and is not to be replaced in the field Fig 24 12 In reassembly be sure rubber seal ring and thrust washer are in place as shown Fig 25 Fig 19 Fig 17 Fig 18 Fig 16 ...

Page 17: ... 17 23833A201 Fig 21 Fig 20 Fig 23 Fig 22 ...

Page 18: ...mic seat Break seats if necessary to get out as they must be replaced with new parts 6 NEVER USE OLD SEAL PARTS USE ONLY COMPLETELY NEW SEALS 7 Remove snap ring with snap ring pliers 8 Pry off upper seal bellows and ceramic seat 9 If no water has entered motor housing check winding with ohmmeter or megger wipe seal chamber thoroughly and replace seals 10 Replace oil in motor housing and seal chamb...

Page 19: ... Flange Available 59 16 123 32 11 2 INLET 203 8 191 2 WHRH WHRH DS 113 4 41 4 59 16 41 4 81 2 17 8 171 2 165 8 59 32 11 2 INLET 21 8 2 NPT 2 NPT 59 32 21 8 11 2 INLET 193 4 187 8 WHRE WHRE DS 12 41 4 53 4 41 4 81 2 15 8 19 181 8 61 2 11 2 INLET 2 2 NPT 2 NPT 61 2 2 11 2 INLET 211 4 203 8 WHR WHR DS 19 23833A201 PUMP DIMENSIONS ...

Page 20: ......

Page 21: ......

Page 22: ...intain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used...

Page 23: ......

Page 24: ...ing Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junction Box __________________________________Manufacturer of Junction Box ______________ Are Floats Installed in Wet Well Yes No Are Floats Set to Engineer s Specs Yes No Are Floats Wired for Proper S...

Reviews: