To Enter In Test Mode
Press Key for 5 sec
- Display Shows
T e S T
2 0 0 0
Where Relay is ON
R
- To exit from test mode, Press key
RLY-ON
RLY-OFF
Ear
th Leak
age Current
Tripping Setting
Set Point
HYST
2.000
1.900
Time
Time
TRIP
RLY-ON
RLY-ON
Delay
Time
Delay
Time
Ear
th Leak
age Current
Tripping Setting
Set Point
To Reset the Relay Contact after tripping two modes are
given.
NOTE: When Leakage Current < Setpoint
1) Auto Reset
Healthy Condition relay mode = ON
Trip Set Point = 2.000 Amp
Hysteresis = 0.100 Amp
Press Key For 2 Sec.
2) Manual Reset
PARAMETER SETTING
TEST MODE
TRIP FUNCTION
RESET FUNCTION
/
/
/
Delay time
Hysterisis
Healthy condition relay mode
Reset Mode
Password Enable/disable
(Auto/Manual)
(Enable/Disable)
ON/OFF
0.001 to 3.000 Amp
Set leakage current
00.00 to 10.00 sec
0.000 to 2.999 Amp
Enter password “123”
Password
O N
Press key
Long Press key
Press key
Press key
Press key
Press key
Press key
Healthy Condition relay mode = ON
Amp
Specifications are subject to change, since development is a continuous process,
So for more updated operating information and Support,
Please contact our Helpline: 9978991474/76/82 or
Email at
Ver:191201
Page -2
Press key to save parameter & exit.
0 0 2 0
p a s s
s e t
d e L y
H Y S
R L Y
M O D E
P A S S
1 2 3
2 0 0 0
0 0 0 0
0 1 0 0
O F F
A U T O
A N L
E N B
d I s
1 0 0 0
(Actual Value of Earth
Leakage Current)
(Set Value of Earth
Leakage Current)
SET
SET
SET
SET
SET
SET
SET
ENT
RST
ENT
RST
TEST
ENT
RST