HD-96044N page 2 of 4

Crank Disconnect Relay

An understanding of the crank disconnect function for your par-
ticular system is critical to speed switch installation. It is also
important to consider the 5 A current limitation of K1 relay con-
tacts. 

Figure 1

illustrates the use of a low-current pilot relay to

operate the high-current starter solenoid. In operation, battery
voltage is supplied through the normally closed contacts of the
speed switch crank disconnect relay K1. When the engine starts,
K1 energizes and its normally closed contacts open. This action
de-energizes the pilot relay and inhibits the starter from operating
until the engine nearly stops. The normally open contacts may be
used if a contact closure is required to disable the cranking func-
tion for your system.

Overspeed and Underspeed Relay

NOTE: Underspeed relay available on HD9063-USOS only.

The overspeed and underspeed functions of the speed switch may
be used in various systems to effect engine shutdown or actuate an
alarm in the event of engine overspeed or underspeed. 

Figure 2

illustrates the overspeed/underspeed function being used to control
a fuel rack solenoid. In this application, battery voltage is available
to the solenoid through normally open contacts of the relay (

K2

overspeed) (

K1

underspeed). If the engine speed exceeds the nor-

mal overspeed or underspeed set point, relay K1 or K2  energizes
and this voltage energizes the solenoid, shutting down the engine.
Similarly, the normally closed contacts may be used if engine shut-
down is to be initiated by removal of battery voltage.

I N

CR

E A S

E

I N

CR

E A S

E

CRANK

DISCONNECT

OVERSPEED

EXT.

MAG.

PICKUP

1 2 3 4 5 6 7 8 9 10 11 12

(+)

(+)

(  )

(  )

EXT.

TEST

EXT.

POWER

NC

NO

C

NC

NO

C

INTERNAL

CRANK

DISCONNECT

RELAY

CONTACTS

INTERNAL

OVERSPEED

RELAY

CONTACTS

2-3/4 in.

(70 mm)

4-1/2 in.

(114 mm)

2-1/4 in.

(57 mm)

Mounting

Holes

4 in. (102 mm)

Mounting Holes

Mounting 
Standoffs
4 Places

3/4 in.

(19 mm)

HD9063 and HD9063-USOS

1

Overspeed Relay 

K2

Contact opens on overspeed or 
underspeed and drops out solenoid.

OPTIONAL

Energize

NO

Off

Start

NO

NC

2

3

1

Underspeed Relay 

K1

NO

NC

2

3

Battery

Starter
Switch

Starter Contactor

Relay

Starter

Energize

Hold

3

2

1

Battery

Crank

Enable

Crank

Disconnect Relay

K1

Battery

Starter
Pilot Relay

To

Starter Solenoid

MOUNTING DIMENSIONS

Figure 1

Figure 2

Mounting

1. 

Drill four 3/16 in. (5 mm) diameter mounting holes (refer to

mounting hole dimensions above).

2. 

Align the plastic standoffs on the HD9063 with the 4 mounting

holes and push gently until standoffs snap into place. 

CAUTION: 

Pushing too hard could damage board.  

Mounting 

1. 

Drill four 1/4 in. (6 mm) diameter mounting holes (refer to mount-

ing hole dimensions above).

2. 

Secure with four 10-32 screws.

RELAY FUNCTIONS