Mounting and Connection
1.
Remove the head of the detector by pulling it upwards (2) by turning it (1) up to the short line in the direction of the counterclockwise direction
as seen from the base.
2.
Mount the base using the 2 mounting locations shown.
3.
Make the cable connection according to the following diagram. Make a connection with pole 4 + pole and pole 1 - by taking pole + number 3
from pole 3 of the next detector.
4.
Use the 3 (+) and 2 (-) connections for the remote indicator.
5.
Replace the detector head. Make sure the line on the head matches the long line on the base
6.
Give the detector power from alarm panel. In the absence of an alarm, the LED on the detector indicates that it is operating with a blue color for
approximately 20 seconds. (the first 15 seconds a blue LED lights up in the detector for 5 seconds).
Test
Smoke Test:
For the smoke test, allow the smoke to enter the smoke detection chamber for at least 1 minute with a flammable material or a test aerosol. When
enough amount of smoke enters the chamber, the LED illuminates and reports the alarm.
1.
Remove the smoke source when the alarm condition is reached.
2.
Check that the red LEDs are lit continuously. Reset the detector on the panel.
3.
If the detector does not give an alarm within 1 minute, the detector should go to service.
4.
The system can be activated after the test has been performed.