Installation Manual

 

 

 

 

Type

NDR DIN rail power supply

Series

NDR-75, 120, 240, 480

 

NDR-75-12 

INPUT: 100-240VAC 1.6A 50/60Hz  

OUTPUT: 12V 6.3A 

NDR-75-24 

INPUT: 100-240VAC 1.6A 50/60Hz  

OUTPUT: 24V 3.2A 

NDR-75-48 

INPUT: 100-240VAC 1.6A 50/60Hz  

OUTPUT: 24V 1.6A 

NDR-120-12  INPUT: 100-240VAC 2.6A 50/60Hz  

OUTPUT: 12V 10A 

NDR-120-24  INPUT: 100-240VAC 2.6A 50/60Hz  

OUTPUT: 24V 5A 

NDR-120-48  INPUT: 100-240VAC 2.6A 50/60Hz  

OUTPUT: 48V 2.5A 

NDR-240-24  INPUT: 100-240VAC 2.8A 50/60Hz  

OUTPUT: 24V 10A 

NDR-240-48  INPUT: 100-240VAC 2.8A 50/60Hz  

OUTPUT: 48V 5A 

NDR-480-24  INPUT: 100-240VAC 5.3A 50/60Hz  

OUTPUT: 24V 20A 

NDR-480-48  INPUT: 100-240VAC 5.3A 50/60Hz  

OUTPUT: 48V 10A 

 

 

Introduction 

NDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well’s DIN series, 
they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source. 

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not 
allowed. 

 
 
 
 
 
 
 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

Rated Current of 
Equipment (Amp) 

7A 

10A 

15A 

20A 

Cross-section of 
Lead(mm

2

 ) 

0.8 

1.3 

2.1 

3.3 

Note: Current each wire carries should be de-rated to 80% of the current suggested   

above when using 5 or more wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C, such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197”).   

6

Recommended screwdriver i

s 3mm, slotted type.   

 