RUN

PRE/POST-LUBE 
5.0 MIN. REMAIN

PERMISSIVE
START 

CLASS-B TIMER 
5.0 MIN. REMAIN

LOSS  OF RUN
SIGNAL

SYSTEM READY

By pressing the START/STOP

key the S1400 will scan all Class

“A” functions for shutdown.

POWER UP THE SYSTEM: 

Make sure the D-sub miniature connector from power and control cable is secured to the back of the S1400 module. The display will show:

SYSTEM READY

. Anytime primary power input signal is lost, the 

PRIMARY POWER FAILURE

message will be displayed. 

(S1400 will resume operations 
if no key is pressed within 30 sec.)

The time will count down to zero. The keys 
YES (up) and NO (down) can be used to speed up or slow
down the countdown. At the end of the prelube time the
lube relay will de-energize. The display will show:

Run signal is seen at the opto-isolator input. If engine
is running or cranking the display will show:

The time will count down to zero. The keys YES
up) and NO (down) can be used to speed up or slow
down the countdown. Display will show:

The alarm relay picks up and the fuel valve and 

ignition relays de-energize. Display will show:

PRE/POST-LUBE 

5.0 MIN. REMAIN

The time will count down to zero. The keys 
YES (up) and NO (down) can be used to speed up or slow
down the countdown. When time expires the cause of
shutdown is displayed. To clear, press the RESET key.  

If a shutdown occurs the display will show: 

If the run signal is lost

the display will show:

UNACCEPTABLE 
LUBE PRESSURE

If permissive function is being used and at the
end of the prelube time, sufficient lube pres-
sure is not reached, the display will show:

MANUAL STOP 
GROUNDING IGNIT.

To stop the compressor, while in the run mode
press  START/STOP key. The display will show:

FAULT

FAULT

FAULT

SEQUENCE OF OPERATIONS FOR ENGINE DRIVEN COMPRESSOR

SHUTDOWN 
SEQUENCE INIT.

TEST TIMER

PRESETTING PARAMETERS

TEST TIMER 
INITIALIZE  ?  (NO)

While in SYSTEM READY or RUN, press the MODE key
and the display will show:

TEST TIMER 
X.X  MIN. REMAIN

If the YES (up) key is pressed the test timer will begin and sen-
sor inputs can be tested without shutting down.
Pressing NO (down) or MODE keys will take you into the PRE-
SETTING PARAMETERS mode.
Test the sensor input (by tripping the end device), then the name
and number for the sensor will be displayed. Clear the sensor,
then press the RESET key, the display will show:

The display will show the remaining time. At the end of the test
or to cancel press the MODE key, this will take you into the
PRESETTING PARAMETERS, to return to RUN or SYSTEM
READY press the MODE key again.  

PRESET CLASS-B 
TIMER  5.0 MIN. 

While in the TEST TIMER mode, press the MODE key and the display will show:

PRESET - 0.1 MIN. 
IGN.   GND.

Press YES (up) or NO (down) keys to increase or decrease the values . Press ENTER key to
accept new values. Press MODE to display the next parameter to be set. Repeat the above
for each value to be preset. Preset displays will be shown in the following sequence every
time MODE is pressed while in PRESETTING PARAMETERS mode.

Press the MODE key again to return
to SYSTEM READY or RUN display.  

PRESET - 5.0 MIN.
PRELUBE

PRESET - 5.0 MIN.
POST LUBE

CLASS - B  TIMER 
INITIALIZE  [NO]

2

If functions are okay, the display will show: 

OK