(1) General
This unit employs many novel features previously unavailable in an industrial power supply. It has been designed to withstand the
high levels of interference found in heavy industry and has emission levels low enough for it to be used in residential, commercial
and light industrial environments.
The MPS10 has a high level of reserve power. This enables loads with significant inrush current to be supported and will also
ensure that circuit breakers will trip in the event of a short circuit.
For manual control of the output voltage, two push buttons are provided. Operation of the red “TESTSTOP” button will turn the
voltage off. Operation of the green “RESTART” button will turn it on.
WARNING!!
the output voltage always comes on when the supply is turned on.
An alarm contact is provided which will open as the unit approaches shut down due to overload or excessive temperature brought
about by lack of ventilation. If no action is taken and the temperature continues to rise, the unit will shut down but may be reset
after cooling by means of the “RESTART” BUTTON.
When the power supply is connected to the mains, there is no inrush current. The supply will monitor low supply voltage and phase
loss.
The power supply can be configured with DIP switches to work with battery back-up. A lead-acid battery can be held on float charge
with the alarm contact operating as low voltage release to prevent deep discharge.
NOTE: The unit is intended to be connected to star-connected network where the main voltage is 3 x 400 VAC (Max. Line to Earth
voltage 250 VAC).
(3) Features
[1]
Input terminal:
Conductor sizes
Solid
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded with ferrule without / with plastic sleeve
1,5 mm² / 16 AWG
Stripping length
8 mm
Tightening torque:
0,5 - 0,6 Nm / 5 - 7 lb. in.
[2]
“SHUTDOWN”-failure LED red
[3]
“RESTART”-start push button, green
[4]
“TESTSTOP”-test stop push button, red
[5]
Output“OK”-LED green
[6]
Output voltage adjust 22 - 28 VDC; when over 24 VDC is
used, must input voltage be accordingly higher.
[7]
“CURRENT LIMIT”-current limit LED
[8]
DIP-switch to set operating mode
[9]
Alarm connection contact, removable
[10]
Output terminal:
Conductor sizes
Solid
2,5 - 4 mm² / 14 - 12 AWG
Stranded
2,5 - 4 mm² / 14 - 12 AWG
Stranded with ferrule without / with plastic sleeve
2,5 mm² / 14 AWG
Stripping length
8 mm
Tightening torque:
0,5 - 0,6 Nm / 5 - 7 lb. in.
Extra parts
[11]
Screw fixing set Art. No. 89500
(4) Operating modes
Conventional power supply
The factory setting is for conventional power supply operating
mode
[12]
with a no load voltage 24,15 volts. DIP switches 1 and
3 are ON, 2 and 4 are OFF. Continuous overload, high ambient
temperature or a load current greater than 13 amps taken for longer
than 400 ms, will cause the unit to trip into the RESTART mode.
As the unit approaches shutdown, a pre-warning will be given by
the alarm contact and the yellow “CURRENT LIMIT” led
Battery backed power supply
The battery backed power supply
[13]
can be set by changing the
DIP switches 2 and 4 to ON and 1 and 3 to OFF. The load will be
energised by the power supply when the mains supply is on and
by the battery should the mains supply fail. If, due to overload, the
terminal voltage falls below 19 volts, the power supply trips to the
RESTART mode. The alarm contact will release the low voltage
relay and isolate the battery from the load. If due to mains failure,
the battery discharges to below 19 volts, the alarm contact will
release the low voltage relay and prevent deep discharge of the
battery. When the mains is restored, the power supply will start
automatically and the battery will be charged with the residual
current available after the load is supplied (I
bat
= I
max
- I
load
)
(5) Location
The power supply should be mounted horizontally (connection
terminals facing downwards). The power supply is cooled by
natural convection. It is important to maintain clearance
dimensions equal to or greater than the minimum shown on the
diagram
[14]
to ensure best performance and long term reliability.
Side clearance to other equipment sholuld be 25 mm or >50 mm
if that equipment is heat generating. The ambient temperature
should be measured on the underside of the unit. There will be an
increase of 20°C at the top. If natural convection is restricted,
forced cooling should be used. Mounting should comply with EN
60950-1 point 4.7 and 4.6.1. Protection class IP20 (EN 60529).
(6) Mounting
Rail mounting
[15]
The rail should be fixed solidly. The two 20 mm diameter washers
supplied should be fitted under the screws and will help to prevent
distortion of the rail. Mounting instructions
[16]
, / Removing
instructions
[17]
.
Screw fixing
[18]
A pair of fixing brackets, Art. No. 89500 must be attached to the
power supply with the screws provided. The keyhole brackets will
accept four M5 screws. (Screws are included).
(7) Switching on - conventional power supply
Factory set, ready to use. Check 10 and 11 for parallel and series
connection.
(8) Switching on - battery backed power supply
(lead acid)
Check the recommendations of float charge voltages from the
specification of the battery manufacturer. If the values are not
available,
the
float
charge
voltages
can
be
set
with
U-ADJ.-adjustment potentiometer as follows:
For maximum lifetime, the battery temperature should not exceed
35°C and must never exceed 40°C. NiCd batteries must not be
used.
The low voltage release relay and the battery fuse module are
available from Murrelektronik.
Always use the correctly sized fuse or circuit breaker and connect
as near to the battery as possible. Ensure that the battery
compartment is ventilated. The power supply can be damaged
by wrong battery polarity. See connections
[25].
When the mains
is disconnected, the power supply and the low voltage release
relay discharges the battery by Art. No. 89510 / 150 mA and Art.
No. 89513 / 700 mA.
(9) Loading
The nominal current is 10 A but due to the nature of industrial
loading, the power supply has been designed to support loads
with high inrush currents without damage or shutdown. Curve
[19]
shows the typical voltage / current curve. Curve
[20]
shows
the voltage / current response to dynamic 50 ms load. Curve
[21]
shows the voltage / current response to a dynamic 400 ms
load. Curve
[22]
shows the overload / temperature limit. To
ensure correct convection cooling, the unit must always be
mounted with the terminals at the bottom.
(10) Parallel connection
[23]
Up to 3 units may be connected in parallel. The open circuit
voltage of each unit should be set to same value. Accuracy of
setting will determine how well the units share the load current.
The gauge and lenght of the cable between each power supply
and the common point should be the same. Operation is based
on the electronically controlled 0.5% voltage / current slope.
Alarm contacts should be connected in series. By redundant use,
outputs must be connected through diodes, so that alarm
contacts will retain their function, Art. No. 896014. When using
a battery back-up, it is advisable to connect each power supply
to the battery positive terminal through it’s own 16 A fuse. Units
should only be used in parallel where the supply exceed 375
volts.
(11) Series connection
[24]
Up to 2 units may be connected in series to give either 48 VDC
or +/-24 VDC. Alarm contacts should be connected in series.
(12) Setting the output voltage
The open circuit voltage is factory set to 24,15 VDC. Clockwise
rotation of the “U-ADJ” potentiometer
[6]
will increase the
voltage. If the setting exceeds 28 VDC, the overvoltage
shutdown protection could operate. If this happens, reduce the
setting and press the green “RESTART” button.
(13) Alarm contact
[9]
The alarm contact is closed during normal running and opens for
phase failure, supply failure, low supply voltage, output short
circuit, overload pre-warning, high output voltage or low output
voltage when used in battery back-up mode
Note !!
The contacts can only be used on DC. Maximum 60 VDC
at 0,2 A. The resistance is approximately 3 - 6 ohms.
(14) Using circuit breakers on the power supply output
On short circuit, the power supply will trip, for example, the
following ABB-STOTZ circuit breakers:
-S201-C2A
-S201-Z4A.
We reserve the right to change this specification.
Product of the
series
In order to take the best advantage of the features that this power supply
has to offer and to ensure long term reliability for your equipment, please
read these instructions carefully before installation and use. They should
be retained for future reference. This power supply can be adapted to
lead-acid-battery and work with battery.
MPS10-3x400/24
THREE PHASE
Art. No. 85065
OPERATING INSTRUCTIONS
(2) Technical specification, Art. No. 85065
V1.4
Operation
Power Supply
Battery back-up power supply
Nominal voltage (L-L)
3 x 400 VAC
Input voltage range (L-L)
3 x 360 - 440 VAC
3 x 380 - 440 VAC
Nominal voltage (L-N)
3 x 230 VAC
Input voltage range (L-N)
3 x 208 - 250 VAC
3 x 220 - 250 VAC
Nominal frequency
50/60 Hz ±6%
Input current, I
typ
0,42 A
rms
/ 3 x 400 VAC and 24 VDC 10 A
Inrush current
none
Efficiency, typ.
90% / 3 x 400 VAC and 24 VDC 10 A
Power factor, typ.
0,80 / 3 x 400 VAC and 24 VDC 10 A
Phase watch, internal
Yes
Low voltage shutdown
Yes
External fuse max.
10 A
Safety class
1
Output voltage
24V DC (22 - 28 VDC)
24 - 28 VDC
Static regulation accuracy
+/-1%
Dynamic regulation accuracy, typ.
0->100%, 5% 1ms / 100%->5%, 5% 1ms
Start-up time
< 2,5 s / 3 x 400 VAC and 24 VDC 10 A
Hold up time of the output
> 3 ms / 3 x 400 VAC and 24 VDC 10 A
Output current, cont60°C
10 A
Output current, cont40°C
12 A
Output current, transient 50 ms
15 A
Output current, short-circuit, < 400 ms
25 A
Output ripple
< 20 mV
rms
Overloading / temperature protection
Yes
Overvoltage shutdown
> 28,5 VDC
Overcurrent shutdown
13 A / 400 ms
No
Undervoltage shutdown
21 VDC typ.,(current controlled)
19 VDC typ.
Parallel use Uin > 3x375 VAC, 5% minimum load. Max. 3 units
Yes
Alarm contact, normal closed
0,2A 60 VDC
Relative humidity
5 - 95% no condensing
Operating temperature
0°C - +60°C (0°C - +50°C UL)
Storage temperature
-25°C - +85°C
Protection class, EN 60529
IP20
Dimensions L x K x S; Weight
198 x 132 x 97 mm; 1,7 kg
Float charge
voltages 12 cells
The average long period temperature of the battery
+5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C
- maintenance
free batteries
28,0V 27,9V 27,8V 27,6V 27,4V 27,2V 27,0V 26,8V
- open lead batter-
ies
27,2V 27,1V 26,9V 26,7V 26,5V 26,3V 26,1V 25,9V
198
231
217.5
L1
L2
L3
1
2
3
4
MPS10-3x400/24
PE
3x400 VAC
L1
L2
L3
1
2
3
4
Art. No. 89510 Art. No. 89520
6
4
2
1
3
5
2
1
A1
A2
2
22-28 VDC
13
14
~
_
__
+
-
A1
A2
1
7
8
9
10
5
6
DC+
DC+
DC-
DC-
+
+
-
-
Art. No. 85065
25
L1
L2
L3
1
2
3
4
MPS10-3x400/24
DC+
DC-
PE
3x400 VAC
L1
L2
L3
1
2
3
4
DC+
DC-
9, 10
7, 8
L1
L2
L3
1
2
3
4
MPS10-3x400/24
DC+
DC-
9, 10
7, 8
48 VDC
(+/- 24 VDC)
24
L1
L2
L3
1
2
3
4
MPS10-3x400/24
DC+
DC-
PE
3x400 VAC
L1
L2
L3
1
2
3
4
DC+
DC-
9, 10
7, 8
L1
L2
L3
1
2
3
4
MPS10-3x400/24
DC+
DC-
9, 10
7, 8
24 VDC
23
2
3
4
5
6
7
8
9
10
10
1
L1
L1 L2
L2 L3
L3
3x400V
-
-
+
+
INPUT
SHUT
DOW
N
REST
A
R
T
T
EST ST
OP
OK
LIMI
T
CURRENT
CONT
A
C
T
SIGNA
L
24-28V
+
OUTPUT
U-A
DJ.
1
2
3
4
5 6
7 8 9 10
24V / 10A
t 60 C
UL t 50 C
o
o
CAUTION
CAUTION
- Read instruction manual before installation
and use. Two operating modes available
- Risk of electric shock. Do not open the
case. No user serviceable parts inside.
ATTENTION
ATTENTION
- Reportez-vous aux instructions de service
avant le montage et la mise en service de l'appareil.
- Risque d' lectrocution. Ne pas ouvrir l'appareil.
é
Ne contient pas de pi ces interchangeables
è
Deux modes op ratoires sont possibles
é
par l'utilisateur
OUTPUT: 24V , 10 A, 240 W, IP20, SELV
product of the
series
Made in Czech Republic
ß
71570 Oppenweiler
Murrelektronik GmbH
Falkenstraße 3
GERMANY
E200364
61RM
IND.CONT.EQ.
INPUT: Y (L - N) 208 - 254 V
/
(L - L) 360 - 440 V , 50/60 Hz, 0.42 A, PF 0.8
SWITCH MODE POWER SUPPLY
ART. NO. 85065
MPS10-3x400/24
60V
/0
.2A
Art. number
System size
Low voltage release relay
Battery fuse
10A
89510
89520
20A
89510
89522
30A
89513
89524