background image

Mydax, Inc. 

1M150W 

Water Cooled Chiller 

 

 

Designed for Lockheed Martin   

 
 

System Electrical Diagram

 

 
Refer to drawing #D2923, the system electrical diagram.  The central component of the electrical system is the M1001 
controller.  It is microprocessor-based and communicates with and/or controls various other circuit boards and 
components.  Most controller circuitry is laid out on circuit boards mounted in the main control cabinet.  The controller is 
powered as long as the system circuit breaker is set, receiving 24 VAC power from a bulkhead-mounted transformer. 
The controller "reads" the RTD's in the system via board M1002, the Input Circuit Board, mounted on the frame.  RTD's 
are included for the recirculating temperatures, as well as for the refrigerant circuit.  Also routed through the M1002 
board are the 100 Ohm and 120 Ohm precision RTD calibration resistor circuits.  The refrigerant valve drive signals and 
the phase monitor circuit are routed through the M1004 power board. 
 
The system interlock loop is controlled by the M1002 board.  In this application the interlock loop consists of the 
refrigerant over pressure switch, the TANK EMPTY level sensor, one power relay coil and a relay pole (RL1,B).  The 
RESET switch serves to feed power to the relay, which energizes the contactor.  When energized, the contactor feeds 
power back to the relay so the RESET switch may open up without cutting off power to the relay.  If the refrigerant 
switch or the level sensor trips, power to the loop is interrupted.  The microprocessor senses this via the contactor 
connection at pin 23 of the M1002 board.  Provided the system has power, if the loop trips out, the controller drives the 
PUSH RESET error message.  Other diagnostic messages are also sent if the level sensors are tripped.  The loop must be 
reset when the fault condition, if present, is resolved. 
 
The M1002 board also routes signals for the FILL TANK level sensor.  If this sensor trips, the controller displays the 
FILL TANK error message.  A compressor crankcase heater is provided and is powered as long as the system circuit 
breaker is set and AC line voltage is present. 
 
The M1003 board reads the DI resistivity probes;  the DI solenoid valve is driven from a digital output from the M1004 
board. 
 
A special feature exists on the M1010 board which engages a relay at a user-defined flow rate. The output of the relay is 
wired to a BNC connector located on the rear panel of the unit, labeled "Flow OK". Further description of this is 
provided in the 

Installation 

chapter. 

 

Summary of Contents for 1M150W

Page 1: ...vanced temperature control technology MYDAX INC INSTRUCTION OPERATION MANUAL 1M150W WATER COOLED CHILLER MYDAX INC 12260 Shale Ridge Road Auburn CA 95602 530 888 6662 FAX 530 888 0962 http www mydax c...

Page 2: ...YSTEM OVERVIEW 4 INSTALLATION 6 FRONT PANEL CONTROLS 8 ALARM ERROR MESSAGES 10 DIAGNOSTIC DISPLAYS 11 SERVICE WARRANTY 14 SHIPPING STORAGE PROCEDURE 15 DRAWINGS PARTS LIST FRAME DRAWING FLUID DIAGRAM...

Page 3: ...70 F 7 Gpm 40 F 20 PSI differential Electrical Service 460 480 VAC 60 Hz 3 phase 50 amp service Physical Parameters 65 H x 36 W x 58 D 1000 lbs dry weight STANDARD FEATURES This chiller is complete wi...

Page 4: ...reas where potentially harmful conditions exist and in this manual to bring attention to such conditions This chiller uses materials that are subject to environmental regulations be sure to familiariz...

Page 5: ...mpressor is hermetically sealed and no service should be required In the event that cleanup is necessary absorb oil with oil absorbent material and dispose of as a hazardous waste Follow approved clea...

Page 6: ...TD s resistance temperature devices located about the circuit The drawing shows RTD s at the discharge line leading from the recirculating pump at the return line leading to the reservoir between the...

Page 7: ...one power relay coil and a relay pole RL1 B The RESET switch serves to feed power to the relay which energizes the contactor When energized the contactor feeds power back to the relay so the RESET swi...

Page 8: ...e starting to allow the crankcase heater to separate the refrigerant from the oil CONDENSER FLOW The condenser inlet and outlet fittings are 1 stainless steel female pipe thread fittings FPT Plumb the...

Page 9: ...ow rate is visible on the front LCD display panel BYPASS VALVE To divert the recirculation flow from the output path back to the tank first open the Bypass valve then close the output flow adjustment...

Page 10: ...ition is eliminated or the MUTE ALARM switch is depressed again Pressing MUTE ALARM when no alarm is active causes the alarm to sound once and the TEST ALARM display to appear SET Enables SET TEMPERAT...

Page 11: ...decrements toggles tank temperature setpoint temperature and evaporator data view modes for multiple channel systems DECIMAL Display shows model number and software revision date and copyright RUN PU...

Page 12: ...s too close to freezing 4 C The microprocessor shuts down the system with a fatal alarm Push Reset Indicates that a fatal alarm in the interlock circuit has occurred and the operator must push the Res...

Page 13: ...a direct indicator of condenser temperature and pressure The microprocessor sends the CONDENSER HOT error message if the condenser temperature exceeds 54 C TEST PANEL 3 The first 3 sets of 4 digit nu...

Page 14: ...e the Flow OK relay below the selected GPM The output of the relay is wired to a BNC connector labeled Flow OK located on the rear panel of the unit The shield and center pin are the normally open con...

Page 15: ...setpoint temperatures of whichever recirculating channel was last selected at the Main Display and the system wide alarm history The second line indicates which recirculating channel was last selecte...

Page 16: ...use of a torch In particular service of Mydax refrigeration circuits requires attention to the following 1 Use caution to protect components from heat damage 2 Prevent any moisture from entering the...

Page 17: ...en run with water ethylene glycol should be added to the recirculating loop Verify that the concentration of ethylene glycol approaches 50 measure with a hydrometer in the recirculating loop before dr...

Reviews: