MultiSmart Integrator Guide 

 
 

 

Page 11 of 20 

MultiSmart_Integrator_Guide_R01.doc 

P2 Pump efficiency, 
yesterday 

MotorProt.Pump._2.EfficiencyYesterday 

Frozen 
Counters 
138 

See Note 4 

Gals or litres / kWHr 

P2 Power, KW 

IO.Unit._1.BottomBoard.Power._2.Power 

Analog 
Input 87 

Input 
Register 
159 

 

P2 power factor 

IO.Unit._1.BottomBoard.Power._2.PowerFactor 

Analog 
Input 88 

Input 
Register 
160 

 

P2 Energy, KWHr, 
yesterday 

IO.Unit._1.BottomBoard.Power._2.EnergykWh 

Analog 
Input 89 

Input 
Register 
161 

To capture energy used yesterday (for daily analysis) use 
IO.Unit._1.BottomBoard.Power._2.EnergyYesterdaykWh, which is DNP Frozen 
Counters 134 (no default Modbus equivalent) 

Insulation Resistance of Motor Windings 

P1 IRT 

IO.Unit._1.BottomBoard.Irt._1.Value 

Analog 
Input 165 

 

Value in MOhms 

P2 IRT 

IO.Unit._1.BottomBoard.Irt._2.Value 

Analog 
Input 166 

 

Value in MOhms 

 

 

 

Note 3: 

The default Modbus tag list (as of v1.5.6) does not include scaled level. Level in % is tag: PumpControl.Well._1.CurrentLevel and Modbus Input Register 38. 

To add via the LCD, go to Settings – More – Communications – Modbus – Modbus slave – Input Registers and press Add New. This allows you to choose the Point Number (or accept the default). 
Navigate down to Tag and press Select.  

You are now in the Tag Browser. Navigate through to Pump Control – Well – Well 1 – Scaled Level and press OK. This has now configured a new Modbus analog (input register) as Scaled Level.  

Scaled level has 4 decimal places by default. Therefore, in order to fit this within a 16 bit register (which is all that Modbus supports), this value needs to be scaled. For current level, we scale this by 
10,000 in order to display from 0-100%. For scaled level, you may want to have some decimal places (e.g., 0.00 – 10.00 ft: In this case, the scale factor should be 100). 

 

 

Note 4: 
The default Modbus tag list (as of v1.5.6) does not include pump efficiency. 

To add via the LCD, go to Settings – More – Communications – Modbus – Modbus slave – Input Registers and press Add New. This allows you to choose the Point Number (or accept the default). 
Navigate down to Tag and press Select.  

You are now in the Tag Browser. Navigate through to Motor Protection – Pump – Pump 1 – Efficiency Yesterday and press OK. This has now configured a new Modbus analog (input register) as 
pump efficiency. Use a similar process to add pump 2. 

 

Lobley St SPS SP331 General (Electrical Manual (MPA) Multismart Manual Multitrode System Integrator Guide) General

Q-Pulse Id VM357

Active 26/09/2013

Page 11 of 20

Summary of Contents for MultiSmart

Page 1: ...ntegrator s Guide MultiSmart Pump Station Manager Lobley St SPS SP331 General Electrical Manual MPA Multismart Manual Multitrode System Integrator Guide General Q Pulse Id VM357 Active 26 09 2013 Page...

Page 2: ...tiSmart 14 7 DNP3 configuration 14 7 1 DNP security 14 7 2 Common things to look for in profile document of DNP3 master 14 7 3 Event buffering SOE vs Most Recent 15 7 4 Planning for communications out...

Page 3: ...apparent energy and provides motor protection functions measures insulation resistance via 1000v megger test RTU Modbus master slave DNP3 master slave allowing multiple masters and slaves DNP security...

Page 4: ...Smart TOPServer www softwaretoolbox com multismart The MultiSmart TOPServer provides an OPC server for the MultiSmart tag list greatly speeding up integration into SCADA platforms MultiSmart has succe...

Page 5: ...nd cleared Active is the typical fault state where the fault condition is present Unacknowledged is a very useful fault condition indicating that the fault has occurred the source of the fault has cle...

Page 6: ...ote 1 Level PumpControl Well _1 CurrentLevel or PumpControl Well _1 ScaledLevel Analog Input 10 or Analog Input 12 Input Register 38 or see Note 3 section 5 5 Currentlevel level in ScaledLevel can be...

Page 7: ...dbus tag follow the same process with Modbus instead You are now in the Tag Browser Navigate through to Faults Pump Pump 1 Active and press OK This has now configured a new DNP point to be Pump 1 Any...

Page 8: ...ts Pump _1 CBOffTrip Status Active Binary Input 104 Discrete Input 96 Pump 1 Contactor Auxiliary fault active pump failed to start Faults Pump _1 ContactorAux Status Active Binary Input 98 Discrete In...

Page 9: ...High high level alarm Faults Well _1 HighHighLevel Status Active Binary Input 30 Discrete Input 28 High level alarm Faults Well _1 HighLevel Status Active Binary Input 32 Discrete Input 30 Low level a...

Page 10: ...on If alternation is off i e fixed sequence then Behaviour 1 is the first pump to run Lead pump de activation setpoint PumpControl Behaviour _1 DeactSetPoint Analog Output 20 Holding Register 20 Lag p...

Page 11: ...ows you to choose the Point Number or accept the default Navigate down to Tag and press Select You are now in the Tag Browser Navigate through to Pump Control Well Well 1 Scaled Level and press OK Thi...

Page 12: ...Voltage DCOverVoltage MaxOnTime MaxOffTime PowerFail Overflow PulseStart PulseStop Note 7 Manual mode on the MultiSmart main display is really Semi Auto mode which means that the pump will run in manu...

Page 13: ...or Guide Page 13 of 20 MultiSmart_Integrator_Guide_R01 doc Lobley St SPS SP331 General Electrical Manual MPA Multismart Manual Multitrode System Integrator Guide General Q Pulse Id VM357 Active 26 09...

Page 14: ...with status the MultiSmart slave can be re configured to handle this Change the value to Single bit Bin 7 1 DNP security DNP security is coming soon in v2 0 of MultiSmart which is expected in Q3 2008...

Page 15: ...wing parameters exist Max analog input events Max analog output events Max binary input events Max binary output events Max counter events Max frozen counter events When multiple events occur within a...

Page 16: ...red if a repeater fails then comes back on line 7 5 Multiple DNP slaves It is possible to configure a MultiSmart unit with multiple DNP Slaves This is particularly useful if a redundant communications...

Page 17: ...ly trigger a command to the slave device 7 7 IO and deadbands DNP3 works on reporting change of state Analog values report a change of state when they change outside of their deadband Deadband values...

Page 18: ...are of trying to communicate over the different channels In unsolicited mode in DNP the slaves themselves need configuration In the Advanced screen Show more options needed to be checked Show more opt...

Page 19: ...me When this occurs it will disable unsolicited responses and will activate unsolicited responses for the other slave When the second slave has unsolicited responses enabled if it goes into comms fail...

Page 20: ...le Add the following line to this entry Argument arg l tmp dnps log The entry will now look like this Enable version 00 00 00 module DNPSlave Launch file dnps Argument arg cDNPSlave slave _1 Argument...

Reviews: