Description

The 

ST8

is an eight point TATTLETALE

®

panel designed to give “first 

out”

indication of cause of alarm or shutdown. This “first out” feature means

that only the first fault will be shown by LED; this feature isolates the

primary cause of shutdown, and helps simplify troubleshooting. The

ST8 is available in two different types of mounting: flush mounting

(“F”), and gimbal mounting (“G”).

Specifications

All specifications apply to both models unless indicated.

Power Input (Operating Voltage): 

8–32 VAC, 8–40 VDC

Sensor Inputs:

8 sensor switches, normally open or 

normally closed dry contacts.

Number of Alarm Points:

ST8: 

8 first out shutdown/alarm.

Lockout Time Delay During Startup:

25 to 35 seconds (selectable for each sensor input).

Please read the following information before installing

.  

A visual inspection of this product for damage during shipping is rec-

ommended before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to

NEC and local codes.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.
Make sure the machine cannot operate during installation.
Follow all safety warnings of the machine manufacturer.
Read and follow all installation instructions.

6-3/8 in.

(162 mm)

5-11/16 in.

(144 mm)

2-3/16 in.

(56 mm)

5-7/8 in.

(149 mm)

2-7/8 in.

(73 mm)

Clearance

1-3/4 in.

(44 mm)

5-3/8 in.

(137 mm)

Gimbal

Mounting 

Bracket

3 1/2 i

G

-

8

T

S

F

-

8

T

S

DIMENSIONS

Certain danger to human safety and to equipment may

occur if some equipment is stopped without pre-warning.

It is recommended that monitored functions be limited to

alarm-only or to alarm before shutdown. 