ST-94112N page 3 of 4

ELECTRICAL

A

B

Battery

R

un

5

9

13

10 11 12

14

A

B

6

A

B

7

A

B

A

B

A

B

A

B

A

B

8

1

2

3

4

ON/OFF

Switch

 

 

 

Push/Pull Solenoid

Solenoid Valve

Slave Relay

Start

Pushbutton

Coil

Distributor

Starter 

Motor

To B

2 Amp

Fuse

Flyback 

Diode

Flyback 

Diode

Flyback 

Diode

Flyback Diode

To Hold Coil

To Pull-in Coil

ON

1 2 3 4 5 6 7 8

The Figures below show typical customer switch wiring for the ST8.

Switch wiring should be run separately from other wires; 

DO NOT

route switch wires with AC power wires since voltages, that may

be induced into the switch wires, may exceed rating and cause

damage to circuits or cause false trips.

Figure 1

shows the wiring for a normally open (N.O.) SWICH-

GAGE

®

connected between terminal B and the negative power input.

A metal jumper is connected between A and B. When the SWICH-

GAGE

®

closes  the shutdown/alarm circuit will be initiated.

Figure 2

shows the wiring for a normally closed (N.C.) switch

connected to input terminals A and B. The factory installed

metal link must be removed to use this wiring. When the switch

opens the shutdown/alarm will be initiated.

Figure 3

shows the wiring for a N.O. SWICHGAGE

®

which is the

same as Figure 1 except two wires are run from terminals A and B to

the SWICHGAGE

®

. This Closed Loop™ wiring circuit monitors the

wires as well as the switch. If the circuit is opened due to a loose

connection or broken wire or the SWICHGAGE

®

closes, the shut-

down/alarm circuit will be initiated.

Figure 4

shows the ST8 internal SPDT relay in the “run” or operat-

ing mode.

Typical Wiring 

Below is a typical wiring diagram for the ST8 TATTLETALE

®

A
B

A
B

A
B

9

N.O.

N.C.

C

10 11

Figure 1: Typical N.O. 

Sensor Connection

Figure 2: Typical N.C. 

Sensor Connection

Figure 3: Typical N.O. 

Closed Loop™ Sensor Connection

Figure 4: Internal Relay

Circuit

NOTE: connect only one shutdown device 

to the ST8. Wiring for Push/Pull Solenoid, 

Solenoid Valve and Slave Relay shown for 

clarity only.

Engine Oil 

Pressure

Engine Water 

Temperature

Low 

Water 

Level

Internal Relay 

(shown in run 

mode)

ST8 

Shutdown 

Sensor Inputs

Differential 

Pressure

No Connection

No Connection

No Connection

No Connection

Sensor Lockout Switches

Remove jumper from 

terminals 12 and 13 and 

set individual sensor 

Lockout Switch for a 25 to 

35 second lockout time 

delay during startup (see 

page 4: Setting Lockout 

Switches).