Section 50
00-02-0695
12-06-11 -
8
-
Modbus
Register
Description
Read/
Write
Range Data
Units
Definitions
40033
Raw
count
Thermocouple
input
11
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40034
Raw
count
Thermocouple
input
12
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40035
Raw
count
Thermocouple
input
13
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40036
Raw
count
Thermocouple
input
14
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40037
Raw
count
Thermocouple
input
15
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40038
Raw
count
Thermocouple
input
16
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40039
Raw
count
Thermocouple
input
17
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40040
Raw
count
cold
junction
input
1
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40041
Raw
count
cold
junction
input
2
R
0
‐
4095
A/D
count
0
=
0.0
VDC,
4095
=
4.096
VDC
40042
Frequency
input
(hertz)
R
30
–
10,000
Hz
40043
Modbus
CTS
R
0
‐
1
state
of
signal
40044
Factory
Use
R
40045
Filtered
Temperature
thermocouple
1
R
‐
2000
to
+25000
deg
F
X10
40046
Filtered
Temperature
thermocouple
2
R
‐
2000
to
+25000
deg
F
X10
40047
Filtered
Temperature
thermocouple
3
R
‐
2000
to
+25000
deg
F
X10
40048
Filtered
Temperature
thermocouple
4
R
‐
2000
to
+25000
deg
F
X10
40049
Filtered
Temperature
thermocouple
5
R
‐
2000
to
+25000
deg
F
X10
40050
Filtered
Temperature
thermocouple
6
R
‐
2000
to
+25000
deg
F
X10
40051
Filtered
Temperature
thermocouple
7
R
‐
2000
to
+25000
deg
F
X10
40052
Filtered
Temperature
thermocouple
8
R
‐
2000
to
+25000
deg
F
X10
40053
Filtered
Temperature
thermocouple
9
R
‐
2000
to
+25000
deg
F
X10
40054
Filtered
Temperature
thermocouple
10
R
‐
2000
to
+25000
deg
F
X10
40055
Filtered
Temperature
thermocouple
11
R
‐
2000
to
+25000
deg
F
X10
40056
Filtered
Temperature
thermocouple
12
R
‐
2000
to
+25000
deg
F
X10
40057
Filtered
Temperature
thermocouple
13
R
‐
2000
to
+25000
deg
F
X10
40058
Filtered
Temperature
thermocouple
14
R
‐
2000
to
+25000
deg
F
X10
40059
Filtered
Temperature
thermocouple
15
R
‐
2000
to
+25000
deg
F
X10
40060
Filtered
Temperature
thermocouple
16
R
‐
2000
to
+25000
deg
F
X10
40061
Filtered
Temperature
thermocouple
17
R
‐
2000
to
+25000
deg
F
X10
40062
Filtered
Temperature
thermocouple
18
R
‐
2000
to
+25000
deg
F
X10
40063
Cold
junction
1
temperature
R
‐
400
to
+1850
F
deg
F
X10