Appendix C: Farm Premium Breeders
•
•
•
•
•
13.1
Egg Room Setup
The following procedures details the steps required to set up the Egg Room functions.
1. In
Install > Relay Layout
, define five relays as:
o
Egg room heater
o
Egg room fan 1
o
Egg room fan 2
o
Egg Room Cool
o
Humidifier
NOTE:
Refer to Relay Layout, page 107, for details on this screen.
2. In
Install > Analog Sensors
, set the input functions as Temperature Sensors and as an Egg Room
Humidity sensor
NOTE:
Refer to Analog Sensors, page 109 for details on this screen.
3. In
Install > Temperature Definition
, configure which temperature sensors operate in the egg
room.
NOTE:
Refer to Temperature Definition, page 114 for details on this screen.
4. In
Service > Humidity Calibration
, calibrate the Egg Room humidity sensor.
RELAY LAYOUT
Relay Function
Num
NO/NC
1
Hum. Egg Room Sensor
1
—
2
Egg Room Cooling
1
—
3
Egg Room Heater
1
—
4
Egg Room Fan
2
—
5
< None>
1
—
6
< None>
2
—
7
< None>
1
—
8
< None>
1
—
10
< None>
9
< None>
N.O. Relay
TEMPERATURE DEFINITION
Function
Temp. Sensor
1 2 3 4 5 6 7 8 9
Full House
√√√▪ ▪ ▪ ▪ ▪
Tunnel setting ▪ ▪ ▪ ▪ ▪ ▪ ▪
Attic
▪ ▪ ▪ √ ▪ ▪ ▪
Outside
▪ ▪ ▪ ▪ √ ▪ ▪
Egg Room
▪ ▪ ▪ ▪ √ ▪ ▪
Work Room
▪ ▪ ▪ ▪ √ ▪ ▪
Feed Area
▪ ▪ ▪ ▪ √ ▪ ▪