Installation Manual
3
1
2
4
(
7
)
The recommended torque setting for terminals is shown as below.
Model
I/P
O/P
NDR-75
6.9 kgf-cm (6 Lb-in)
6.9 kgf-cm (6 Lb-in)
NDR-120
10.35 kgf-cm (9 Lb-in)
10.35 kgf-cm (9 Lb-in)
NDR-240
10.35 kgf-cm (9 Lb-in)
10.35 kgf-cm (9 Lb-in)
NDR-480
10.35 kgf-cm (9 Lb-in)
10.35 kgf-cm (9 Lb-in)
(
8
)
Suggested fuse and maximum number of the SDR PSUs that can be connected to a circuit breaker at 230V are
shown as below.
Model
Fuse
Circuit breaker
C16
D16
NDR-75
T3.15A/L250V
6
13
NDR-120
T4A/L250V
5
10
NDR-240
T5A/L250V
4
10
NDR-480
T8A/L250V
3
5
(
9
)
Mounting Instruction
:
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible.
Admissible DIN rail
:
TS35/7.5 or TS35/15
For rail fastening
:
(
a
)
Tilt the unit slightly rearwards.
(
b
)
Fit the unit over top hat rail.
(
c
)
Slide it downward until it hits the stop.
(
d
)
Press against the bottom for locking.
(
e
)
Shake the unit slightly to check the locking action.
(
11
)
For other information about the products, please refer to www.meanwell.com for details.
Warning / Caution !!
(
1
)
Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do
not remove the case of the power supply by yourself!
(
2
)
Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides
together is not allowed.
(
3
)
Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
(
4
)
Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
(
5
)
Only install the unit in a pollution degree 2 environment (Note.1).
(
6
)
Please do not install the unit in places with high moisture or near the water.
"Click"