Note on Pipe Length
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
Refrigerant Piping Connection
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height
between the indoor and outdoor units meets the requirements shown in the following table :
The Maximum Length And Drop Height Based on Models. (Unit: m)
Liquid side
Indoor
Outdoor
Liquid side
Indoor
Outdoor
X
Liquid side
Indoor
Outdoor
X
CAUTION
Mark the data plate with the Orifice installed (for some models).
Please purchase the fittings according to the requirements in the manual strictly.
Refer the diagram when installing.
Model
Pipes
12
18
1/4"
Liquid
Gas
3/8"
1/4"
1/2"
Max. Length
(m)
25
30
Drop Height
(m)
10
20
Refrigerant
preload (m)
5
5
Additional
refrigerant (g/m)
12
12
Note: The pipes in all cases must be copper for refrigerant gas.
78
Summary of Contents for MUCNR-H11
Page 40: ...Control remoto Especificaciones del Control Remoto 40 ...
Page 41: ...Información Previa a su Utilización 41 ...
Page 42: ...BREEZE AWAY Se utiliza para evitar que el aire vaya sobre las personas 42 ...
Page 44: ...44 ...
Page 45: ...45 ...
Page 46: ... 46 ...
Page 48: ...48 ...
Page 49: ...Función Silence 49 ...
Page 68: ...Installation Summary 68 ...
Page 71: ...71 ...
Page 72: ...72 ...
Page 74: ...74 ...
Page 243: ......
Page 244: ...www mundoclima com C NÁPOLES 249 P1 08013 BARCELONA 34 93 446 27 80 ESPAÑA SPAIN ...