2. TECHNICAL DATA
MUAT-10-FBC
MUAT-10-FBC
Speed
III
II
I
Max airflow [m3/h ]
2900
2050
1150
Power supply [V/Hz]
230/50
Max current consumption [A]
1,5
1,2
0,6
Max power consumption [W]
340
240
120
IP/ Insulation
54 /F
Max acoustic pressure level [dB(A
64,1
54,5
42,1
Horizontal range** [m]
18,0
12,7
7,1
Max heating water temperature [
o
C]
70
Max operating pressure [MPa]]
1,6
Connection | Przył
ą
cze
3/4”
Installation
Indoor
Max working temperature [
o
C]
55
Device weight [kg]
23,1
Weight of device filled with water [kg]
25,8
* Acoustic pressure level has been measured 5m from the unit in a 1500m
3
space with a medium sound absorption coefficient
** Horisontal isothermal range for 0,5 m/s border air stream speed