147
EMERGENCY
SHUTDOWN
FINISHED
2.4.9 EMERGENCY SHUTDOWN PROCEDURE
TURN-OFF BOTH THE AC & BATTERY BREAKER IN AN EMERGENCY. The MP2000E BBS contains more
than one live circuit. In an emergency, AC line power may be disconnected at the sy
stem’s input, but output
AC power may still be present from batteries.
For parts or technical information contact:
Myers Emergency Power Systems
TEL: (610) 868-3500
FAX: (610) 868-8686
WEB: www.myerseps.com
START
Turn OFF the battery
circuit breaker
Turn
OFF
the AC
input & output circuit
breaker
Unplug the Line
Figure 65
Cord
or turn off
the incoming utility
MP2000E BBS Front Panel
input breaker
located upstream,
supplying power
Alternate Connection