A 120 ohm resistor on the Platinum Expansion communication card 

3. The Controller and Expansion RS-485 cards each have dip switches that define the unit's function 
and address.  

 

Define the Controller's RS-485 card dip switches as Main. 

 

Define the Expansion units dip switches as required. 

Table 1: Dip Switch Settings 

 

SWO Position 

SW1 Position 

Main 

Off 

Off 

Extension 1 

Off 

On 

Extension 2 

On 

Off 

Extension 3 

On 

On 

 
 

 

Figure 3: Platinum Pro Address Dip Switches  

4. Connect the relays as required. Refer to the Platinum Pro/Touch Installation manual for details. 
5. Attach the power wiring to the Expansion as shown below.  